thermastor Ultra Aire DEH 3000 User manual

INSTALLER’S & OWNER’S MANUAL
HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER
Dehumidifier & Ventilation System Controller
Part No. 4028539
© 2008 Therma-Stor LLC •Manual P/N TS-499e 12/12
4201 Lien Rd Madison, WI 53704 •TOLL-FREE 1-800-533-7533 •www.thermastor.com •sales@thermastor.com
DEH 3000
DEH 3000

Table of Contents
1. Contents & Specifications ............................................... 2
2. Installation...................................................................... 2
2.1 Install Instructions ...................................................... 2
2.2 Wiring......................................................................... 3
2.3 Auxiliary Relay, A/C Lockout or Run Central Fan.......... 3
2.4 Dehumidifier, Activate/De-Activate with A/C Unit......... 4
2.5 Testing ....................................................................... 5
2.6 Troubleshooting.......................................................... 5
3. Operation....................................................................... 5
3.1 Display....................................................................... 6
3.2 Setting ....................................................................... 6
3.3 Personal Settings reference........................................ 6
3.4 On/Off and Display items............................................ 6
3.5 Setting Clock Time ..................................................... 6
3.6 Adjusting the Relative Humidity Setpoint..................... 6
3.7 Fan Setting & Operation ............................................. 7
3.8 Damper Operation and Ventilation,
Manual (Hold) mode ......................................................... 8
3.9 Damper Operation and Ventilation,
Programmed Ventilation ................................................... 8
4.0 Temperature Cutout Programming ................................ 9
Warranty........................................................................... 10
Read and Save These Instructions
WARNING! — This symbol means important
instructions. Failure to heed them can result in serious
injury or death.
1. Specifications
Part # (P/N): 4028539.
Model: DEH 3000
Operating Voltage: 24 VAC
Max Current - DMP, COMP, FAN 1 AMP each
Humidity Range/Accuracy: 10 – 95% RH,
±
5%
Auxillary Relay Capacity: 5 Amps, 24VAC
Temp Range/Accuracy: 30°-90°F, 2%
Size: 4.95"L x 1.06"W x 4.19"H
2. Installation
Install the DEH 3000 control panel in a central area of the
structure where it will sense the relative humidity of the
structure accurately. Do not install the control panel where it
may not accurately sense the relative humidity such as near
HVAC supply registers, near exterior doors and windows, or
near a pool or spa. Install in accordance with all applicable
codes and standards.
2.1 Install Instructions
1. Separate the front panel from the back panel by depressing
the middle sections of the top and bottom of the front
panel.
2. Locate the wiring access hole in the wall or other flat
mounting surface. Place the back panel into position and
drill the appropriate mounting holes.
3. Insert the screws and tighten. Level as necessary.
4. Make the electrical connections to the terminals on the
back panel as shown in the applicable wiring diagram (see
Sections 2.2-2.4).
5. Test the installation (see Section 2.5).
2
DEH 3000 Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual
Mounting Hole
Mounting Hole
24 VAC Yellow Wire 24 VAC Red Wire
Damper
White Wire
(Optional. See
warning below)
Dehumidifier
Blue Wire
Fan
Green Wire
ON-Detect
Common
OFF-Detect
Normally Open
Common
Normally Closed
Optional
Use
Optional
Use

3
2.2 Wiring
WARNING! DO NOT ALLOW THE YELLOW
WIRE FROM THE ULTRA-AIRE DEHUMIDIFIER TO CONTACT
THE RED OR WHITE WIRES FROM THE ULTRA-AIRE
DEHUMIDIFIER, DAMAGE TO THE 24-VOLT TRANSFORMER
WILL RESULT.
WARNING! THE REMOTE CONTROL OF THE
ULTRA-AIRE DEHUMIDIFIER OPERATES ON A LOW VOLTAGE
CIRCUIT (24 VAC) AND MUST NEVER CONTACT OR BE
CONNECTED TO A HIGH VOLTAGE CIRCUIT.
WARNING! UNPLUG THE ULTRA-AIRE
DEHUMIDIFIER BEFORE WIRING THE DEH 3000.
The installer must supply all field wiring, including the wiring
between the Ultra-Aire dehumidifier and the DEH 3000. Some
of the control wires leaving the Ultra-Aire may not be used in
some control situations and should be left disconnected with
wire nuts taped onto the stripped ends.
Be sure to consult the electrical schematic in this manual or
the internal electrical box of the Ultra-Aire dehumidifier before
making any control connections.
WARNING! ONLY CONNECT THE WHITE WIRE
TO THE CONTROL IF IT IS WIRED IN A CIRCUIT THROUGH
AN ELECTRIC DAMPER, OTHERWISE TRANSFORMER
DAMAGE MAY RESULT.
The White wire controls the optional motorized damper
that can be installed into a fresh air duct. This damper
provides the ability to control fresh air ventilation using
the ventilation timer function of the DEH 3000 and the
terminal labeled “DMP” on the DEH 3000 (See Section
3.8). Leave the “DMP” terminal unused if a motorized
damper is not used, and cap off the White wire from
the Ultra-Aire dehumidifier.
Standard wire colors for thermostats are as follows:
Description Color Terminal code
24VAC Red R
Call for Heat White W or W1
Force Fan On Green G
Compressor
Call for Cooling Yellow Y or Y1
2.3 Auxiliary relay operation
It may be desirable to coordinate fan operation of the central
heating/cooling system with dehumidifier fan operation. The
DEH 3000 contains a relay that provides this ability.
The relay terminals labeled NC, COM and NO operate according
to the following chart:
FAN COM to NO COM to NC
ON CONNECTED OPEN
OFF OPEN CONNECTED
Common uses (assuming standard thermostat wiring colors as
noted):
Lock-out the A/C during dehumidifier fan operation
This will turn off the A/C whenever the dehumidifier fan runs.
1. Wire the Yellow thermostat terminal to the NC terminal on
the DEH 3000.
DEH 3000 Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual
NO
COM
NC

2. Run the Yellow wire from the A/C unit to the COM terminal
on the DEH 3000.
Energize the A/C central fan during dehumidifier fan
operation
To automatically run the A/C FAN when the dehumidifier
fan runs.
1. Attach a second Green wire to the Green fan wire terminal
on the thermostat.
2. Connect the new Green wire to the COM terminal on the
DEH 3000.
3. Run a wire from the Red terminal on the thermostat to the
NO (Normally Open) terminal on the DEH 3000.
2.4 Dehumidifier lock-OFF or lock-ON:
A/C sensor feature
To automatically activate or deactivate the dehumidifier when
the air conditioner runs.
Activate dehumidification when the air-conditioner
is running
A voltmeter is required for the next steps to ensure the correct
wiring from the A/C transformer is used to set up the Lock-in
dehumidifier function.
1. The common wire from the existing A/C transformer (usually
Black) must be attached to the "COM" sensor terminal
between "ON-D" and "OFF-D" on the DEH 3000.
TIP: The common wire can be identified as the wire
from the A/C transformer that reads 0 volts between it
and the Yellow air conditioning call for cooling wire.The
incorrect wire will give a 20 to 28 volt reading.
2. Another Yellow wire must be added to the thermostat Yellow
terminal and run to the “ON-D” sensor terminal on the DEH
3000.
Deactivate dehumidification when the
air-conditioner is running
A voltmeter is required for the next steps to ensure the correct
wiring from the A/C transformer is used to set up the Lock-out
dehumidifier function.
1. The common wire from the existing A/C transformer
(usually Black) must be attached to the "COM" sensor
terminal between "ON-D" and "OFF-D" on the DEH 3000.
TIP: The common wire can be identified as the wire
from the A/C transformer that reads 0 volts between it
and the Yellow air conditioning call for cooling wire. The
incorrect wire will give a 20 to 28 volt reading.
2. Another Yellow wire must be added to the thermostat
Yellow terminal and run to the “OFF-D” sensor terminal on
the DEH 3000.
4
TO A/C
TO A/C
TO A/C
TO A/C
DEH 3000 Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual
A/C
Unit
Red
Green
Yellow
A/C
Unit
Red
Green
Yellow
A/C
Unit
Red
Green
Yellow
A/C
Unit
Red
Green
Yellow
ON-D
COM
OFF-D

2.5 Testing
Verify the wiring connections.
WARNING! ONLY CONNECT THE WHITE WIRE
TO THE CONTROL IF IT IS WIRED IN A CIRCUIT THROUGH AN
ELECTRIC DAMPER, OTHERWISE TRANSFORMER DAMAGE
MAY RESULT.
After checking the wiring, this short test will confirm proper
hook-up.
1. Install front cover of the DEH 3000; connect the top first,
then the bottom.
2. Plug in the Ultra-Aire dehumidifier. The DEH 3000 should
power up.
3. Turn the DEH 3000 ON by pressing the “ON/OFF” button.
4. Verify dehumidification operation by adjusting the RH
“SETPOINT” to below the “%RH” reading on the display.
Use the down “RH” button. Confirm Ultra-Aire fan and
compressor operation. Both should be ON now.
Increase the RH “SETPOINT” on the display to well above the
“%RH” reading on the display. Press the “RH” up arrow to
increase the RH “SETPOINT”.
After running the dehumidifier compressor the DEH 3000
applies a 10 minute restart lockout on all functions. You will
have to wait for the restart lockout to expire.
5. Verify FAN-only operation:
a. Check the “VENT” mode on the display, it will either
be “CLOSED” or “OPEN”. If it is “CLOSED” go to the
next step. If it is “OPEN”, press and hold the “VENT”
key until “OPEN” flashes on the display, release the key
and then press it one more time. “OPEN” will change to
“CLOSED”. Don’t touch the keys for several seconds until
it stops flashing.
b. Press and hold the “FAN” button until “AUTO” begins
flashing on the display, release it, and then press it again
to switch the fan to the “ON” setting.
c. Confirm that the Ultra-Aire fan is ON. Ultra-Aire
compressor must be OFF. Ventilation damper (if used)
should be CLOSED.
6. Verify optional VENT operation (if electric damper is installed):
a. Press and hold the “FAN” button until “ON” flashes on
the display.
b. Release the “FAN” button, then press it again to switch
fan operation to “AUTO”.
c. Press and hold the “VENT” button until “CLOSED”
flashes on the display.
d. Release the “VENT” button, then press it again to switch
vent mode to “OPEN”.
e. Confirm that the Ultra-Aire fan is ON. Ventilation damper is
OPEN. Ultra-Aire compressor must be OFF.
f. Press and hold the “VENT” button until the “OPEN”
flashes on the display.
g. Release the “VENT” button, then press it again to switch
vent mode to “CLOSED”.
WARNING! DO NOT MAKE ANY OTHER
CONNECTIONS OR TRANSFORMER DAMAGE MAY RESULT.
7. Verify any additional optional control operations such as fan
interlock or A/C lockout.
8. Proceed to the Operation section.
2.6 Troubleshooting
FOR THE HVAC PROFESSIONAL:
n No display on initial start up.
Note: This is often the result of a drained capacitor. The
capacitor will recharge once power is applied or re-applied to
the unit.
– Verify unit has power.
– Turn unit off then on.
– Disconnect the unit from power source then re-apply
power to the unit. Display should now operate.
n Function not working properly.
– Verify wiring.
– Verify voltage with voltmeter.
n Dehumidifier not working properly.
– See chart below:
Wire connections Operation
Yellow & Blue Fan & Compressor
Yellow & Green Fan Only
5
DEH 3000 Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual

FOR INSTALLER & HOMEOWNER:
3. Operation
On the display screen, a solid “O” in front of any of the 3
functions (SETPOINT, VENT, FAN) indicates the function is
operating. A flashing “O” indicates it is in a wait mode and
not available at the moment. No “O” indicates the function is
currently OFF.
Solid “O” before Indicates
SETPOINT Dehumidifier on
VENT Fresh air ventilation cycle in progress
FAN Fan on
Wait mode is a factory-programmed time period meant to
prevent short cycles. This extends the life of the dehumidifier.
When a flashing “O” is encountered, the unit is in wait mode
and IT COULD BE UP TO 10 MINUTES BEFORE OPERATION
RESUMES.
3.1 Display
• Whenever there is power to the control, it will display the time,
the day, % relative humidity, and temperature.
• When the control is actually switched ON, the %RH setpoint,
fan status, run mode (program or hold), and fresh air
ventilation status is displayed.
• When a key is pressed the display will light for approximately
½ a minute.
• The Time and Day is displayed at the top of the screen.
• RH and Temperature are displayed in real time.
• A solid “O” before the SET POINT, VENT, OR FAN indicates the
function is operating.
• A ashing “O” before the SET POINT, VENT, OR FAN indicates
the unit is in wait mode.
3.2 Setting
During the set-up process, if you make a mistake, simply
continue. You can always go back to adjust the settings. If you
leave the control alone and don’t touch any buttons for 10
seconds, the control will remember any changes made and
return to the normal display screen, allowing you to proceed to
the next step.
3.3 Personal Settings reference list
Please record your settings here.
Function Factory setting My Setting
SETPOINT (%RH) 50%
VENT Closed
FAN Auto
TEMP CUTOUT 99°
3.4 On/Off and display items
Press the “ON/OFF” button to turn the system ON or OFF.
When the system is ON, the setpoint, fan status, operation mode
(RUN or HOLD), and fresh air vent status is displayed.
When the system is OFF, the control will display the time, day,
%RH, and temperature.
When the unit is shipped, it is in manual (hold) mode.
3.5 Setting Clock Time
1. Press and hold the “CLOCK” button. The hour display will
flash. Release the button.
2. Use the up/down “RH” buttons to change the value.
3. Press the “CLOCK” button again and the minute display will
flash. Use the “RH” buttons to change the value.
4. Press the “CLOCK” button again and AM or PM will flash.
Use the “RH” buttons to change the value.
6
DEH 3000 Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual

5. Press the “CLOCK” button again and the day display will
flash. Use the “RH” buttons to change the value.
6. Don’t touch any buttons for several seconds until the display
stops flashing, this will save your settings. If you need to
change anything go back to step #1.
3.6 Adjusting the relative humidity “SETPOINT”
The DEH 3000 senses the ambient relative humidity (%RH) of
the space in which it is located, it comes factory preset to hold
50% relative humidity.
The relative humidity “SETPOINT” (desired RH to be
maintained) operates the dehumidifier function of the Ultra-Aire
dehumidifier. It has no effect on the optional VENT (fresh air
ventilation) or FAN (household air recirculation) functions if they
are being used.
Operation
The standard range that the dehumidifier holds around your
“SETPOINT” is 3%. With a setpoint of 50%, the dehumidifier
will run until the relative humidity reaches 47%. The
dehumidifier will then switch off until the relative humidity
reaches 53%.
If the setpoint is higher than the ambient relative humidity, the
space does not need to be dehumidified so the dehumidifier will
not run.
Example: Setpoint: 50% RH
Current condition: 45% RH –The dehumidifier will be off (no “O”
indicator will be displayed).
If your setpoint is below the ambient condition, the dehumidifier
will be on and “O” will display.
Example: Setpoint: 50% RH
Current condition: 55% RH –The dehumidifier will be on (“O”
displayed).
3.7 Fan Setting and Operation
Use the “FAN” button to change the fan operation. There are 2
choices for fan operation: “ON” or “AUTO”. The factory preset
is “AUTO”.
“ON” –The fan in the Ultra-Aire dehumidifier will run
continuously. This does not affect either the dehumidification
or ventilation functions of the system. The system may or may
not be ventilating or dehumidifying while the fan is running. This
setting is commonly used for maximum air filtration and/or air
recirculation.
“AUTO” – Indicates the fan will run when the DEH 3000 calls
for dehumidification or ventilation. If the control has not called
for dehumidification for 3 hours, the control will automatically
run the dehumidifier fan for 10 minutes.
After a dehumidification cycle, the fan automatically shuts off
for 10 minutes. This pause allows the water to drain from the
dehumidifier.
A solid “O” indicates the fan is operating. A flashing “O”
indicates the fan is in a wait mode. No “O” indicates the fan is
OFF.
To set the operation:
1. Press and hold the “FAN” button. The current fan setting will
begin to flash on the display. Release the button.
2. Press the “FAN” button to toggle between the “ON” and
“AUTO” modes.
With the fan in the “AUTO” mode, the fan will operate only
when needed by other functions of the system. The fan will
remain OFF unless the system is dehumidifying or ventilating.
The fan always runs during dehumidification and ventilation and
the fan “O” icon will be lit. To completely turn the system OFF,
use the “ON/OFF” button as described earlier.
7
DEH 3000 Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual

3.8 Damper Operation and Ventilation,
Manual (Hold) Mode
The “VENT” setting controls the ventilation function of the
system. It has no control over the dehumidification function. In
order to provide ventilation, the motorized damper must be open
and the fan must be running. The controller takes care of these
two functions automatically so that whenever the damper is
open, the fan is running.
The ventilation indicator “O” will be displayed whenever the
unit is ventilating. The fan operation indicator “O” will also be lit.
There are three damper operation modes:
1. “OPEN” – hold mode: The damper will be open and the
dehumidifier fan will be continuously operating to introduce
fresh air into the space. Use this mode for continuous fresh
air ventilation. The fan is always on when the damper is open.
2. “CLOSED” – hold mode: The damper will never open, and
the dehumidifier will not ventilate. The fan will still operate
normally for recirculation and dehumidification.
3. “PROGRAMMED” mode: The DEH 3000 will operate the
motorized damper and the dehumidifier fan according to the
programmed ventilation schedule (Section 3.9).
The factory preset for the “VENT” setting is “CLOSED”.
To set “OPEN” – hold or “CLOSED” – hold ventilation
operation:
1. Press the “VENT” button. The current setting will begin to
flash on the display. Release the button.
2. Press the “VENT” button again to switch between “OPEN”
and “CLOSED”.
3. Leave the control alone for 10 seconds and your settings will
be saved.
3.9 Damper Operation and Ventilation,
Programmed Ventilation
This example shows the system in program mode (denoted by
the schedule 15 minutes on, 5 minutes off and the word RUN in
the lower right corner of the display).
The DEH 3000 will operate fresh air ventilation according to your
ventilation program. The control needs to be programmed to
turn the ventilation function ON and OFF at the desired intervals.
This is done by programming the ventilation timer.
There are two programs available for ventilation:
1. Monday through Sunday
2. Monday through Friday & Saturday/Sunday
Each block of days has a morning schedule and a night
schedule. Morning is the first 12 hours of the day and night is
the second 12 hours.
Each schedule has:
• A “START” time when the ventilation schedule begins,
• An “OPEN FOR” duration for the amount of time the damper
stays open in 5 minute intervals, from 0 to 60,
• And “CLOSED FOR” duration which closes the damper for a
specified time in 5 minute intervals from 0 to 60.
Setting the Ventilation Program:
1. Press the “PROGRAM ENTER” button until the following
menu appears:
2. Using the up/down “RH” buttons, highlight “PROGRAM”
and select it by pressing the “PROGRAM ENTER” button.
The following menu appears:
8
DEH 3000 Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual

You can select from:
“MON-FRI” “SAT-SUN” for separate weekday and weekend
schedules, or “MON-SUN” which gives you equal weekday and
weekend schedules.
3. Using the Up/Down “RH” buttons, highlight and then select
one of the two choices. The example given shows how to
program separate weekday and weekend schedules. The same
method is used if you choose the other program.
Example: menu when you select “MON-FRI” “SAT-SUN”:
1. Enter the starting time for weekdays using the up/down “RH”
buttons to change the time.
2. Press the “PROGRAM ENTER” button to switch to the
“OPEN FOR” setting. Using the up/down “RH” buttons,
change the duration that the damper will ventilate fresh air.
3. Press the “PROGRAM ENTER” button to switch to the
“CLOSED FOR” setting. Using the up/down “RH” buttons,
change the duration that the damper will remain closed
between ventilation cycles.
For the example given, starting at 8:00AM in the morning, the
control will ventilate fresh air for 15 minutes then stop for 15
minutes. This schedule of 15 minutes open, 15 minutes closed
will continue until the start time of the night schedule.
Morning schedule is available anytime from 12:00AM until
11:59AM.
Night schedule is available anytime from 12:00PM until
11:59PM.
4. Press “PROGRAM ENTER” again to go to the “MON-FRI”
night schedule. Repeat the steps listed above for this and the
“SAT-SUN” day and night schedules.
When you have finished programming your schedule (either the
7-day version or the weekday/weekend split version), use the
down “RH” button to highlight the EXIT option and then press
“PROGRAM ENTER” to select it.
Running the Ventilation Program
Press and hold the “PROGRAM ENTER” button until the
“PROGRAM” screen appears.
Use the down “RH” button to highlight “RUN PROGRAM”:
Then press “PROGRAM ENTER” to select it. The display will
appear as follows:
4.0 Temperature Cutout Programming
Dehumidifiers produce heat when dehumidifying and depending
upon outside conditions, the ventilation function may also
introduce warm air. Some conditions may introduce enough
heat to drive household temperatures up. The DEH 3000
temperature cutout feature disables all Ultra-Aire operations if
household temperatures reach the cutout setpoint.
In most installations this feature will not need to be used (the
cutout is factory set to 99°F). If a lower temperature cutout
is desired, program the setpoint by pressing and holding the
“PROGRAM ENTER” button until the “PROGRAM” screen
appears. Press the up/down “RH” buttons until “TEMP
CUTOUT” highlighted. Then press the “PROGRAM ENTER”
button again to select it. Now use the “RH” up or “RH” down
buttons to adjust the setpoint. Press “PROGRAM ENTER” to
return to the home screen.
9
DEH 3000 Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual

10
WARRANTOR:
Therma-Stor LLC
4201 Lien Rd
Madison, WI 53704
Telephone: 1-800-533-7533
WHO IS COVERED: This warranty extends only to
the original residential end-user of the DEH 3000
Dehumidifier & Ventilation System Controller, and may
not be assigned or transferred.
FIRST YEAR WARRANTY: Therma-Stor LLC warrants
that, for one (1) year the DEH 3000 Dehumidifier &
Ventilation System Controller will operate free from any
defects in materials and workmanship, or Therma-Stor
LLC will, at its option, repair or replace the defective
part(s), free of any charge.
END-USER RESPONSIBILITIES: Warranty service must
be performed by a Servicer authorized by Therma-Stor
LLC.If the end-user is unable to locate or obtain warranty
service from an authorized Servicer, he should call
Therma-Stor LLC at the above number and ask for the
Therma-Stor LLC Service Department, which will then
arrange for covered warranty service. Warranty service
will be performed during normal working hours.
The End-user must present proof of purchase (lease)
upon request, by use of the warranty card or other
reasonable and reliable means. The end-user is
responsible for normal care. This warranty only applies
to residential applications and does not cover any
defect, malfunction, etc. resulting from misuse, abuse,
lack of normal care, corrosion, freezing, tampering,
modification, unauthorized or improper repair or
installation, accident, acts of nature or any other cause
beyond Therma-Stor LLC's reasonable control.
LIMITATIONS AND EXCLUSIONS: If any DEH 3000
Dehumidifier & Ventilation System Controller part is
repaired or replaced, the new part shall be warranted
for only the remainder of the original warranty period
applicable thereto (but all warranty periods will be
extended by the period of time, if any, that the DEH
3000 Dehumidifier & Ventilation System Controller is out
of service while awaiting covered warranty service).
UPON THE EXPIRATION OF THE WRITTEN WARRANTY
APPLICABLE TO THE DEH 3000 Dehumidifier &
Ventilation System Controller OR ANY PART THEREOF,
ALL OTHER WARRANTIES IMPLIED BY LAW, INCLUDING
MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE, SHALL ALSO EXPIRE. ALL WARRANTIES
MADE BY THERMA-STOR LLC ARE SET FORTH HEREIN,
AND NO CLAIM MAY BE MADE AGAINST THERMA-STOR
LLC BASED ON ANY ORAL WARRANTY. IN NO EVENT
SHALL THERMA-STOR LLC, IN CONNECTION WITH THE
SALE, INSTALLATION, USE, REPAIR OR REPLACEMENT
OF ANY DEH 3000 Dehumidifier & Ventilation System
Controller OR PART THEREOF BE LIABLE UNDER
ANY LEGAL THEORY FOR ANY SPECIAL, INDIRECT OR
CONSEQUENTIAL DAMAGES INCLUDING WITHOUT
LIMITATION WATER DAMAGE (THE END-USER SHOULD
TAKE PRECAUTIONS AGAINST SAME), LOST PROFITS,
DELAY, OR LOSS OF USE OR DAMAGE TO ANY REAL OR
PERSONAL PROPERTY.
Some states do not allow limitations on how long an
implied warranty lasts, and some do not allow the
exclusion or limitation of incidental or consequential
damages, so one or both of these limitation may not
apply to you.
LEGAL RIGHTS: This warranty gives you specific legal
rights, and you may also have other rights which vary
from state to state.
DEH 3000 Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual
DEH 3000
DE
H 3000
Dehumidifier & Ventilation System Controller

4201 Lien Rd • Madison, WI 53704
Phone: 608-222-5301 • Fax: 608-222-1447
www.thermastor.com • sales@thermastor.com
Information in this document is subject to change without notice. No part of
this document may be reproduced or transmitted in any form or by any means,
electronic or mechanical, for any purpose, without the express written permission
of Therma-Stor LLC. © 2007 Therma-Stor LLC. All rights reserved.
DEH 3000 Dehumidifier & Ventilation System Controller Installation, Operation & Service Manual
Table of contents
Other thermastor Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

SMA
SMA TEMPSENSOR-AMBIENT installation guide

Trane Technologies
Trane Technologies X1351152701 Installation, operation and maintenance

Viessmann
Viessmann OpenTherm operating instructions

dixell
dixell XW20K Installing and operating insructions

Full Gauge Controls
Full Gauge Controls MT-511C Guide book

Arico
Arico tc5f user manual