
7
The default shut-down time is three minutes plus 20 seconds
for a nal purge. The shutdown time can be changed be
scrolling through the menu to this screen.
3.8 PURGE Button
During normal operation the pump automatically cycles when
the reservoir is full.
Press the button to remove condensate manually from
the reservoir.
4 Maintenance
4.1 Air Filter
The Phoenix Dry Max is equipped with a pleated media air
lter that must be checked regularly. The standard lter
is a MERV-10 high efciency lter. Operating the unit with
a dirty lter will reduce the dehumidier’s capacity and
efciency and may cause the compressor to cycle off and on
unnecessarily. The lter can generally be vacuumed clean
several times before needing replacement. Replacement
lters can be ordered from the manufacturer or purchased
locally if available IMPORTANT: DO NOT operate the unit
without the lter or with a less effective lter as the
coils inside the unit could become clogged and require
disassembly to clean.
4.2 Storage
There are two issues to consider when the Phoenix Dry Max
is stored between uses and both pertain to the water trapped
in the unit: damage caused by freezing or biological growth.
The effect of the trapped water can be greatly reduced
if precautions are taken to remove as much as possible
before storage. 1. Use the pump PURGE button to reduce
the water level in the reservoir 2. Walk out the hose to drain
it completely In order to reduce biological growth ush the
unit with a bio-fungicide that is approved for use with copper,
aluminum, polyethylene and ABS. To ush:
1. Run the hose to a drain
2. Plug in the unit but do not turn it on
3. Remove the air lter. Slowly pour a pint of the chemical
through the top so that it drains into the heat exchanger
4. Use PURGE button to remove chemicals in reservoir. Run
PURGE until hose runs dry
5. Walk out hose to drain completely
6. Replace air lter
5 Service
WARNING: Servicing the Phoenix Dry Max with its high
pressure refrigerant system and high voltage circuitry
presents a health hazard which could result in death,
serious bodily injury, and/or property damage. Only
qualified service people should service this unit.
CAUTION: Do not operate unit without the top cover in
place.
CAUTION: Do not operate unit without the top cover in
place.
5.1 Technical Description
The Phoenix Dry Max uses a refrigeration system similar
to an air conditioner’s to remove moisture from incoming
air and to add heat to the air that is discharged. Hot, high
pressure refrigerant gas is routed from the compressor
to the condenser coil. The refrigerant is cooled and
condensed by giving up its heat to the air that is about to
be discharged from the unit. The refrigerant liquid then
passes through a lter/drier and capillary tubing which
cause the refrigerant pressure and temperature to drop.
It next enters the evaporator coil where it absorbs heat
from the incoming air and evaporates. The evaporator
operates in a ooded condition, which means that all the
evaporator tubes contain liquid refrigerant during normal
operation. A ooded evaporator should maintain constant
pressure and temperature across the entire coil, from inlet
to outlet. The mixture of gas and liquid refrigerant enter the
compressor after leaving the evaporator coil. The compressor
evacuates the cool refrigerant gas from the accumulator and
compresses it to a high pressure and temperature to repeat
the process.
5.2 Troubleshooting
No dehumidication, control does not light up and unit will
not turn on from power button.
1. Unit unplugged or no power to outlet
2. Defective control board
3. Loose connection in internal wiring
Some dehumidication, air mover runs continuously but
compressor only runs sporadically.
1. Unit is in defrost cycle, DEFROST light on
2. Defrost thermistor defective or loose
3. Loose connection in compressor circuit
4. Defective compressor overload
5. Defective compressor
6. Defective control board
7. Upper housing is not sealed to lower housing
PURGE