TIME MARK 850 User manual

ll Continuous or Pulse Modes
ll AC or DC Versions
ll Socket-Mounted Design
ll 5-Year Unconditional Warranty
DESCRIPTION
The Model 850 Two Hand Control Module is designed to be
used with two palm or pushbutton switches, which must be
closed within 0.5 seconds of each other to operate machinery.
As long as both switches are pressed, the relay will remain
energized in the continuous mode.
For applications requiring a pulse to initiate operations, the
Model 850 can be set to produce a pulse output by connecting
a resistor to pins 4 and 7. The resistor value in ohms should be
100,000 times the desired time in seconds (R=100,000 x T).
The internal relay de-energizes on completion of the pulse,
even if both switches are depressed. The relay de-energizes
immediately,if either hand switch is released, in standard or
pulsed mode.
The compact size of the Two-Hand Control Module allows
installation into an existing control panel. It can be used with
any type of machinery requiring safe, two-handed operation
such as presses, punches, cutters, etc. The standard nominal
supply voltages are 120VAC, 240VAC, 24VAC, 24VDC.
Other voltage versions may be available by special request.
SPECIFICATIONS
MODEL 850-120VAC 850-240VAC 850-24VAC 850-24VDC
Supply Voltage 120VAC 240VAC 24VAC 24VDC
Max. Input Voltage 135VAC 265VAC 28VAC 28VDC
Min. Input Voltage 105VAC 215VAC 22VAC 22VDC
Power Consumption 2 W
Transient Protection 2500V FOR 10 msec
Pulse Time/Resistance Minimum: 50 msec/5K ohms
Maximum: 10 sec/1 megohm
Input Switch Resistance 100 ohms max.
Expected Relay Life Mech: 10 million operations
Elec: 100,000 operations at rated load
Contact Rating SPDT 10A at 240VAC resistive
Operating Temperature -40º to +131º F
Humidity Tolerance 0 -97% w/o condensation
Case Material ABS plastic
Weight 5 oz.
Mounting 11-pin socket (*not included)
* order 11-pin socket number 51X016
2.88"
0.65"
1.75"
2.44"
DIMENSIONS
MODEL 850
Two-Hand
Control Module
Both Hand
Switches-CLOSED
Output
STANDARD OPERATION
(without resistor)
PULSED OUTPUT OPERATION
(with resistor)
Output
Both Hand
Switches-CLOSED
OPERATIONS
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A419 12/00
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116

MODEL 850 Two-Hand Control Module
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 850.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
PIN CONNECTIONS
The Model 850 Two Hand Control Module requires a
standard 11-pin socket for mounting and uses a
standard pin configuration. Refer to the pin diagram
below, or on the control module for pin connections.
PIN DIAGRAM
TROUBLESHOOTING
Should the Model 850 fail to operate properly, check
that the operating voltage is present and of the correct
level. Check all fuses and verify that all wiring
connections are correct. Should problems persist,
contact the manufacturer for assistance.
WARRANTY
The Model 850 Two-Hand Control Module is covered
by Time Mark Corporation’s exclusive 5-Year
Unconditional Warranty. Should this device fail, for
any reason, within five years from the date of purchase,
we will repair or replace it free. Contact the Time Mark
Sales department, Monday through Friday; 8 a.m. to 5
p.m., CST, for further details.
OPERATIONS
Both Hand
Switches-CLOSED
Output
STANDARD OPERATION
(without resistor)
PULSED OUTPUT OPERATION
(with resistor)
Output
Both Hand
Switches-CLOSED
1
2
3
4
567
8
9
10
11
INSTALLATION
Mount the module’s socket in a suitable enclosure.
Connect AC operating power, two switches and the load
to the appropriate socket terminals referring to the pin
diagram.
For pulsed operation–Install a resistor across terminals
4 and 7. The resistor should be 100k Ωfor each 1 sec-
ond of delay required (example: 50k Ωfor a 0.5 second
delay).
Install the module in the socket and apply power.
NOTE: When installing the Model 850 Module in areas of
high humidity or contamination, it is recommended that the
base area and all exposed metal parts of the socket be
coated liberally with a good quality silicon grease, such as
Dow Corning DC-4 or DC-4X. Insert the unit into the socket
and wipe off excess grease around the base. This will prevent
the entrance of moisture and other contaminates into the
base and socket areas.
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A419 12/00
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116
Shows No Power
Applied

SPECIFICATIONS
MODEL 295-120 295-240
Nominal input voltage 120 VAC 240 VAC
Input voltage range 90 -120 VAC 190 -240 VAC
Output voltage 170 VDC 339VDC
Frequency range 50 -400 Hz
Operating temperature -40º to +131º F
Humidity tolerance 0-97% w/o condensation
Case material 20 Gauge CRS
Mounting Surface
Weight 2 lbs.
DIMENSIONS
2.80"
1.44"
1.25"
2.58" .37" dia
3.25"
5.53"
6.25"
7.0"
1 2 3 4
Model 295-240
2.80"
1.44"
1.25"
2.58"
3.25"
6.87"
.37" dia
7.56"8.37"
1 2 3 4
Model 295-120
TYPICAL APPLICATION
Model
295
Control Relay or Phase
Loss Monitor contacts
1 2 3 4
L1
L2
L3
Shunt
Trip
Breaker
ll Discharge Manually
or with a Control Device
ll 120 and 240 Volt Versions
MODEL 295
Capacitor
Trip Device
DESCRIPTION
The Model 295 Capacitor Trip Device is used to trip
circuit breakers by using the stored energy in a capacitor.
The capacitor is kept at full charge during normal operation
by a half-wave silicon rectifier which draws its energy from
the power line.
When completely discharged, the Model 295 draws
approximately 10 amps from the line in the first half cycle,
3 amps the second half cycle and 1 amp from the third.
Continuous current required to keep the capacitor charged
is less than 5 milliamps.
The capacitor holds sufficient charge to trip the breaker for
at least 12 seconds after the charging voltage is removed.
However, on most fault conditions, some voltage is still
present, so the Model 295 is designed so that 65% of
normal voltage gives sufficient charge to trip the breaker.
A low-energy lamp, connected in parallel with the storage
capacitor, gives a visual indication when the voltage
charge is 85 volts or more on the 120V version and 170
volts or more on the 240V version.
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A129 12/00
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116

INSTALLATION
Connect the control wiring to the terminals with the
contact markings (refer to the diagram on the unit).
Apply power.
ADJUSTMENT
No calibration or adjustments are needed for this
device.
TROUBLESHOOTING
Should the Model 295 Capacitor Trip Device fail to
operate, check all connections. Verify that power is
present, and check all fuses. Should problems persist,
contact the factory at 800-862-2875 for assistance.
The following graph shows the energy from the Model
295 in Watt-Seconds (WS).
The horizontal axis represents the input voltage (VAC)
with the corresponding output voltage (VDC).
WARRANTY
The Model 295 Capacitor Trip Device is warranted to
be free from defects in materials and workmanship for
one year. Should this device fail to operate, we will
repair or replace it for one year from the date of
purchase. For complete warranty details, see the
Terms and Conditions of Sales page in the front section
of the Time Mark catalog.
TYPICAL APPLICATION
Model
295
Control Relay or Phase
Loss Monitor contacts
1 2 3 4
L1
L2
L3
Shunt
Trip
Breaker
Energy from Capacitor Trip Device
VAC Input
(VDC Output)
Energy(watt-seconds)
0
5
10
15
20
25
30
60 80 100 120
(170) 140
(198) 160
(226) 180
(255) 200
(283) 220
(311) 240
(339)
6.1 ws
7.2 ws
24.1 ws
28.7 ws
26.8 ws
14 ws
31.8 ws
Energy=/ CE
122
Model
295-120 Model
295-240
MODEL 295 Capacitor Trip Device
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 295.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A129 12/00
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116

ll Self-contained standby power source
ll Maintains full operating voltage
for a minimum of two days
ll Discharge manually,
or with an external control device
DESCRIPTION
The Model 410 Auto-Charged Capacitor Trip Device is
a high speed capacitor-type circuit breaker tripping unit. It
differs from the conventional capacitor trip device in that it
has a self-contained standby power source, which is
capable of maintaining full operating voltage for several
days.
This device is primarily for use with circuit breakers which
require some form of AC power for their closing operation;
i.e., circuit breakers having either a stored energy closing
mechanism with an AC-operated release coil, or an AC
solenoid-operated closing mechanism. There are no field
adjustments required.
The Model 410 has a cover-actuated safety switch, which
discharges the capacitor and disconnects the primary
source when the cover is removed.
The Model 410 can be tripped manually, or by means of a
voltage-sensing or phase loss monitor. Versions are
available for 120 vac or 240 vac operations.
SPECIFICATIONS
Model 410-120 410-230
Nominal AC voltage(phase to phase) 120 VAC 208/230 VAC
Input voltage range 108-132 VAC 216-264 VAC
Frequency 60 Hz 60 Hz
Battery 4,000ma hour, 1.2v, ‘D’ cell NiCad
(user replaceable)
Output voltage 380 VDC minimum
Output power 28.7 watt seconds
Operating temperature -40° to +131° F
Humidity tolerance 0 -97% w/o condensation
Case material 20 gauge CRS
Mounting Surface
Weight 3.2 lbs
Agency approval UL Recognized
DIMENSIONS
"
""
"
""
TYPICAL APPLICATION
Model 410
EnableEnable
22
44
33
11
Power
Fail
Relay
Shunt
Trip
Breaker
LoadLoad
AC Input
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A130 12/00
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116
MODEL 410
Auto-Charged
Capacitor Trip Device

PRE-INSTALLATION CHECK
The energy storage capacitor used in the Model 410 is a
special high grade, low leakage, industrial type electrolytic
capacitor. One trait of any electrolytic capacitor is the
tendency to change characteristics when left de-energized
for extended periods.
Although these units have been completely tested at the
factory, they may be stored for a considerable length of
time. To insure proper performance, it is highly recom-
mended that this unit be energized from the power source
for a minimum two hours just before putting it into
operation. This will insure that the unit will operate at
maximum efficiency.
CHECK THE BATTERY. If the battery has run down, it is
best to replace it, or to re-charge it EXTERNALLY, before
installation.
INSTALLATION
Before putting the Model 410 into service, it should be
examined carefully to make certain that the unit has not
been damaged during shipment.
Verify that the supply voltage is of the proper value and
frequency (see Specifications table).
Mount the Model 410 in the desired location.
Connect the operating power source and output tripping
circuit (refer to Typical Application example).
CAUTION
The Model 410 uses a half-wave rectifier circuit to
charge the energy storage capacitor from the source.
With this type of circuit, it is important that no load be
placed across the energized capacitor (pins 1 & 3).
Should this occur, no charge can be built up across
the capacitor; the rectifier and current limiting resistor
will then be subjected to prolonged, excessive current
resulting in their DESTRUCTION.
Under normal operating conditions, the capacitor is protected
from damage since it’s source is applied from either the
battery and it’s associated circuitry, or from the circuit breaker,
thus keeping all loads from the capacitor. There is ample time
during a circuit breaker closing operation for the capacitor to
charge since it requires only 3 cycles for the unit to reach 90%
(applies to 240vac only) of full charge.
During testing of the unit, with it’s associated circuit
breaker, care should be exercised not to have the tripping
circuit completed while applying AC voltage to a
discharged unit.
OPERATION AND MAINTENANCE
The operation of the Model 410 is completely automatic, requiring
only an occasional check to determine if the unit is functioning
properly. A front panel neon light and rocker switch are supplied
for this purpose. If the voltage across the capacitor is above the
minimum required to operate the breaker, the light will glow when
the test button is pressed. This indicates the readiness of the unit
to trip the breaker,but it does not indicate the status of the
external power source, or the internal battery circuit.
FIELD SERVICE AND ADJUSTMENT
The Model 410 has been completely checked and adjusted at
the factory. It is advisable not to disturb these adjustments. If
for any reason the unit fails to operate properly, it should be
returned to the factory for repair, or re-calibration.
REPAIRS
The Model 410 Auto-Charged Capacitor Trip Device is not
field repairable. Should this unit require repairs, call Time
Mark Corporation at 800-862-2875 (8 a.m. to 5 p.m. CST) for
instructions on returning it to the factory for service.
WARRANTY
The Model 410 Auto-Charged Capacitor Trip Device is war-
ranted to be free from defects in materials and workmanship
for one year. Should this device fail to operate, we will repair
or replace it for one year from the date of purchase. For com-
plete warranty details, see the Terms and Conditions of Sales
page in the front section of the Time Mark catalog.
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A130 12/00
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116
MODEL 410 Auto-Charged Capacitor Trip Device
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 410.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions

ll Adjustable Current Level
ll Up to 5 Forward-Reverse Cycles
ll Push-button Simulator/Tester
MODEL 412
Automatic Reverse
Controller
Model 412
Nominal Input Voltage 120VAC ±10% 50/60 Hz
Power Consumption less than 2 watts
Input Currents 5 amps at 480VAC 3-phase
10 amps at 240VAC 3-phase
(a CT must be used with higher currents)
Transient Protection 2500 VRMS for 10 msec
Cycles 0 to 5 cycles user-selectable
Full Cycle Period 7 seconds
Reverse Cycle Time 0.5 seconds
Contacts SPDT 10 amps at 240VAC resistive
Expected Relay Life Mech: 10 million operations
Elec: 100,000 operations at rated load
Operating Temperature -40º to +140º F
Humidity Tolerance 0-97% w/o condensation
Enclosure Material 20 gauge CRS
Weight 2.3 lbs
SPECIFICATIONS
DESCRIPTION
The Model 412 Automatic Reverse Controller is a
current sensor designed to detect jamming of sewage
grinders, and to initiate the reversing of the grinder.
This controller allows the selection of up to 5 forward/
reverse cycles, and provides for an alarm output if the
number of cycles is exceeded.
The current loop inputs are designed for direct
connection of 10 amps at 240VAC, or 5 amps at
480VAC (up to 2 hp motors). For higher currents, a
current transformer (CT) must be used (CT
secondaries are connected to the 5 amp terminals,
regardless of voltage).
A push-button is used to simulate an over-current
condition and to test the relay contacts and alarm. A
current level adjustment is used to optimize the trip
point setting. LED indicators show the running direction
of the motor and the alarm condition.
OPERATION
When operating the Model 412 in the forward mode, an
over-current condition of a half second will cause the
START contact to open for 3 seconds. The FWD/REV
contact switches to REV and the START contact re-
closes. One half second later the START contact opens
and the FWD/REV contact switches to FWD. Three
seconds later the START contact will close.
If the over-current condition persists, this sequence
repeats for the number of cycles selected. After the last
cycle, the START contact opens and the ALARM
contact closes. The controller is locked out and must be
reset by removing and re-applying the operating
voltage.
DIMENSIONS
0.187
dia. typ.
4.0"
7.0"
2.0"
2.8"
5.0"
7.6"
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A185 12/00
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116

TROUBLESHOOTING
Should the Model 412 fail to operate properly, check
that the operating voltage is present and of the correct
level. Check all fuses and verify that allwiring
connections are correct. Should problems persist,
contact the manufacturer for assistance.
WARRANTY
The Model 412 Automatic Reverse Controller is
warranted to be free from defects in materials and
workmanship for one year. Should this device fail to
operate, we will repair or replace it for one year from
the date of purchase. For complete warranty details,
see the Terms and Conditions of Sales page in the
front section of the Time Mark catalog.
INSTALLATION
Mount the Model 412 is a suitable enclosure. Connect
120VAC to the terminals marked SUPPLY.
Refer to marking on the unit and in the Typical
Application diagram on this sheet for control circuit
connections.
MODEL 412 Automatic Reverse Controller
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 412.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
TYPICAL APPLICATION
R1
StartStop
120
VAC
Motor
F
F
F
O/L's
R
R
R
L2
L3
L1
AC CT
FR
CT
Start Alarm
R1
FR
Shows No Power Applied
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A185 12/00
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116

MOTOR
4-20mA
OUTPUT
REVERSE WIRES TO CT
IF MOTOR FAILS TO RUN
FOR MORE THAN THE INITIAL
2 SECOND PERIOD.
MODEL 276A-
xx
L1
L2
MANUAL
RESTART
120VAC
COIL
DESCRIPTION
The Model 421 Over/Under Motor Load Monitor
detects an overload or underload condition on all types
of running motors: conveyer motors, elevator motors,
mixer motors, submersible pumps, etc.
This Monitor detects the actual power used (voltage x
current xpower factor) and is more sensitive than
simple current monitors. The 421 can be used with
single phase motors or, using the Model 276C current
transducer, with three-phase motors. Matching CT’s
allow the Model 421 to be used with most motor sizes.
Optional trip and restart delays are provided.
DIMENSIONS
TYPICAL APPLICATION -single-phase monitoring
C
L
3.88"
3.0"
0.44"
3.03" Holes are symetrical
about center line.
0.203" 4 PL.
5.5" 6.06" 0.55"
2.63"
0.28"
SPECIFICATIONS
Model 421
Input Voltage Range 100-130 VAC or 200-250 VAC
Frequency 50/60 Hz
Power Consumption 0.5 VA max.
Nominal Current 2.5 amps
Minimum Current 0.25 amps
Current Adjustment 0-5 amps xPF
Current Output 4-20mA for chart recorders
Repeat Accuracy 1 % (fixed conditions)
Output SPDT 10 A at 240 VAC resistive
Expected Relay Life Mech: 10 million operations
Elec: 100,000 operations at rated load
Trip Delay OFF or 0.3 to 180 seconds
Restart Delay OFF or 0.1 to 4 hours
Indicators Red LED: Overload or Underload; tripped
Yellow LED: Restart timing
Transient Protection 2500V for 10 msec
Operating Temp -40º to 131º F
Humidity Tolerance 97% w/o condensation
Enclosure Material ABS plastic
Weight 1 lb.
Agency Approvals UL Listed to US and Canadian safety
standards CSA Certified
MODEL 421
Over/Under
Motor Load Monitor
ll Monitors True Motor Power
(volts xcurrent xpower factor)
ll Detects Motor Overload or Underload
ll Operates on 120 or 240 VAC,
Single-phase or 3-phase
ll Built-in Trip and Restart Delay Options
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A182 12/00 page 1 of 8
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116

Figure 1. RESISTIVE LOAD
With a purely resistive load, the current and voltage
waveforms are occurring simultaneously.
MODEL 421 Over/Under Motor Load Monitor
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
APPLICATION GUIDE
Figure 2. INDUCTIVE LOAD
With an inductive load, the current waveform lags the
voltage waveform by 60°.
The current, as measured with an ammeter, may only
vary a slight amount as the motor changes from a fully
loaded condition to a completely unloaded condition.
This makes it difficult to detect an unloaded condition by
simply monitoring current alone.
To obtain an accurate picture of real power
consumption of any inductive device, such as a motor,
the formula V x A x Cosø = W is used.
The Cosø is a multiplication factor derived from the
number of degrees of lag between the current and
voltage waveforms.
This is called the “power factor” (or “PF”). The power
factor is the natural cosine of the degrees of lag:
GENERAL
This application guide is written for equipment
designers, maintenance personnel, electrical
contractors, etc.
It is intended to aid in the installation of the Model 421
Motor Load Monitor into motor protection systems.
The notes and diagrams deal with methods of protecting
motors in the event of an underload condition or an
overload condition.
THEORY
The need for a system to detect an underload condition
other than by the simple monitoring of current becomes
clear when examining the following waveforms.
In a purely resistive circuit, as in Figure 1, the current
(amps) is directly proportional to the power (watts) being
consumed. To find the power, multiply the voltage
across the load times the current through the load. The
result is in watts (V x A = W).
In Figure 2, When the load is not resistive, but inductive
as it is with a motor, the formula is no longer correct.
The inaccuracy occurs because the current and the
voltage waveforms are not in phase.
The current waveform lags the voltage waveform by as
much as 90 degrees in a completely unloaded
condition, or as little as 5 or 10 degrees in a fully loaded
condition.
Degrees
of lag Power
Factor Degrees
of lag Power
Factor
0 1.000 50 0.643
5 0.996 55 0.574
10 0.985 60 0.500
15 0.966 65 0.423
20 0.940 70 0.342
25 0.906 75 0.259
30 0.866 80 0.174
35 0.819 85 0.087
40 0.766 90 0.000
45 0.707
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A182 12/00 page 2 of 8
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116

MODEL 421 Over/Under Motor Load Monitor
APPLICATION GUIDE
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A182 12/00 page 3 of 8
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116
Example: TRUE POWER CONSUMED BY AN AC
MOTOR
For this example we will use a 3-horsepower, 230 volt,
single phase motor.
Condition 1 represents the motor being used at near full
load, while Condition 2 represents a drop in motor load.
Comparing the results of this example, the motor
current decreased only 10% with a drop of 61% in the
motor load (input power). A drop in motor power
cannot be accurately measured by only monitoring the
current and voltage.
By monitoring the phase relationship and applying the
resultant power factor,an accurate and selective
method of sensing changes in true power consumption
can be obtained.
The Model 421 Monitor is based on the above principal
of detecting the actual power used, and is more
sensitive than simple current monitors.
ADDITIONAL FEATURES
As described previously, the Model 421 would fulfill the
basic requirements in most motor protection control
systems. However, there are situations which would
require the motor to restart automatically after a preset
time.
The Model 421 has an adjustable restart timer for
such applications. This timer has a range of 0.1 to 4
hours. If the restart timer is not needed, turn it off with
DIP switch 2.
If restart timing is needed for an underload condition
only, the overload restart can be turned off with DIP
switch 1.
Resetting the Model 421 is accomplished by cycling the
power off and back on, pressing the RESET button, or
by using the restart timer (DIP switch 2).
Some applications require a trip delay period before
shutting down the motor. The Model 421 has a built-in
trip delay timer. The timing range is from 0.3 to 180
seconds. The trip delay timer can be turned off with
DIP switch 4.
Refer to the chart under INSTALLATION (pg 4) for all DIP
switch settings.
Example: (V x A x Cosø = Watts)
Condition 1
230 volts x 10 amps x 0.985 pf = 2265.5 watts
Condition 2
230 volts x 9 amps x 0.423 pf = 875.6 watts
A 4-20 mA output is provided for monitoring power
consumption. A 4 mA output is equal to 0 watts and a
20 mA output is equal to 600 watts at 120 V or 1200
watts at 240 V.
This signal can be sent to a strip chart recorder, a
process controller, computer, etc.
INPUT CURRENT REQUIREMENTS
The CT input of the Model 421 is the isolated winding of
a small current transformer within the unit. Ideally, the
current range needed should be between 2 and 3.5
amps for a fully loaded motor.
Polarity of the wires connected to the CT terminals is
critical to achieve the correct phase relationship
between the current and voltage waveforms as
described earlier.
This is simple to determine after the installation is
complete (refer to the ADJUSTMENT PROCEDURE, pg
5).
If the full load motor current is 3.5 amps or less, and
the motor is a single-phase type, connect one leg of the
motor current directly into the Model 421.
Figure 3 showsthe Model 276A and Figure 4 shows
the Model 276B Current Transformers, available from
Time Mark.
Figure 3. MODEL 276A CURRENT TRANSFORMER
2.38"
1.95"
1.63" Secondary
Space for Primary turn:
0.25" 0.38"x
1.25"
0.43"
.187" dia.
Secondary terminals
(0 - 5 amps)
Loop one leg of AC
line thru transformer
as shown

276B
50 -500 600 -1200
B = 0.87”B = 0.87”
C = 1.56” C = 2.06”
3.90"
2.00"
0.44"
1.25"
4.50"
3.88"
(2) 0.27" x 0.44" slots B
C
APPLICATION GUIDE INSTALLATION INSTRUCTIONS
Figure 5. CURRENT TRANSFORMER CHART
Single-Phase 3-Phase
HP 120VAC 240VAC 240VAC 480VAC
1/4 276A-10 * *
1/3 276A-15 * *
1/2 276A-15 276A-10 **
3/4 276A-20 276A-10 **
1276A-25 276A-15 276A-10 *
1 1/2 276A-30 276A-15 276A-10 *
2276A-35 276A-20 276A-10 *
3276B-50 276A-25 276A-15 276A-10
5276B-80 276A-40 276A-25 276A-15
7 1/2 276B-150 276B-60 276A-35 276A-20
10 276B-150 276B-75 276A-40 276A-20
15 276B-60 276A-30
20 276B-80 276A-40
25 276B-100 276B-50
30 276B-150 276B-60
40 276B-150 276B-75
50 276B-200 276B-100
60 276B-250 276B-150
75 276B-300 276B-150
100 276B-400 276B-200
125 276B-250
150 276B-300
200 276B-400
250 276B-500
300 276B-600
350 276B-700
400 276B-750
500 276B-1000
* Direct connection to Model 276C (see page 8)
* * Direct connection to Model 422
MODEL 421 Over/Under Motor Load Monitor
3-PHASE INSTALLATION
The basic Model 421 Controller is designed for use with
single-phase motors. However, it can easily be used in
3-phase applications by installing the current cancelling
transformer, Model 276C. The Model 276C (figure 6)
monitors two of the three phases, and cancels the effect
of the current signal in the third phase, which would
otherwise cause a phase shift error in the Model 421.
Figure 6. MODEL 276C
IMPORTANT NOTE:
In 3-phase applications, the current inputs must
come from the same phases providing the voltage
inputs. The applications schematics shown on the
last page describe the interconnections.
INSTALLATION
Mount the Model 421 in the control panel or in a suitable
enclosure. Connect the voltage and current inputs to
the appropriate terminals on the Model 421 Monitor.
If the 4-20mA output is used, connect it across a 300Ω
resistive load. Set the four MODE switches on the
Model 421 according to the chart below. During the
initial setup you may wish to disable all time delays.
After the system is completely installed, a simple test
and adjustment will insure that the polarity and
threshold are correct.
DIP SW MODE ON OFF
1Overload Restart Disabled Enabled
2Restart Delay Enabled Disabled
3Reset Button Enabled Disabled
4Trip Delay Enabled Disabled
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A182 12/00 page 4 of 8
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116
Figure 4. MODEL 276B CURRENT TRANSFORMER
The Current Transformer Chart in Figure 5lists various
models available and is referenced to the horsepower ratings
of single-phase and 3-phase motors.
2.6"
3.6"
.187" dia. typical
4.0"
2.3"
4.6"

ADJUSTMENT
Connect a temporary jumper across the NO contacts on
the Model 421 (this keeps the motor running as the
Model 421 trips off and resets).
With the correct voltage applied to the system, the
motor should start and run continuously. Make sure the
motor is running under it’s normally loaded condition.
With a clamp-type ammeter, measure the current in one
of the wires connected to the CT terminals on the Model
421. A reading between 2 and 3.5 amps should be
measured for best results. This current level can be
changed by exchanging the CT with a different ratio.
Turn the UNDER adjustment through it’s entire range
and find the spot where the UNDERLOAD LED just
illuminates.
Turn the UNDER adjustment until the LED just goes
out. If the UNDERLOAD LED is lit all the time, reverse
the two wires connected to the CT terminals and re-
adjust.
Repeat this procedure for the OVER adjustment. If the
OVERLOAD indicator LED stays on all the time, the
current input may be incorrect. Check the CTs for
proper sizing.
Set the SECONDS adjustment for the appropriate TRIP
delay, and HOURS adjustment for the appropriate
RESTART delay, as required for the application.
Remove the jumper from the NO contacts; the motor
should continue to run. The adjustment is now
complete.
MODEL 421 Over/Under Motor Load Monitor
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 421.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
INSTALLATION INSTRUCTIONS
TROUBLESHOOTING
Should the Model 421 Motor Load Monitor fail to
operate, check all connections to the device and its
control circuits. Insure that the proper voltage and
currents have been applied.
Check all fuses. Should the Model 421 operate
improperly, check that the CT is properly sized. Check
all DIP switch settings. If problems persist, contact the
factory for technical assistance.
OPERATION
When AC voltage is first applied, the output transfers for
approximately two seconds, completing the motor
control circuit and allowing the motor to come up to
speed.
If the power being used is within acceptable limits the
contacts remain energized and the motor continues to
run. If the power drops or rises outside the limits, the
contacts will open.
WARRANTY
The Model 421 Under/Over Motor Load Monitor is
warranted to be free from defects in materials and
workmanship for one year. Should this device fail to
operate, we will repair or replace it for one year from the
date of purchase. For complete warranty details, see
the Terms and Conditions of Sales page in the front
section of the Time Mark catalog.
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A182 12/00 page 5 of 8
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116

MODEL 421 Over/Under Motor Load Monitor
TYPICAL APPLICATIONS
SINGLE-PHASE, 240V, ≥≥ 7.5 HP
THE INFORMATION PRESENTED IN THIS GUIDE IS CORRECT TO THE BEST OF OUR KNOWLEDGE. HOWEVER, TIME MARK CORPORATION
DOES NOT WARRANT THE APPLICATIONS AS OUTLINED NOR MAKE ANY OFFERS THAT THE CIRCUITS ARE FREE FROM PATENT
INFRINGEMENT. TIME MARK CORPORATION RESERVES THE RIGHT TO CHANGE OR ALTER SPECIFICATIONS AT ANY TIME.
SINGLE-PHASE, 120V, < 3 HP
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A182 12/00 page 6 of 8
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116
MOTOR
4-20mA
OUTPUT
REVERSE WIRES TO CT
IF MOTOR FAILS TO RUN
FOR MORE THAN THE INITIAL
2 SECOND PERIOD.
MODEL 276A-xx
L1
L2
MANUAL
RESTART
120VAC
COIL
MOTOR
4-20mA OUTPUT
REVERSE WIRES TO CT
IF MOTOR FAILS TO RUN
FOR MORE THAN THE INITIAL
2 SECOND PERIOD.
MODEL 276B-xx
L1
L2
MANUAL
RESTART
240VAC
COIL

MODEL 421 Over/Under Motor Load Monitor
TYPICAL APPLICATIONS
THE INFORMATION PRESENTED IN THIS GUIDE IS CORRECT TO THE BEST OF OUR KNOWLEDGE. HOWEVER, TIME MARK CORPORATION
DOES NOT WARRANT THE APPLICATIONS AS OUTLINED NOR MAKE ANY OFFERS THAT THE CIRCUITS ARE FREE FROM PATENT
INFRINGEMENT. TIME MARK CORPORATION RESERVES THE RIGHT TO CHANGE OR ALTER SPECIFICATIONS AT ANY TIME.
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A182 12/00 page 7 of 8
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116
3-PHASE, 240V, 1 to 10 HP
SINGLE-PHASE, 240V, 1/2 to 5 HP
4-20mA
OUTPUT
REVERSE WIRES
TO CT IF MOTOR
FAILS TO RUN
FOR MORE THAN
THE INITIAL
2 SECOND PERIOD.
MODEL276C
L1
L2
MANUAL
RESTART
240VAC
COIL
OBSERVE POLARITY
AS SHOWN
USE MODEL 276A-xx
MOTOR
L3
MOTOR
4-20mA OUTPUT
REVERSE WIRES TO CT
IF MOTOR FAILS TO RUN
FOR MORE THAN THE INITIAL
2 SECOND PERIOD.
L1
L2
MANUAL
RESTART
240VAC
COIL
MODEL 276A-xx

MODEL 421 Over/Under Motor Load Monitor
TYPICAL APPLICATIONS
OVER/UNDER LOAD & PHASE LOSS PROTECTION
THE INFORMATION PRESENTED IN THIS GUIDE IS CORRECT TO THE BEST OF OUR KNOWLEDGE. HOWEVER, TIME MARK CORPORATION
DOES NOT WARRANT THE APPLICATIONS AS OUTLINED NOR MAKE ANY OFFERS THAT THE CIRCUITS ARE FREE FROM PATENT
INFRINGEMENT. TIME MARK CORPORATION RESERVES THE RIGHT TO CHANGE OR ALTER SPECIFICATIONS AT ANY TIME.
3-PHASE, 240V, <1 HP
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A182 12/00 page 8 of 8
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116
4-20mA
OUTPUT
REVERSE WIRES
TO CT IF MOTOR
FAILS TO RUN
FOR MORE THAN
THE INITIAL
2 SECOND PERIOD.
MODEL276C
MANUAL
RESTART
120VAC
COIL
MOTOR
OBSERVE POLARITY
AS SHOWN
USE MODEL 276B-
xx
120VAC
480VAC
TIMEMARK
3-PHASEMONITOR
L1
L3
L2
4-20mA
OUTPUT
REVERSE WIRES
TO CT IF MOTOR
FAILS TO RUN
FOR MORE THAN
THE INITIAL
2 SECOND PERIOD.
MODEL276C
L1
L2
MANUAL
RESTART
240VAC
COIL
OBSERVE POLARITY
AS SHOWN
MOTOR
L3

DESCRIPTION
The Model 640 Power Factor Regulator is a monitoring and
control factor correction system. It was designed to help
obtain an improved power factor, with a minimum of added
capacitors. This device uses a unique phase-angle sensing
circuit to monitor the power factor of a 3-phase power line.
The Model 640 automatically responds to changing power
factor by closing or opening the internal relays, which add or
subtract capacitor banks on the line. Although intended for
115VAC 60Hz systems, other voltage or frequency models
may be available.
OPERATION
The Model 640 has a LOW POWER FACTOR control,
adjustable between 0.50 and 0.95. If the power factor drops
below this setting, the unit will begin adding capacitor stages
each 40 seconds, until the high PF setting is reached. The
HIGH POWER FACTOR control is adjustable between 0.80
and 1.00 and should always be set higher than the low setting.
The Model 640 will drop out one stage of capacitors every 40
seconds if the power factor becomes capacitive (or leading too
much capacitance). This continues until the power factor is
again inductive (lagging).
A manual mode allows capacitance to be removed or added at
the push of a button. If the operating voltage is lost or the
input current is too low, all relays will drop out.
Indicator lights on the face of the Model 640 show if the power
factor is inductive or capacitive. Output lights show relay
status. An output is provided to drive a 1 mA DC meter.
Center scale on the meter will indicate a power factor of 1.0; a
left deflection will indicate a capacitive power factor, while a
right deflection will indicate aninductive power factor. Use of
an external meter is optional.
Model 640
Input voltage 115 VAC, 60 Hz
Input current Min: 0.25 to 1A adjustable
Max: 5A continuous
Output contacts 2A at 240VAC resistive
Expected relay life Mech: 10 million operations
Elec: 100,000 at rated load
Adjustment Low: 0.5 to 0.95 PF
High: 0.8 to 1.0 PF
Time delay 40 seconds between steps
Enclosure material 20 gauge CRS
Weight 3.5 lbs
SPECIFICATIONS
ll High accuracy phase-angle sensing
ll Adjustable limits
ll Automatic/manual modes
ll Activated steps indicators
ll Capactive-inductive status LEDs
DIMENSIONS
8.0"
6.0"
.20 dia. typ.
7.5" 8.0"
2.5"
MODEL 640
Power Factor
Regulator
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A205 12/00 page 1 of 4
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116

POWER FACTOR DEFINED
The Power Factor, or PF, is stated as a decimal number
between 0 and 1, and is the cosine of the angle between the
voltage and current wave forms. In AC circuits, power (in
watts) is defined as voltage xcurrent xpower factor. From
this, you can see that with a power factor of 0 there can be no
power, regardless of how large the voltage or current may be.
A normal inductive motor will have a power factor between
0.30 and 0.90, depending on how the motor is loaded.
OPERATING THRESHOLDS
A current threshold adjustment is used to set the point where
the Model 640 will disconnect all of the capacitors. This
current threshold is adjustable between 0.25 and 1.00 amp,
from the current transformer. This threshold sets the point
below which the unit is inoperative. A power loss to the Model
640 will also cause all capacitors to be disconnected.
MANUAL OPERATION
The Model 640 can be operated manually. Capacitor stages
can be added or subtracted with a push button on the front of
the unit.
OPTIONAL DISPLAY METER
A meter signal is provided from the Model 640 for a DC meter
with a 0-1 milliamp movement. The meter calibration will be:
0.1 ma = 0.50 power factor (capacitive)
0.5 ma = 1.00 power factor
0.9 ma = 0.50 power factor (inductive)
The meter output is nonlinear, i.e. 1.00 PF = 0.5 ma DC;
0.5 PF = 0.90 ma DC. Refer to Chart 1. for details.
HOW TO SELECT CAPACITORS
Power factor correcting capacitors and capacitor banks are
normally rated in KVARS. There are three basic steps to
properly size the capacitors to a given application:
Determine present load, measured in KW
Determine present power factor
Determine desired power factor
Using Chart 2. on page 4, locate the original (present) power
factor in the vertical left-hand margin. Locate the desired
(corrected) power factor across the top of the chart.
The correction factor (a three place decimal number) is
denoted at the intersection of the row and column of these two
figures.
The correction factor is next multiplied by the present KW
load. The result is the required capacitor size, stated in KVAR.
Correcting to a power factor of 0.95 is generally considered
optimum; correcting to a leading, or capacitive, condition
should not be attempted.
When the total KVAR requirement is determined, it can be
divided among the six stages of the Model 640, to provide six-
step power factor correction. When installing capacitors,
consult the manufacturer’s literature for fusing and
contactor requirements.
In addition to the capacitors and contactors, a properly sized
current transformer with a minimum burden rating of 2 VA and
a 5 amp secondary is required. You will also need a power
transformer with a 115 VAC secondary at 50 VA minimum.
Proper phasing of CT and the PT is essential. If correction
stages work in reverse, disconnect power and reverse the CT
secondary leads.
TROUBLESHOOTING
Should this regulator fail to operate properly, check that all
voltages are present and of the correct level. Check to see if
all wiring is correct. If problems persist, contact the
manufacturerat 800-862-2875; Monday thru Friday, 8 a.m. to
5 p.m. CST.
WARRANTY
The Model 640 Power Factor Regulator is warranted to be
free from defects in materials and workmanship for one year.
Should this device fail to operate, we will repair or replace it
for one year from the date of purchase. For complete
warranty details, see the Terms and Conditions of Sales page
in the front section of the Time Mark catalog.
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A205 12/00 page 2 of 4
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116
MODEL 640 Power Factor Regulator
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
KEEP THIS DATA SHEET FOR FUTURE REFERENCE
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 640.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions

MODEL 640 Power Factor Regulator
A(L1)
B(L2)
C(L3)
XXX/5 CT
IN PHASE
PT
115VAC
IN PHASE
METER
+_
+
_
NEUT.
N
OPTIONAL
CONNECTION
CONTROL
VOLTAGE
TO OTHER
STAGES
BC
MODEL 640
A6 5 4 3 2 1
FUSE FUSE
ALINE
ALOAD
TYPICAL APPLICATION
Power Factor Capacitive Output
(in mA) Inductive Output
(in mA)
0.40 0.0571877 0.942812
0.45 0.0782908 0.921709
0.50 0.0999998 0.900000
0.55 0.122446 0.877554
0.60 0.145799 0.854201
0.65 0.170277 0.829723
0.70 0.196180 0.803820
0.75 0.223936 0.776064
0.80 0.254201 0.745799
0.85 0.288078 0.711922
0.90 0.327720 0.672280
0.95 0.378701 0.621299
1.00 0.500000 0.500000
Chart 1. METER READING vs. POWER FACTOR
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A205 12/00 page 3 of 4
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116

CHART 2. KW multipliers to determine capacitor kilovars required for power factor correction.
MODEL 640 Power Factor Regulator
ORIG
PF 0.80 0.81 0.82 0.83 0.84 0.85 0.86 0.87 0.88 0.89 0.90 0.91 0.92 0.93 0.94 0.95 0.96 0.97 0.98 0.99 1.00
0.50 0.982 1.008 1.034 1.060 1.086 1.112 1.139 1.165 1.192 1.220 1.248 1.276 1.306 1.337 1.369 1.403 1.440 1.481 1.529 1.589 1.732
0.51 0.937 0.962 0.989 1.015 1.041 1.067 1.094 1.120 1.147 1.175 1.203 1.231 1.261 1.292 1.324 1.358 1.395 1.436 1.484 1.544 1.687
0.52 0.893 0.919 0.945 0.971 0.997 1.023 1.050 1.076 1.103 1.131 1.159 1.187 1.217 1.248 1.280 1.331 1.351 1.392 1.440 1.500 1.643
0.53 0.850 0.876 0.902 0.928 0.954 0.980 1.007 1.033 1.060 1.088 1.116 1.144 1.174 1.205 1.237 1.277 1.308 1.349 1.397 1.457 1.600
0.54 0.809 0.835 0.861 0.887 0.913 0.939 0.966 0.992 1.019 1.047 1.075 1.103 1.133 1.154 1.196 1.230 1.267 1.308 1.356 1.416 1.559
0.55 0.769 0.795 0.821 0.847 0.873 0.899 0.926 0.952 0.979 1.007 1.035 1.063 1.093 1.124 1.156 1.190 1.227 1.268 1.316 1.376 1.519
0.56 0.730 0.756 0.782 0.808 0.834 0.860 0.887 0.913 0.940 0.968 0.996 1.024 1.054 1.085 1.117 1.151 1.188 1.229 1.277 1.337 1.480
0.57 0.692 0.718 0.744 0.770 0.796 0.822 0.849 0.875 0.902 0.930 0.958 0.986 1.016 1.047 1.079 1.113 1.150 1.191 1.239 1.299 1.442
0.58 0.655 0.681 0.707 0.733 0.759 0.785 0.812 0.838 0.865 0.893 0.921 0.949 0.979 1.010 1.042 1.076 1.113 1.154 1.202 1.262 1.405
0.59 0.619 0.645 0.671 0.697 0.723 0.749 0.776 0.802 0.829 0.857 0.885 0.913 0.943 0.974 1.006 1.040 1.077 1.118 1.166 1.226 1.369
0.60 0.583 0.609 0.635 0.661 0.687 0.713 0.740 0.766 0.793 0.821 0.849 0.877 0.907 0.938 0.970 1.004 1.041 1.082 1.130 1.190 1.333
0.61 0.549 0.575 0.601 0.627 0.653 0.679 0.706 0.732 0.759 0.787 0.815 0.843 0.873 0.904 0.936 0.970 1.007 1.048 1.096 1.156 1.299
0.62 0 516 0.542 0.568 0.594 0.620 0.646 0.673 0.699 0.726 0.754 0.782 0.810 0.840 0.871 0.903 0.937 0.974 1.015 1.063 1.123 1.266
0.63 0.483 0.509 0.535 0.561 0.587 0.613 0.640 0.666 0.693 0.721 0.749 0.777 0.807 0.838 0.870 0.904 0.941 0.982 1.030 1.090 1.233
0.64 0 451 0.474 0.503 0.529 0.555 0.581 0.608 0.634 0.661 0.689 0.717 0.745 0.775 0.806 0.838 0.872 0.909 0.950 0.998 1.068 1.201
0.65 0.419 0.445 0.471 0.497 0.523 0.549 0.576 0.602 0.629 0.657 0.685 0.713 0.743 0.774 0.806 0.840 0.877 0.918 0.966 1.026 1.169
0.66 0.388 0.414 0.440 0.466 0.492 0.518 0.545 0.571 0.598 0.626 0.654 0.682 0.712 0.743 0.775 0.808 0.846 0.887 0.935 0.995 1.138
0.67 0.358 0.384 0.410 0.436 0.462 0.488 0.515 0.541 0.568 0.596 0.624 0.652 0.682 0.713 0.745 0.779 0.816 0.857 0.905 0.965 1.108
0.68 0.328 0.354 0.380 0.406 0.432 0.458 0.485 0.511 0.538 0.566 0.594 0.622 0.652 0.683 0.715 0.749 0.786 0.827 0.875 0.935 1.078
0.69 0.299 0.325 0.351 0.377 0.403 0.429 0.456 0.482 0.509 0.537 0.565 0.593 0.623 0.654 0.686 0.720 0.757 0.798 0.846 0.906 1.049
0.70 0.270 0.296 0.322 0.348 0.374 0.400 0.427 0.453 0.480 0.508 0.536 0.564 0.594 0.625 0.657 0.691 0.728 0.769 0.817 0.877 1.020
0.71 0.242 0.268 0.294 0.320 0.346 0.372 0.399 0.425 0.452 0.480 0.508 0.536 0.566 0.597 0.629 0.663 0.700 0.741 0.789 0.849 0.992
0.72 0.214 0.240 0.266 0.292 0.318 0.344 0.371 0.397 0.424 0.452 0.480 0.508 0.538 0.569 0.601 0.635 0.762 0.713 0.761 0.821 0.964
0.73 0.186 0.212 0.238 0.264 0.290 0.316 0.343 0.369 0.396 0.424 0.452 0.480 0.510 0.541 0.573 0.607 0.644 0.685 0.733 0.793 0.936
0.74 0.159 0.185 0.211 0.237 0.263 0.289 0.316 0.342 0.369 0.397 0.425 0.453 0.483 0.514 0.546 0.580 0.617 0.658 0.706 0.766 0.909
0.75 0.132 0.158 0.184 0.210 0.236 0.262 0.289 0.315 0.342 0.370 0.398 0.426 0.456 0.487 0.519 0.553 0.590 0.631 0.679 0.739 0.882
0.76 0.105 0.131 0.157 0.183 0.209 0.235 0.262 0.288 0.315 0.343 0.371 0.399 0.429 0.460 0.492 0.526 0.563 0.604 0.652 0.712 0.855
0.77 0.079 0.105 0.131 0.157 0.183 0.209 0.236 0.262 0.289 0.317 0.345 0.373 0.403 0.434 0.466 0.500 0.537 0.578 0.626 0.685 0.829
0.78 0.052 0.078 0.104 0.130 0.156 0.182 0.209 0.235 0.262 0.290 0.318 0.346 0.376 0.407 0.439 0.473 0.510 0.551 0.599 0.659 0.802
0.79 0.026 0.052 0.078 0.104 0.130 0.156 0.183 0.209 0.236 0.264 0.292 0.320 0.350 0.381 0.413 0.447 0.484 0.525 0.573 0.633 0.776
0.80 0.000 0.026 0.052 0.078 0.104 0.130 0.157 0.183 0.210 0.238 0.266 0.294 0.324 0.355 0.387 0.421 0.458 0.499 0.547 0.609 0.750
0.81 0.000 0.026 0.052 0.078 0.104 0.131 0.157 0.184 0.212 0.240 0.268 0.298 0.329 0.361 0.395 0.432 0.473 0.521 0.581 0.724
0.82 0.000 0.026 0.052 0.078 0.105 0.131 0.158 0.186 0.214 0.242 0.272 0.303 0.335 0.369 0.406 0.447 0.495 0.555 0.698
0.83 0.000 0.026 0.052 0.079 0.105 0.132 0.160 0.188 0.216 0.246 0.277 0.309 0.343 0.380 0.421 0.469 0.529 0.672
0.84 0.000 0.026 0.053 0.079 0.106 0.134 0.162 0.190 0.220 0.251 0.283 0.317 0.354 0.395 0.443 0.503 0.646
0.85 0.000 0.027 0.053 0.080 0.108 0.136 0.164 0.194 0.225 0.257 0.291 0.328 0.369 0.417 0.477 0.620
0.86 0.000 0.026 0.053 0.081 0.109 0.137 0.167 0.198 0.230 0.264 0.301 0.342 0.390 0.450 0.593
0.87 0.000 0.027 0.055 0.083 0.111 0.141 0.172 0.204 0.238 0.275 0.316 0.364 0.424 0.567
0.88 0.000 0.028 0.056 0.084 0.114 0.145 0.177 0.211 0.248 0.289 0.337 0.397 0.540
0.89 0.000 0.028 0.056 0.086 0.117 0.149 0.183 0.220 0.261 0.309 0.369 0.512
0.90 0.000 0.028 0.058 0.089 0.121 0.155 0.192 0.233 0.281 0.341 0.484
0.91 0.000 0.030 0.061 0.093 0.127 0.164 0.205 0.253 0.313 0.456
0.92 0.000 0.031 0.063 0.097 0.134 0.175 0.223 0.283 0.426
0.93 0.000 0.023 0.066 0.103 0.144 0.192 0.252 0.395
0.94 0.000 0.034 0.071 0.112 0.160 0.220 0.363
0.95 0.000 0.037 0.079 0.126 0.186 0.329
0.96 0.000 0.041 0.089 0.149 0.292
0.97 0.000 0.048 0.108 0.251
0.98 0.000 0.060 0.203
0.99 0.000 0.143
1.00 0.000
CORRECTED POWER FACTOR
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A205 12/00 page 4 of 4
© 2000 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116
Table of contents
Other TIME MARK Controllers manuals
Popular Controllers manuals by other brands

Veikong
Veikong gpd 515/g5 Startup guide

Ingersoll-Rand
Ingersoll-Rand ST1000M Series Installation and maintenance information

INTERPIDCS
INTERPIDCS neoVI PLASMA manual

SMC Networks
SMC Networks JX73 Series Installation and maintenance manual

Balluff
Balluff BNI PBS-504-001-K008 user guide

Honeywell
Honeywell ComfortPoint Open CPO-PC400-W manual

Hy-Gain
Hy-Gain TAILTWISTER T-2X instruction manual

maxxess
maxxess eMAX-LP2500 Specification and installation guide

Sollae Systems
Sollae Systems PES-2403 user manual

Mitsubishi Electric
Mitsubishi Electric MELSERVO-J5 MR-J5-G Series user manual

EYC
EYC DPME01 Operation manual

Evco
Evco c-pro 3 nano Series Hardware manual