Beck 42-107 User manual

80-0042-00
Rev. 06.9
INSTRUCTION MANUAL
42-107
42-105
42-103
MODELS
R
ELECTRIC ACTUATORS FOR INDUSTRIAL PROCESS CONTROL

2
80-0042-00, Rev. 06.9
Product Description ........................................................................................................3
General Specications ..................................................................................................4
Outline Dimensions.......................................................................................................6
Installation........................................................................................................................7
Power and Signal Wiring...............................................................................................7
Safety Precautions......................................................................................................10
Start-up Instructions.................................................................................................... 11
Calibration ......................................................................................................................12
Travel Limit Switch Adjustment ...................................................................................12
Setting Auxiliary Switches ...........................................................................................14
Changing Direction of Travel.......................................................................................15
Feedback Signal .........................................................................................................16
Demand Input Signal...................................................................................................18
Loss of Signal Function...............................................................................................19
Deadband Adjustment.................................................................................................20
Short-stroke Operation (Reducing Full Stroke Travel Distance) .................................20
Maintenance ...................................................................................................................21
Component Replacement ...........................................................................................21
Troubleshooting ..........................................................................................................22
Services ..........................................................................................................................23
Warranty .........................................................................................................................23
TABLE OF CONTENTS

3
80-0042-00, Rev. 06.9
INTRODUCTION
Beck’s Group 42 actuators are designed to
meet the actuation needs of long stroke linear
applications. Typical applications include burner
air registers and OFA port dampers, but they can
be used on any application requiring up to 18
inches of linear stroke. Employing Beck’s unique
design characteristics, reliability and quality into
a long stroke linear actuator design lls a much
requested slot in the Beck family of products.
As with all Beck actuators, the Group 42 is
designed for simple installation, no duty cycle
limitations, excellent performance and little or no
required maintenance.
Ideally suited for harsh industrial environments,
the Group 42 handles long stroke applications
requiring up to 1,000 lbs. (4 450 N) of thrust. The
design employs a highly ecient ball screw coupled
with a time-proven Beck motor and oers consistent,
repeatable positioning as precise as 0.25% of span.
Like all Beck actuators, the Group 42 incorporates
a heavy-duty, weather-proof, cast aluminum body.
HAZARDOUS LOCATION
ACTUATORS FOR DUST AREA
CLASSIFICATIONS (OPTIONAL)
Group 42 Actuators are available approved
for the following Protection Methods and
Protection Concepts, suitable for use in:
Class II, Division 1, Groups E, F and G; T3C
Class II, Division 2, Groups F & G; T3C
Class III, Division 1 & 2
Enclosure type 4X
Enclosure rated IP66
Tambient = –30ºC. to 70ºC. (120V operation)
–30ºC. to 60ºC. (240V operation)
PRODUCT DESCRIPTION

4
80-0042-00, Rev. 06.9
GENERAL SPECIFICATIONS
Actuator Power 120 V ac, single-phase, 50 or 60 Hz
Allowable Tolerance +10% / -15%
Max. Current & Power 1.2A, 144W @ 120 V ac
Output Thrust and Timing 1,000 lbs (4 450 N), 4.2 sec/in (1.65 sec/mm)
Stroke Range 5 to 18 inches (127 to 457 mm)
Weight Approx. 71 lbs (32.2 kg), depending on selected options.
Operating Conditions –40° to 85° C. (–40° to 185° F.)
0 to 99% relative humidity
Control Options Three types of control are available:
1) Open/close option 3. Two position control using manual
pushbuttons or an automatic controller.
2) Direct ac control option 5. Actuator is energized by 120 V ac
line current from a remote controller or manual switches.
3) Modulating analog control option 7. Onboard actuator control
electronics position output proportionally to mA Demand input
signal.
Demand Input Signal 4–20 mA or 1–5 V dc
(Option 7)
Deadband 1.0% of Span
Minimum Step .25% of Span
Hysteresis .5% of Span at any point
Position Feedback Signal 4–20 mA or 1–5 V dc
(Options 5 & 7)
Feedback may be congured as a two wire transmitter or as a four wire active signal source.
Two wire systems require a customer supplied external power supply. Four wire systems
require 120 V ac supply to the drive.
Isolation Demand input and position Feedback signals are isolated from
ground and the ac power line. Signal buering provides 24 V dc
isolation between the signals.
Action on Loss of Power Stays in place.
PRODUCT DESCRIPTION

5
80-0042-00, Rev. 06.9
Action on Loss of Demand Stays in place or moves to predetermined position with ac power
Input Signal (Option 7) supplied.
Stall Protection (Option 7) If the motor tries to run in one direction for more than approx. 136
seconds, it will shut o.
Stall Relay Contacts Form A, 10 volt-amps at 120 V ac or dc
(Option 7)
Action on Stall (Option 7) Motor power is turned o when relay contacts open (after 136
seconds of stall). Remote signal is available.
Travel Limit Switches Two Form C (Retract and Extend), eld-adjustable.
Rated 10 A, 125/150 Vac; .5 A, 125 Vdc; .25 A, 150 Vdc.
Auxiliary Switches Two Form C rated for 1 A, 250 V ac., eld-adjustable.
Rated 10 A, 125/150 Vac; .5 A, 125 Vdc; .25 A, 150 Vdc.
Handswitch (Option 7) Permits local electrical operation, independent of Demand input
signal.
Handwheel Provides manual operation without electrical power.
Customer Wiring Terminals accommodate up to 12 AWG (3.31 mm2).
Motor 120 V ac, single-phase, no burnout, non-coasting. Capable of 60
starts per minute.
Enclosure Precision-machined aluminum alloy, painted with corrosion-
resistant polyurethane paint, to provide a rugged, dust-tight,
weatherproof enclosure. Type 4X; IP66.* Actuators designed for
hazardous locations are also available.
Mounting Orientation Can be mounted in any orientation.
Standards* CSA Certied
CE Compliant
*NOTE: May not be available with all options and models. For more information, or to inquire about
standards not specically listed, please call Beck at 215-968-4600.

6
80-0042-00, Rev. 06.9
FRONT VIEW REAR VIEW
MODEL 42-107, -105 & -103 SPECIFICATIONS
(All dimensions are in inches and [mm] and are subject to change)
RIGHT SIDE VIEW
Note:
Front mounting clevis rotates 360°.
Custom rear clevis extensions are available.
Max. Drive
Travel (in) [mm]
Min. Drive
Travel (in) [mm]
"L" Dim. Fully
Ret. (in) [mm]
"L" Dim. Fully
Ext. (in) [mm]
Approx. Wt.
(lbs) [kgs]
8 [203] 5 [127] 18 19/32 [472] 26 19/32 [675] 64 [29]
12 [305] 7 [178] 22 19/32 [574] 34 19/32 [879] 66 [30]
18 [457] 11 [279] 28 19/32 [726] 46 19/32 [1 183] 69 [31]
2 17/32"
DIA.
[64]
7 25/32"
[198]
8 7/32"
[209]
ALLOW 2 3/4" [70]
FOR REMOVAL
2 1/4"
[57]
3 11/32"
[85]
"L" DIMENSION
3/8 [10]
1 1/16"
[27]
(SEE TABLE)
REAR CLEVIS
HOLE DIAMETER
1"
[25]
(SEE TABLE)
FRONT CLEVIS
HOLE DIAMETER
16"
[406]
ALLOW 6" [152]
FOR REMOVAL
11/16"
[17]
3/4"
[19]
3/4" N.P.T. CONDUIT
POWER CONNECTION
3/4" N.P.T. CONDUIT
SIGNAL CONNECTION
Available Front & Rear
Clevis Hole Diameters
.504 ± .003 [12.80 ± 0.76]
.754 ± .003 [19.15 ± 0.76]
.879 ± .003 [22.33 ± 0.76]
3 1/2"
[89]
.625
±.010
[15.875
.254]
4 15/32"
[114]
7 15/16"
[202]
3 13/16"
[97]
4 31/32"
[126]
3 13/32"
[87]
2 5/8"
[67]
3/4"
[19]
7 15/16"
[202]
1 15/32"
[37]
3 1/2"
[89]
3 7/16"
[87]
.625
±.010
[15.875
.254]
OUTLINE DIMENSION DRAWINGS

7
80-0042-00, Rev. 06.9
POWER AND SIGNAL WIRING
The Group 42 actuator has a pair of 3/4"
NPT threaded holes for signal and power
conduit connection. Conduits should be routed
from below the actuator so that condensation
and other contaminants flow away from the
conduit. All conduit entrances must be properly
sealed in accordance with National Standards or
Regulatory Authorities.
Power and signal wires must be routed to the
actuator separately and be either shielded cables
or installed in conductive conduit and/or cable
trays.
All signal and power connections are made
on the terminal board. Typical wiring connections
for each Group 42 control option are described
on the following pages. A specic wiring diagram
is axed to each actuator shipped.
All actuators are furnished with two auxiliary
switches. Wiring connections for these are
described separately. In addition, a safety
ground is required for all actuators and is located
on the baseplate of the control module.
NOTE: Customer wiring inside the control
module must be properly dressed and routed
to prevent damage to wires from the control
module cover.
Figure 1
INSTALLATION
(Option 7 Terminal Board Shown)
Figure 1

8
80-0042-00, Rev. 06.9
Auxiliary Switches
Customer connections to the auxiliary switches are on the terminal board. Switch 1 connects to terminals
6, 7 and 8. Switch 2 connects to terminals 3, 4 and 5. Each switch is form C, rated for 1 amp at 120 V ac.
There is no electrical connection between the two switches. S1 is factory set to operate 2% of the travel
range before the Retract travel limit. S2 is factory set to operate 2% before the Extend travel limit. See page
14 for additional information about setting the auxiliary switches.
Option 7, Modulating
Analog Position Control with Loop Powered Position Feedback Signal
Customer must supply two wires to power the drive: One 120 V ac line (terminal 1), and one neutral (terminal
2). Customer must supply two wires for the analog input control signal: Connect to terminal 11 (-) and to terminal
12 (+). The loop powered position feedback signal must be connected to a “2-wire” type analog input that
provides a dc voltage over the signal wires (a dc voltage power supply must be wired in series with the signal
wiring). If the dc supply is 24 to 35 volts, connect to terminal 14 (-) and to terminal 15 (+). If the dc power supply
is 36 to 45 volts, reverse polarity and connect to terminal 14 (+) and to terminal 15 (-).
Analog Position Control with Drive Powered Position Feedback Signal
Customer must supply two wires to power the drive: One 120 V ac line (terminal 1), and one neutral
(terminal 2). Customer must supply two wires for analog control: Connect to terminal 11 (-) and to terminal
12 (+). Customer may supply two additional wires to monitor the analog position feedback signal: Connect to
terminal 13 (-) and to terminal 14 (+). The drive’s feedback circuit power supply is derived from the 120 V ac
line, therefore the feedback signal must be wired to a "4-wire" type, non-powered analog input.
78
6
45
3
S1
S2
INSTALLATION
Typical Wiring Diagram (Option 7)

9
80-0042-00, Rev. 06.9
Option 5, Modulating
Direct AC Control with Loop Powered Position Feedback Signal
Customer must supply three wires to directly control the actuator motor direction: One 120 V ac line
to run Extend (terminal 10), one 120 V ac line to run Retract (terminal 9), and one neutral (terminal 2).
Customer may supply two additional wires to monitor a loop powered position feedback signal. The loop
powered position feedback signal must be connected to a “2-wire” type analog input that provides a dc
voltage over the signal wires (a dc voltage power supply must be wired in series with the signal wiring). If
the dc supply is 24 to 35 volts, connect to terminal 14 (-) and to terminal 15 (+). If the dc supply is 36 to 45
volts, reverse polarity and connect to terminal 14 (+) and to terminal 15 (-).
Direct AC Control with Actuator Powered Position Feedback Signal
Customer must supply three wires to directly control the actuator motor direction: One 120 V ac line
to run Extend (terminal 10), one 120 V ac line to run Retract (terminal 9), and one neutral (terminal 2).
Customer may supply two additional wires to monitor the analog position feedback signal: Connect to
terminal 13 (-) and to terminal 14 (+). If position feedback monitoring is desired, a 120 V ac line must
be connected to terminal 1. The drive’s feedback circuit power supply is derived from this 120 V ac line,
therefore the feedback signal must be wired to a “4-wire” type, non-powered analog input.
Option 3, Open/Close
Direct AC Control
Customer must supply three wires to directly control the actuator motor direction: one 120 V ac line to run
Extend (terminal 10), one 120 V ac line to run Retract (terminal 9) and one neutral (terminal 2).
Typical Wiring Diagram (Option 5)
Typical Wiring Diagram (Option 3)

10
80-0042-00, Rev. 06.9
Power and signal wires must be routed to the
actuator separately and be either shielded cables
or installed in conductive conduit and/or cable trays.
Shielded, twisted pair cables should be used
for signal connections to avoid being aected by
electrical noise. These signal wires, based on Noise
Susceptibility Level (NSL) per IEEE-518, fall into the
level 1 classication. A braided shield will be more
eective than a wrapped foil shield. Signal wire
shields should be connected to the actuator casting
grounding screw. If grounding at the signal source
is required, then the shield should not be grounded
at the drive. Raceways such as conduits and trays
have to be grounded at both ends to properly meet
immunity requirements.
A large, clearly labeled terminal block in the
actuator is enclosed in a separate, gasketed metal
enclosure. Terminals will accommodate up to 12
AWG (3.31 mm2) wiring.
CAUTION
Always close covers immediately
after installation or service to prevent
moisture or other foreign matter
from entering the actuator.
Refer to the wiring diagram furnished with your
Beck actuator for proper AC power and signal
connections. It is advisable to provide normal short
circuit protection on the AC power line. A copy of
the wiring diagram is shipped with each actuator
and is fastened to the inside of the terminal block
cover. If there is no wiring diagram available, you
may obtain a copy from Beck by providing the serial
number of your drive.
Your Beck actuator has been supplied to match
the signal source in your control loop. If it does not
match, a 250 ohm input resistor may be added or
removed to obtain the proper match. Consult the
factory for details.
For maximum safety, and to comply with
national and international standards, the Beck
actuator body is required to be grounded. Use
one of the two grounding terminals in the wiring
compartment of the actuator to make this
connection. Wire size 12 AWG (3.31 mm2) is
recommended for this purpose.
CONDUIT ENTRIES
Conduits are provided for power and signal
wiring. Temporary plugs are installed in the
conduits at the factory for shipping only and are
not intended for permanent use. Prior to actuator
operation, all conduit entrances must be properly
sealed in accordance with National Standards or
Regulatory Authorities.
SAFETY PRECAUTIONS
WARNING
Installation and service instructions
only. To avoid injury and electric
shock, do not perform any servicing
other than that contained in this
manual. Please read and understand
the appropriate sections in this
manual before attempting to install
or operate your drive.
CAUTION
Hot surfaces! Surfaces of equipment
may be at an elevated temperature
depending on operating conditions
and environment. Allow to cool
before servicing.
STORAGE INFORMATION
Beck actuators should be stored in their shipping
cartons in a clean, dry area.
If it is necessary to store actuators outdoors for
a long period of time, they should be stored above
ground and covered with a waterproof cover. Do not
stack cartons. Stored actuators should be checked
periodically to ensure no condensation has formed
in electronic and terminal compartments. Moisture
damage while in storage is not covered by warranty.
UNPACKING
Group 42 actuators are shipped in standardized
cardboard shipping containers and secured to a
wooden platform.
INSTALLATION—ELECTRICAL
NOTE: All Beck actuators are shipped from
the factory ready for installation; no electrical
adjustments are required before placing them
in operation. Each actuator is set up and
that were written into the equipment order.
Two N.P.T. conduit connections are provided for
power and signal wiring to the drive. One 3/4" conduit
is provided for signal wiring connections, and the
other 3/4" conduit is provided for power and auxiliary
switch connections. A sealant must be used on
threaded conduit connections to keep moisture out.
Conduits should be routed from below the actuator so
that condensation and other contaminants entering
the conduit cannot enter the drive.
INSTALLATION
Other manuals for 42-107
1
This manual suits for next models
2
Table of contents
Other Beck Controllers manuals
Popular Controllers manuals by other brands

Digiplex
Digiplex DGP-848 Programming guide

YASKAWA
YASKAWA SGM series user manual

Sinope
Sinope Calypso RM3500ZB installation guide

Isimet
Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

LSIS
LSIS sv-ip5a user manual

Rockwell Automation
Rockwell Automation 1769-L31 installation instructions





















