TIS T-3A-HVAC6 User manual

TIS HVAC VAV CONTROLLER
INSTALLATION MANUAL
This module has 6 relays to control multiple fan
speeds (low, medium, high), cooling, heating,
and auxiliary contact. the auxiliary contact can
be congured for both a dehumidier and/or
second heating/cooling pump or a Valve Reverse
Connection.
The HVAC Module is also equipped with an
external temperature sensor and 0-10V output for
VAV control.
Automation Made Easy
Model: HVAC6-3A-T
6 58921 79838 6
BARCODE (UPC-A)
PRODUCT INFORMATION
PRODUCT SPECIFICATIONS
Output switching voltage
Number of channels 6
Nominal voltage 0 – 230 V AC 50/60 Hz
VAV outputs 0-10V / 50mA
Output switching current
Nominal current per channel
Low current 3 A / VDC
Air condition controllers 2 A / VAC
Max switching current 3 A / VDC
Max Continues current 2 A / VAC
Input Temperature Resistive temperature sensor
TIS Bus
Number of devices on 1 line Max. 64
Bus voltage 12-32 V DC
Current consumption <30 mA / 24 V DC
Protection Reverse Polarity Protection
Functions
Cool, Heat, Aux Cool, Heat, Aux programmable outputs
Fan speed control Low, Medium, High linked outputs
VAV 0-10V Can set any voltage for Low, Med & High
Dimensions Width × Length × Height 76mm × 75mm × 91mm
Housing
Materials ABS fire proof
Casing color Black Gray
IP rating IP 20

TIS HVAC VAV CONTROLLER
INSTALLATION MANUAL
MODEL: HVAC6-3A-T
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
Data Cable
Use screened stranded RS485 data cable
with four twisted pairs. Congure devices in
a “Daisy Chain.”
Do not cut or terminate live data cables.
Electrical Wires
The installer should adequately consider
the total current consumption when
selecting the wires.
Warranty
We provide a warranty as required by law.
A hologram warranty seal and product
serial number are provided on each device.
Please send the description of the defect
with Product S/N to our dealer network.
Read Instructions
We recommend that you read this
Instruction Manual before installation.
Safety instructions
Electrical equipment should only be
installed and tted by electrically skilled
persons.
Failure to observe the instructions may
cause damage to the device and other
hazards.
These instructions are an integral part of
the product and must remain with the end
customer.
Programming
This device can be tested and programmed
manually. Advanced programming requires
TIS Device Search software. Advanced
software programming knowledge should
be obtained in the advanced training
courses.
Simple Installation
DIN Rail mount facilitates installation.
Fixing points are provided for installation
without the use of DIN rail.
Mounting Location
Install in a dry, well-ventilated location.
Controllers may emit some mechanical
noises. Consider this when deciding on a
mounting location.

TIS HVAC VAV CONTROLLER
INSTALLATION MANUAL
MODEL: HVAC6-3A-T
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
Turn off the main electrical source before
installation.
1WARNING! HIGH VOLTAGE
Mount the device on a DIN Rail inside an
approved enclosure. The device can also
be installed without the use of DIN Rail
by two mounting screw holes.
2
+24D+D-GND+24D+D-GND
Connect RS485 data cable to the TIS-
BUS port as per the connection diagram.
No need to loop the TIS-bus cable if 2
DIN Rail modules are connected together
from the side bus train terminal.
3
GND(white-orange)&(white-brown)
D-(white-green)&(white-blue)
D+(blue-green)
+24V(brown-orange)
Cat5e connection
To the TIS BUS Network
Cat5e
34
1 2
PRG
TIS-BUS
GND D+ +24V
D-
1 2 3 4
RLY-4CH-10A WARNING! HIGH VOLTAGE!
!
INSTALLATION STEPS

TIS HVAC VAV CONTROLLER
INSTALLATION MANUAL
MODEL: HVAC6-3A-T
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
Complete the connection, as per the following steps:
CONNECTING TO FCU/HVAC UNIT
Connect the cool (Y), heat (W), and fan
speed wires (Low, Med, Heat) to their
respective terminals on the module.
Connect the supply wire (24V,110V, or
220V) to module COM connection. All
inputs must have an appropriate voltage
source and an MCB to protect that load
circuit.
4
Cool
Heat
LOW
MEDIUM
HIGH
Connect to 220/24V AC
Second stage Cooling OR Second stage Heating
1.5 mm Electric Cable
2.5 mm Electric Cable
GND(white-orange)&(white-brown)
D-(white-green)&(white-blue)
D+(blue-green)
+24V(brown-orange)
Cat5e connection
HVAC6-3-A-T
Low Med
Cool Heat
PRG
TIS-BUS
GND D+ +24V
D-
High
AUX
MODE FAN
TEMP
VAV
GND 0-10V T- T+
Com Cool Heat Aux Low Med High
Com
To the TIS BUS Network
Cat5e
INSTALLATION STEPS
WARNING: For Aux connection you
should congure the aux output (Y2,
W2, O/B, humidier or dehumidier) in
software before connecting it to the unit
terminal. Each channel can control a
maximum of 5A loads. The installer should
make sure not to overload the channels.
CONNECTING TO VAV UNIT
Connect the 0-10v wires of the unit to the
module 0-10V connection.
To the TIS BUS Network
Cat5e
HVAC6-3-A-T
Low Med
Cool Heat
PRG
TIS-BUS
GND D+ +24V
D-
High
AUX
MODE FAN
TEMP
VAV
GND 0-10V T- T+
Com Cool Heat Aux Low Med High
Com
low voltage Cable
low voltage Cable
GND(white-orange)&(white-brown)
D-(white-green)&(white-blue)
D+(blue-green)
+24V(brown-orange)
Cat5e connection
Motorized Air Damper 0-10V

TIS HVAC VAV CONTROLLER
INSTALLATION MANUAL
MODEL: HVAC6-3A-T
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
TEMPERATURE SENSOR
If you want to use the HVAC as stand-
alone device without the wall panel
(thermostat).
Then connect TIS temperature sensor 2
wires to Temperature sensor terminal in
the module.
low voltage cable
low voltage cable
GND(white-orange)&(white-brown)
D-(white-green)&(white-blue)
D+(blue-green)
+24V(brown-orange)
Cat5e connection
To the TIS BUS Network
Cat5e
HVAC6-3-A-T
Low Med
Cool Heat
PRG
TIS-BUS
GND D+ +24V
D-
High
AUX
MODE FAN
TEMP
VAV
GND 0-10V T- T+
Com Cool Heat Aux Low Med High
Com
TIS Temp Sensor Probe
INSTALLATION STEPS
Turn on the power source, and then
test the loads by short pressing on the
device’s local override buttons Cool,
Heat, Aux, Low, Med, High.
5
HVAC6-3-A-T
Low Med
Cool Heat
PRG
TIS-BUS
GND D+ +24V
D-
High
AUX
MODE FAN
TEMP
VAV
GND 0-10V T- T+
Com Cool Heat Aux Low Med High
Com

TIS HVAC VAV CONTROLLER
INSTALLATION MANUAL
MODEL: HVAC6-3A-T
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
Go to the Air Conditioning page in your
Luna TFT, Mars AC, Terre AC, or other
thermostat panel, and turn the AC ON.
2
1Press the PRG button for 6 seconds until
the green LED steady turns on.
To pair the module to wall panel (thermostat) complete the following steps manually:
Test your air conditioning by changing
the fan speed from low to medium to
high. HVAC module should respond
accordingly.
3
PAIRING (MANUAL PROGRAMMING)
HVAC6-3-A-T
Low Med
Cool Heat
PRG
TIS-BUS
GND D+ +24V
D-
High
AUX
MODE FAN
TEMP
VAV
GND 0-10V T- T+
Com Cool Heat Aux Low Med High
Com
6”
00:00:00
INDOOR
23
30 MINUTES
ONOFF
SPEED MODE
29
AC1
LOW
HI
MED
AUT
FAN
HEAT
COOL
AUT
00:00:00
INDOOR
23
30 MINUTES
ONOFF
SPEED MODE
29
AC1
LOW
HI
MED
AUT
FAN
HEAT
COOL
AUT
HVAC6-3-A-T
Low Med
Cool Heat
PRG
TIS-BUS
GND D+ +24V
D-
High
AUX
MODE FAN
TEMP
VAV
GND 0-10V T- T+
Com Cool Heat Aux Low Med High
Com

TIS HVAC VAV CONTROLLER
INSTALLATION MANUAL
MODEL: HVAC6-3A-T
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
DISABLING/ ENABLING LOCAL OVERRIDE BUTTONS
1To disable device’s local override buttons,
press on the PRG button for 12 seconds
until the LED starts blinking rapidly.
To enable device’s local override buttons
if it was disabled, press on the PRG
button for 12 seconds until the LED starts
blinking rapidly.
2
HVAC6-3-A-T
Low Med
Cool Heat
PRG
TIS-BUS
GND D+ +24V
D-
High
AUX
MODE FAN
TEMP
VAV
GND 0-10V T- T+
Com Cool Heat Aux Low Med High
Com
HVAC6-3-A-T
Low Med
Cool Heat
PRG
TIS-BUS
GND D+ +24V
D-
High
AUX
MODE FAN
TEMP
VAV
GND 0-10V T- T+
Com Cool Heat Aux Low Med High
Com
12”
12”

TIS HVAC VAV CONTROLLER
INSTALLATION MANUAL
MODEL: HVAC6-3A-T
TIS CONTROL LIMITED
RM 1502-p9 Easey CommBldg
253-261 Hennessy Rd Wanchai
Hong Kong
TEXAS INTELLIGENT SYSTEM LLC
SUITE# 610. 860 NORTH DOROTHY DR
RICHARDSON
TX 75081.USA
Copyright © 2020 TIS, All Rights Reserved
TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the
United States of America. This company takes TIS Control Ltd. in other
countries. All of the Specifications are subject to change without notice.
www.tiscontrol.com
TROUBLESHOOTING
PRG Button Blinks Red Color
Rapidly
Reason: The Module address conicts with other
device in TIS network, you need to press and hold the
PRG button for 6 seconds so the module can get new
address
Device PRG LED is not Blinking;
Device not Powered
Reason: Device is not powered on; no TIS-BUS 24V
supply connected to the device.
Device Button LED is ON but
unit is not responding
Reason 1: Compressor / heat protection time enabled
Reason 2: Unit main supply is off.
Wall Panels can’t Pair with the
Device
Reason 1: TIS-BUS connection has a problem; check
the wires and make sure there’s not a short in the
connection.
Reason 2: Manual programming function disabled in
the device (default is enabled).
Wall Panels can’t Control the
Device Channels
Reason 1: TIS-BUS connection has a problem; check
the wires and make sure there’s not a short in the
connection.
Reason 2: Programming address is wrong.
HVAC Turned ON even when
the Wall Thermostat is Off.
Reason 1: HVAC stand-alone Logic enabled in
software.
Reason 2: another wall panel thermostat programmed
to the same HVAC module address.
Table of contents
Other TIS Controllers manuals
Popular Controllers manuals by other brands

Hayes
Hayes 81725 Operation manual

Controlli
Controlli MVE2XX Mounting instructions

Staubli
Staubli CS8C instruction manual

Richdel
Richdel 446PRi Installation and operating guide

Digital Monitoring Products
Digital Monitoring Products X1 Series quick start guide

TDI
TDI TURBOTWIN T100-VE Installation and operating manual