Titon ECOaura HRV3 PH User manual

Product Manual
ventilation systems
EN
HRV controller
aura-t TP536/EU
Heat Recovery Ventilation Unit
HRV3 PH ECOaura TP412B PH

Warnings, Safety Information and Guidance
Important Information
Important: read these instructions fully before the installation of this appliance
1. Installation of the appliance and accessories must be carried out by a qualied and suitable
competent person and be carried out in clean, dry conditions where dust and humidity are
at minimal levels.
2. This manual covers the installation of the Heat Recovery Ventilation (HRV) unit
3. All wiring must conform to current I.E.E. Wiring Regulations and all applicable standards
and Building Regulations.
4. Inspect the appliance and electrical supply cord. If the supply cord is damaged, it must be
replaced by the manufacturer, their service agent or similarly qualied persons in order to
avoid a hazard.
5. The unit is supplied with a mains rated 3 core exible cord (PVC sheathed, brown, blue and
green/yellow 0.75mm²).
6. The appliance must be connected to a local double pole isolation switch with a contact
separation of at least 3mm.
7. The appliance must be earthed.
8. HRV3 suitable for 230V ~ 50/60Hz single phase with a fuse rating of 5A.
9. Controller - control & communication cable access is via the tted cable gland(s) which are
suitable for Ø3- 6mm cable.
10. Controller - control & communication cable - Unshielded 4 Core 18-24AWG
Stranded, Tinned Copper.
11. Control & communication cables should not be placed within 50mm or on the same metal
cable tray as any 230V~ lighting or power cables.
12. Ensure all cable glands are fully tightened and supplied grommets are used.
13. The unit must be stored in a clean and dry environment. Do not install the appliance in
areas where the following may be present or occur;
•Excessive oil or a grease laden atmosphere,
•Corrosive or ammable gases, liquids or vapours,
•Ambient temperatures above 40°C or below -5°C,
•Humidity levels above 90% or is a wet environment.
14. The appliance is not suitable for installation to the exterior of the dwelling.
15. This appliance can be used by children aged from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience and knowledge if
they have been given supervision or instruction concerning use of the appliance in a safe
way and understand the hazards involved. Children should be supervised to ensure that
they do not play with the appliance. Cleaning and user maintenance shall not be made by
children without supervision.
16. Ensure that external grilles are located away from any ue outlet, in accordance with rel-
evant Building Regulations.
17. The unit must not be connected to a tumble dryer or a cooker hood.
18. Precautions must be taken to avoid the back-ow of gases into the room from an open ue
appliance.
19. Ensure all ducting, condensate drain and associated pipe work is free from debris and
blockages before switching on the unit.
2

Explanation of symbols on the appliance.
Read instruction Manual.
Risk of Electric Shock.
General hazard safety alert.
Disconnect the mains supply before removing this cover.
Wait until all machine components have completely stopped before touching
them.
Disconnect the mains supply before removing this
cover.
&
Before obtaining access to terminals or removing this
cover, all supply circuits must be disconnected.
Titon Recommend:
1. A minimum distance of 200mm between the HRV unit and any sharp bends in duct work.
2. Ducting should be insulated where it passes through unheated areas and voids with the equivalent of at least 25 mm
of a material having a thermal conductivity of ≤0.04 W/(m.K) to reduce the possibility of condensation forming. Where
a duct extends externally above roof level the section above the roof should be insulated or a condensate trap should
be tted just below roof level.
3. Ducts within the building heated envelope between the external terminals and the unit’s From Atmosphere and To
Atmosphere ports should be insulated and wrapped additionally with a vapour barrier outside the insulation.
4. Where ducts pass through re barriers, they must be appropriately re stopped in accordance with the requirements
of Building Regulations.
5. A ducting condensate drain must be tted to vertical To Atmosphere duct work.
6. Ducting must be installed in such a way that resistance to airow is minimised.
7. Ducting connected to the From Atmosphere & To Atmosphere ports, must be to/from the external air outside the
building envelope.
8. Duct joints to the unit’s duct ports must be xed using a method that ensures a long term seal is achieved.
9. A minimum distance of 2m exists between the external supply and exhaust terminals .
+
+
+
3

Contents
When this document
is viewed as a PDF the
headings & sub headings on
this page are hyperlinks to the content.
Additionally the page numbers in this
document are hyperlinks back to this
contents page.
Warnings, Safety Information and Guidance
Important Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Explanation of symbols on the appliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Titon Recommend: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Product Information
HRV3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
aura-t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Packaging Contents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Product Overview
Control & Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Programmable Speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Speed Selection & Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
24 Hour Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Day of Week Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Status Icons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Filter Change Alert. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Multiple InternalTemperature Sensors. . . . . . . . . . . . . . . . . . . . . . . . . 6
Internal Humidity Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Boost Overrun Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Boost Delay Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Boost Inhibit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Summer Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SUMMERboost® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Summer By Pass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Duct Heater. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Frost Protection Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Shut Down of Supply Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3 x Volt Free Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2 x Live Switch Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2 x Proportional Sensor Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
HRV3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
aura-t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation
HRV3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Condensate Drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Ducting Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Wiring Connections Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
aura-t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Fixing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
aura-t Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
HRV3 Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Switching & Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
External Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Duct Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Ducting Layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Sensor Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Control
Menu Tabs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Run Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Status Icons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Other Icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Timer Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Setup
Fan Commission. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Timer Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Timer Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Controller Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Summer Bypass Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Passcode Enable / Disable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Switch Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Maintenance
aura-t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Cleaning Exterior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
HRV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Front Cover Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Cleaning Interior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Cleaning Exterior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Condensate Tray. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Filter Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
How to Change Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Appendix
aura-t Congurable Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
HRV ECOaura Defaults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Service Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4

Product Information
HRV3
The HRV ECOaura are Mechanical Ventilation with Heat Recovery (MVHR) units. They are designed for the energy ecient
ventilation of dwellings. The units are designed for continuous ventilation, exhausting stale moist air from bathrooms,
toilets, kitchen and utility rooms. As the stale air is extracted, the unit’s heat exchanger transfers heat, which would have
been wasted, to the fresh air being supplied to the bedrooms and living rooms.
aura-t
The aura-t is a programmable touch screen controller which monitors and displays the status of a Titon ECOaura HRV
unit. It allows the unit to be commissioned, and gives the user both manual and timed control of fan speeds. The aura-t is
connected to the HRV via a low voltage connection and can be sited remotely from the unit.
Packaging Contents
Inspect the unit when taking delivery. Check the unit for damage and that all accessories have been supplied. Package
supplied with;
HRV unit x 1.
aura-t controller x 1.
~3m aura-t communication cable x 1.
Mounting Bracket x 2.
Safety Bracket x 1.
15mm Condensate Drain Olive & Nut x 1.
M6x10mm Pan head screws x 4.
M6 washers x 4.
Transport Bungs x 4, supplied packed in Duct Ports.
Product Manual x 1.
EuP Documentation.
Any shortages or damage must be immediately reported to the supplier.
5

Product Overview
Control & Features
The HRV3 TPxxx, aura-t controller TPxxx and Ventmatika Duct Heater KA NV 150-1.5 1f, work together and have the
following functionality.
Programmable Speeds
The unit has 4 programmable speed
settings, all speeds are variable
between 14-100% and allow
independent speed setting of both
supply and extract ventilation rates
Speed 1, Setback.
Reduced ventilation.
Speed 2, Continuous.
Normal ventilation.
Speed 3, Boost.
Increased ventilation
Speed 4, SUMMERboost®.
Very high ventilation.
Speed Selection & Display
The unit speed can be manually
selected via the on screen 1, 2, 3 & 4
buttons/icons which are also used to
display any automatically selected
speed.
24 Hour Clock
The aura-t has a twenty four hour clock
with a battery backup.
Day of Week Display
The aura-t displays the days of the
week as numbers.
Timer
The aura-t has a programmable timer
that can be used to switch the HRV to
Speed 1 at specied times.
Status Icons
The aura-t displays icons to indicates
modes of operation in Real-time.
Filter Change Alert
The aura-t will display an alert after
a specied time when the HRV lters
require changing.
Multiple Internal
Temperature Sensors
The HRV measures From Atmosphere
and To Atmosphere air temperatures
in real-time. Additionally the
temperatures of the air extracted
from, and supplied to, the property are
monitored.
Internal Humidity Sensor
The HRV has a relative humidity
(RH) sensor. The RH sensor can be
programmed to switch the HRV into
Boost Speed.
Boost Overrun Timer
A programmable timer that controls
the time the HRV remains at Boost
Speed after all boost switches have
been released.
Boost Delay Timer
A programmable timer which can be
used to delay the HRV running at Boost
Speed after a boost switch has been
activated.
Boost Inhibit
A programmed time period that
prevents the HRV switching into Boost
Speed or SUMMERboost®.
Summer Mode
Summer Mode operates by slowing or
stopping the supply fan. This reduces
the supply of From Atmosphere air
to the dwelling. Summer Mode is
triggered automatically or via a Volt
Free input. Summer Mode must not be
enabled or installed in dwellings where
open ue combustion appliances are
used.
SUMMERboost®
SUMMERboost® allows both the supply
and extract fans to run at full speed
whenever the Summer Bypass is
activated. By default SUMMERboost® is
enabled.
Summer By Pass
Summer Bypass is designed to operate
during hot periods where fresh air can
be vented straight into the property
without being preheated by the
extracted stale air. Summer Bypass
operation is automatically controlled.
The Summer Bypass mechanism diverts
the stale air being extracted from the
dwelling around the heat cell so that
its heat energy is not transferred to
the fresh air being supplied to the
dwelling.
Duct Heater
The duct heater, EKA-NV160/1.5kW,
is installed upstream of the HRV unit
in the From Atmosphere insulated
ducting.
6

Frost Protection Program
Stage 1
Frost protection is achieved by the unit
detecting the outside air temperature
being drawn into the HRV and then,
below the trigger temperature,
enabling the duct heater. The duct
heater is then controlled proportionally
based on the temperature of the
exhaust air. This is pre-set to ensure
that the exhaust air temperature does
not fall below 2°C.
Stage 2
During very cold weather with the
duct heater activated, if the exhaust
air temperature falls below 0.5 degrees
C the duct heater will be de-activated
and the supply fan ventilation rate
stopped allowing the warmer air
extracted from the property to raise
the exhaust air temperature preventing
the formation of ice within the heat
cell. As temperatures rise the Frost
Protection Program will increase the
supply ventilation ow rate back to the
commissioned settings.
.
Shut Down of Supply Fan
This feature stops all ventilation and
overrides any other speed control
input when a problem with the exhaust
fan or associated ductwork causes
insucient warm air to be available to
heat the incoming air supplied to the
property. The sensor monitoring the
Supply Air into the property will stop
both fan motors when this temperature
measures below 5˚C.
The Frost program icon will ash and
the fan speeds will display 0%. The
unit will remain o until the fan key is
pressed or the temperature increases
above 5˚C.
When the fan key is pressed the
unit will restart at full speed and
settle back to normal operation after
approximately 40 seconds. If the air
supplied to the dwelling is still below
5˚C Shut Down of Supply Fan mode will
stop ventilation again.
3 x Volt Free Inputs
Enables the connection of single pole
momentary switches, latching switches
or normally open relay contacts
to the HRV. These can be used to
switch between fan speeds or control
SUMMERboost® and Summer Mode.
2 x Live Switch Inputs
These inputs are used to switch the
HRV to Boost Speed via a switched live
input.
2 x Proportional Sensor
Inputs
Enables connection of environmental
sensors to the HRV which can be used
to proportionally control HRV fan
speeds.
7

Dimensions
HRV3
DO NOT BOX IN UNIT
aura-t
23.70
87
87
aura-t
426
Service Void
Service Void
715
860
490
300
100
295 600
600
430
300
100
8

Installation
HRV3
Read and observe the guidance & safety notices listed in Warnings, Safety Information and Guidance .
Do not remove the Port Covers until connecting ducting. Port Covers are tted
to prevent debris falling into the unit and causing blockages and damage:
The Titon HRV is designed to be mounted on a wall or similar. The
mounting surface must be suciently strong to support the unit.
Consider the positioning of electrical services and the Condensate Drain
when siting the unit.
Ensure there is sucient access around the HRV for future maintenance.
Do not ‘box-in’the unit making access to the unit dicult for maintenance
and repair.
The Unit Must be mounted plumb and level front to back and side to side.
1. Mark a horizontal line on the wall using a spirit level. This line will be
approximately 95mm below the location of the top face of the unit when
tted (excluding duct ports)
2. Use one of the Mounting Brackets as a template to mark the three xing
hole centres
3. Drill holes for xings, always use a xing suited to the wall type
4. Fix one Mounting Bracket to the wall ensuring the interlocking side is at the
top, as shown
5. Fix the remaining Mounting Bracket to the unit using the M6 screws and
washers provided, ensuring the interlock side is at the bottom. Do not
overtighten
6. Mount the unit by locating the two Mounting Brackets together. Ensure a
positive location is made between the two Mounting Bracket
7. The Safety Bracket MUST be tted. Fix the lower Safety Bracket as shown
using the remaining M6 screw, washer and suitable wall xing. Packing to
be used as required behind the Safety Bracket to ensure unit is level
Hook onto
Wall Bracket
Safety Bracket highlighted
Mounting Bracket highlighted
9

Condensate Drain
The unit’s Condensation Drain Pipe must be tted and connected to the dwelling’s foul water drainage system in
accordance with the relevant building regulations.
The Condensation Drain Pipe:
Is attach via a 15mm compression tting (drain pipe shown un-insulated for clarity), on the base of the unit
Must incorporate a suitable trap, which must act as an air lock
Must be adequate secured and be insulated with the equivalent of at least 25mm of insulating material with a thermal
conductivity of 0.04 W/(mK) if any part of the pipe passes though an unheated void
Should be installed to have a minimum 5° fall from the unit
Titon recommend the use of diaphragm type waste valve in place of a conventional ‘wet’ trap which could dry out.
Such as, BRE certicate no. 042/97 ‘Hepworth Hepv0 Hygienic self sealing plastic waste valve’recommended as an
alternative to traditional U-Traps
10

Ducting Connections
Read and observe the Warnings, Safety Information and Guidance.
The HRV unit has a labels with the icons indicating which port is which.
It is very important that ducting is connected to the correct ports in line with the icons below.
EXTRACT FROM DWELLING - This duct port is connected to the ducting that carries waste air from the‘Wet Rooms’
to the HRV unit.
TO ATMOSPHERE - This duct port is connected to the ducting that carries the waste air to outdoors from the HRV
unit.
SUPPLY TO DWELLING - This duct port is connected to the ducting that carries the fresh warmed air to the
habitable rooms from the HRV unit.
FROM ATMOSPHERE - This duct port is connected to the ducting that carries fresh outdoor air to the HRV unit.
Wiring Connections Access
All wiring must conform to current I.E.E. Wiring Regulations and all applicable national standards and Building
Regulations. Read and observe the Warnings, Safety Information and Guidance.
The electronics compartment is mounted on top of the unit. The compartment has two removable lids, front & rear. The
front lid must always be removed before the rear lid; both lids are xed by four screws. All wiring must be routed into the
electronics compartment via the knock-outs and using cable glands or similar.
11

aura-t
Location
The aura-t should be mounted in position convenient for the householder and where the supplied control cable will reach.
Fixing
1. Un-clip the front of the aura-t case from the Back Plate.
2. Thread the control cable through the hole in the Back Plate.
3. Fix Back Plate .
4. Connect the communication cable, see Wiring section.
5. Clip the front of aura-t to the Back Plate.
Connection to HRV
60
Fixing Holes
Wiring Access Hole
12

13

aura-t Wiring Diagrams
The aura-t’s control cable may be supplied tted with a plug in connector for connection to the HRV, if the HRV does not
have a socket remove the plug and use the wiring diagrams below.
12V
A
B
0V
HRV
12V
A
B
0V
Connection to HRV
Connection to aura-t
14

HRV3 Wiring Diagrams
Supply
Supply wiring Ref EE167
230V~
2 Pole
Isolator
Fuse
15

Switching & Controls
Supply wiring with switch inputs Ref EE166
The Switched Live (LS1, LS2) Boost(s) must be supplied via
the same circuit as used to power the unit.
A 3 (LS1 only) or 4 (LS1 &LS2) pole local isolator must be
installed. The Boxed Relay (Part No. TP505) may be required
to switch from other circuits.
Wet Room Light Switch
Kitchen Light Switch
230V~
4 Pole
Isolator
2 Pole
Isolator
Fuse
16

Volt Free switch inputs Ref EE163
LIVE switch inputs Ref EE163
Switch Defaults
SW1 - Volt Free - Kitchen Boost.
SW2 - Volt Free - Wet Room Boost.
SW3 - Volt Free - SUMMERboost Control.
Switch Defaults
LS1 - 230V~ - Kitchen Boost
LS2 - 230V~ - Wet Room Boost
The Switched Live (LS1, LS2) Boost(s) must be supplied via
the same circuit as used to power the unit.
SW Live from Kitchen
SW Live from Wet Room
17

External Sensors
Connections Ref EE165
Any of these switch arrangements can be used in
switch inputs SW1 to SW3 depending on their
conguration and the type of MVHR.
Volt-free control of SUMMERboost® using room
thermostat. TP509 Room Thermostat
Volt-free activation of Summer Mode using room
thermostat. TP509 Room Thermostat
Volt-free boost switching of MVHR using single-
pole switches TP502, TP503, TP507 and / or
TP500/TP501 Humidistat.
There is a maximum of 10 single pole switches or
Humidistats that can be used.
TP506 Latching Summer Mode switch /
TP522 Latching SUMMERboost® switch.
1 2 3
T
L
Y1 Y2
T
L
Y1 Y2
18

0-10V Sensor connections Ref EE161
If sensors are tted with switches ensure they are switched to VDC
Vin
GND
AO1
Vin
GND
AO1
Room Sensor 1
(default TP542 RSH
Room Humidity Sensor)
Room Sensor 2
(default TP541 RSC Room
CO Sensor)
Additional Options:
TP540 RSQ Room Air Quality Sensor
TP543 RST Room Temperature Sensor
VOut =24Vdc
Combined sensor load
must not exceed 4W
3-Way rotary switch Ref EE162
Switch Positions TP508 Three Position Rotary Switch
1 - Setback Speed
2 - Continuous Speed
3 - Boost Speed
For this conguration to function correctly;
S1-1 Needs to be set to a Kitchen or Wet Room Boost switch,
S1-2 Needs to be set to a Setback switch.
19

20
This manual suits for next models
3
Table of contents
Other Titon Heating System manuals
Popular Heating System manuals by other brands

Viessmann
Viessmann VITOVENT 300 installation instructions

SND
SND SND-1500-3 owner's manual

Vaillant
Vaillant VIHSGB210 operating instructions

Bryant
Bryant 551A Installation, Start-Up and Service Instructions

Biddle
Biddle PRO270 Installation, operating and maintenance instructions

York
York AFFINITY DEZ024 Technical guide

Baxi
Baxi Assure Vertical SHRU Installation & maintenance manual

NuAire
NuAire UNI-X Series Installation and maintenance instructions

Roca
Roca GAVINA 20 GTI Confort SP Operation, Cleaning and Maintenance Instructions for the USER

2VV
2VV ALFA 95 II vertical quick start

Dimplex
Dimplex VFMQ Product guide

Kabola
Kabola ECOLINE KB Series user manual