Titon WHR180 User manual

Step 3 - Store fan speed setting.
• To store fan speed press +and F.
• To not save press OK.
• Restore factory setting press OK and -.
Step 4 - Press OK to return to the settings menu - Repeat steps 1 to 3 for further modifications.
Step 5 - Press OK to return to the settings menu, then press Ffor 1 second to return to the main menu.
The unit is now set.
Process for setting extract and supply terminals.
Before commencing system commissioning ensure compliance with Section 1: Installation Guidance of
the Standard Assessment Procedure 2005 - Appendix Q MVHR Installation Guide.
• All extract and supply terminals must be set such that the correct flow rate is achieved for the room
in which it is situated, this must be done using:
• A calibrated anemometer or similar airflow measuring device.
• The Titon system design specification for the room flow rates and fan speed settings.
• The Speed Setting Control Switch.
Process for setting room extract and supply rates.
1. Ensure all external & internal windows and doors are closed.
2. Ensure that all the extract terminals are extracting air from the wet rooms and that all supply
terminals are supplying air to the habitable rooms.
3. Set the supply flow rates with the unit on fan speed setting 1. (Low rate/Continuous).
4. Set the extract flow rates with the unit on fan speed setting 2. (High rate/Boost).
Rotate the terminals to adjust the flow rate to the required value. Checking and rechecking of the
terminals is required, as when one terminal is adjusted it affects the others. Adjustment of supply
terminals does not affect the flow rate of the extract terminals, and visa versa.
If the flow rates cannot be achieved using the fan speed settings specified, increase the unit’s fan
speed setting incrementally until flow rates are reached.
When the fan speed settings have been set and the terminals are providing the specified flow rates,
tighten all lock nuts on the individual ventilation room terminals to prevent accidental occupier
adjustment.
* The system must be set to provide the ventilation rates in accordance with the Approved Document F1 ‘Means of ventilation’ Building Regulations, England &
Wales if applicable. Failure to install the heat recovery unit and ducting correctly is the sole responsibility of the contracted installer. Titon will not accept any
responsibility for incorrectly fitted systems or failure to follow these instructions and this may invalidate the unit warranty.
BM813 Iss 02
WHR180 & WHR350
Installation and Commissioning Guide
To store fan speed
press +and F
To not save press OK
Energy–Saving Whole House Heat Recovery Unit
MA RKE TI NG D IV IS IO N
International House, Peartree Road, Stanway, Colchester, Essex CO3 0JL
Tel: +44 (0) 1206 713800 Fax: +44 (0) 1206 543126
Email: enquiries@titon.co.uk Web: www.titon.com
BM813_WHR_installation_instructi1 1 14/08/2007 12:24:59
Control switch wiring diagram.
Before installation and commissioning you will need:
• WHR180 or WHR350 manufacturer’s installation and user instructions.
• Titon ventilation system design specification and parts list.
• A copy of Standard Assessment Procedure 2005 - Appendix Q - MVHR Installation Guide
(available from www.sap-appendixq.org.uk/documents/MVHR_Installation_Guide_Final.pdf).
• Calibrated cone anemometer or similar airflow measuring device.
• Tool to lock the room ventilation terminals.
Installation guide
Titon recommend the installation guidance given in Standard Assessment Procedure 2005 - Appendix
Q of the MVHR Installation Guide is followed; not doing so can lead to problems in commissioning or
failure of the system to meet the requirements of applicable Building Regulations*.
Commissioning
Note: The instructions included in this commissioning guide are product specific and take precedence
over some parts of Section 2: Commissioning Guidance of Appendix Q MVHR Installation Guide.
Before switching the unit on for the first time ensure that all ventilation terminals (extract and input)
are fully open and the unit filters are present and clean.
To turn on unit press “OK” and “+” simultaneously
WHR180 & WHR350 - Installation and Commissioning Guide
The fan speeds of the WHR180 and WHR350 are factory set to 75 (program 1) and 100 (program 2).
These must be modified in accordance with the Titon system design specification.
a Speed Setting Control Switch Position
b Speed Setting
Modifying fan speeds
Step 1 - Select fan speed that requires modification.
• Press Ffor 3 seconds to activate ‘settings menu’.
• Use +to select desired parameter.
Step 2 - Set fan speed, refer to the Titon system design specification for fan speed values.
• Press OK for 1 second to display the fan speed value.
• Modify fan speed value using the +or –.
User
Setting
Speed Setting
1 Setting 1
2 Setting 2
3 Not Used
4 Not Used
5 Not Used
Press Ffor 3 seconds to
activate ‘settings menu’
Use +to select desired
parameter
Press OK for 1 second
to display the fan speed
value
Modify fan speed value
using the +or -
BM813_WHR_installation_instructi2 2 14/08/2007 12:25:00

This manual suits for next models

1

Other Titon Heating System manuals

Titon ECOaura HRV3 PH User manual

Titon

Titon ECOaura HRV3 PH User manual

Titon HRV1 Q Plus User manual

Titon

Titon HRV1 Q Plus User manual

Titon HRV1.5 Q Plus User manual

Titon

Titon HRV1.5 Q Plus User manual

Popular Heating System manuals by other brands

KOB KOB PYROT SERIES Operation and maintenance instructions

KOB

KOB KOB PYROT SERIES Operation and maintenance instructions

System air Villavent VR-300 TK/B/3 User and maintenance instructions

System air

System air Villavent VR-300 TK/B/3 User and maintenance instructions

System air SAVE VTR 700 user manual

System air

System air SAVE VTR 700 user manual

Magic-Pak MGE4-09-18 Installation and maintenance instructions

Magic-Pak

Magic-Pak MGE4-09-18 Installation and maintenance instructions

N'oveen EB350 user manual

N'oveen

N'oveen EB350 user manual

Soler & Palau ORKA HR D150 manual

Soler & Palau

Soler & Palau ORKA HR D150 manual

Kroll HM200 Instruction handbook

Kroll

Kroll HM200 Instruction handbook

Intertek GPG 16 SEER installation instructions

Intertek

Intertek GPG 16 SEER installation instructions

Olmar GENESIS Installation and use instruction

Olmar

Olmar GENESIS Installation and use instruction

Vasco Energy plus Installation, use and maintenance instructions

Vasco

Vasco Energy plus Installation, use and maintenance instructions

Empire 682161 installation instructions

Empire

Empire 682161 installation instructions

PAW HeatBloc MC42 Installation and operation instructions

PAW

PAW HeatBloc MC42 Installation and operation instructions

ThermaWave PureHeat Cub owner's manual

ThermaWave

ThermaWave PureHeat Cub owner's manual

Carrier WEATHERMAKER 48A2 Series Wiring diagrams

Carrier

Carrier WEATHERMAKER 48A2 Series Wiring diagrams

Vent-Axia Air Minder Plus Installation, Connection and set up Instructions

Vent-Axia

Vent-Axia Air Minder Plus Installation, Connection and set up Instructions

SHUFT UniMAX-R 2800SE Technical manual

SHUFT

SHUFT UniMAX-R 2800SE Technical manual

Aqua-Hot 400 series Service manual

Aqua-Hot

Aqua-Hot 400 series Service manual

Oxygen X-Air V400 Installation and operation manual

Oxygen

Oxygen X-Air V400 Installation and operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.