Toho Electronics TTM-i4N SERIES User manual

NOTICE/WARNING BEFORE OPERATION USE
ACCESSORY & CONFIGURATION
TTM-i4N SERIES USER'S MANUAL
: Cautions,Danger,Refer to a manual
: Alternating current
: Reinforced/dual insulation
: Cautions,Danger of Electric Shock
The meaning of the symbols indicated on the label found at the side of the unit is as follows.
CAUTION
WARNING
Due to mishandling,the serious damages may occur to the operator,such as death,
electrocution or skin burn.
Owing to mishandling,the operator may be inflicted with slight injury,or may cause some
damage to the unit.
1) Please be sure that the unit enclosed in packing carton is a right model before using.
2) Kindly check the following accessory being contained in that carton box.
3) Model Configuration
Thank you for purchasing model TTM-i4N SERIES Digital Temperature Controller.
Please go through this Instruction Manual carefully and use the unit in proper manner.
If the unit is used in a manner not specified by the manufacturer,the protection provided the unit may be impaired.
TTM-i4N- -A
OUT1Option
Code
OUT1
R
Relay Contact Output
P
SSR Driving Voltage Output
Option
B
OUT2/EV2 Relay Contact Output
SPECIFICATIONS
※Clean the unit by well squeezed cloth with water.
OUTER DIMENSION
PANEL CUTOUT & INSTALLATION
WIRING
For change of display
For action of function setting
Up down key for change of setting value.
Holding the U/D keys changes value at a rapid rate.
Measured value indication,Charactor indication
F KEY
M KEY
▲▼KEY
PV
Set value indication,Operation quantity indicationSV
Output monitor(appears when OUT1 is ON)OUT
Alarm1 monitor(appears when EV1 is ON)AL1
・When fitting the product,give more than 12 mm space between the upper / lower / left & right
・Install the unit in either horizontal or vertical ( upward ) direction.
①
②
③
④
⑤
⑥
⑦
⑧
⑨
⑩
OUT1
SSR Driving Voltage Output DC12V
② ③
② ③
+ -
OUT2/EV2
Relay Output AC250V 1A (Load resistance)
Relay Output AC250V 3A (Load resistance)
① ⑥
POWER SUPPLY
100 to 240V AC 50/60HZ 6VA
(NO polarity)
④
⑤
EV1
⑦ ⑥
Temp. INPUT
RTD
⑧
⑨
⑩
b
B
A
TC
⑧
⑨
⑩
-
+
Exactly same potential wires for EV1 and EV2
circuits can be connected.
※Terminal ⑥
・Do not touch the terminal part while the power is on.
AC100 to 240V, 50/60Hz
85% to 110% of the rated voltage
Operating Voltage Range
Input Power Requirments
6VA MAXPower Consumption
EEPROMMemory Element
a) Thermocouple Input ( type:K,J,R,T,N,S,B )
b) 3-wire Resistance Temperature Detector Input ( type:Pt100,JPt100 )
(Changeable by input type selection)
3 kinds of PID,ON/OFF
Input of Sensor
Control Method
a) Relay Contact Output AC250V 3A MAX
b) SSR Driving Voltage Output DC12V 600Ω(ormore)
( Output type depends on the model. )
OUT1 (Control Output )
Relay Contact Output AC250V 1A MAX
Relay Contact Output AC250V 1A MAXOUT2 / EV2 ( Option )
Event1
0 to 50℃, 20 to 90%RH ( Avoid making of dew )
-25 to 75℃, 5 to 95%RH ( Avoid making of dew )
Operation Environment
Storage Environment
Less than 100 gms.Weight
Overvoltage Category Ⅱ
Installation Environment
Keep away from the following:
・Gas of corrosion,dust and oily smoke.
・The electrical noise of the generator.
・The influence of electromagnetic field.
・Mechanical vibration and shock.
・The direct sunlight.
Location of the Unit Setting
Installation Attachment
Watertight packing
※Thispacking is not attached
・The use of Noise Filter close to the Power Supply terminal is recommended.
Recommended Noise Filter:RSEL-2002W/A(available from TDK Lambda)
Noise filter's terminal 3 and 4 should be connected to the unit.
Noise filter's body may or may not to be connected to frame ground. Both are acceptable.
・Make sure the wiring is done correctly for any wires with polarity ( + and - ).
・For relay contact output, “C : common” and “NO : normal open” .
・Temp.INPUT and OUT1 in case of SSR Output,only the secondary circuits
with reinforced/dual insulation from the primary side can be connected.
・A conformity wire : copper / AWG18-24 / Temp.rating 80℃
・Use specified size (M3.5 width 7.3 mm or less) crimped terminals for wiring and
machines & tools.
・Tightening torqe : 0.5 Nm ( 5kgfm, 4.43 lb.fin)
CAUTION BEFORE CONTROL
PID Control
Better control result is achieved as opposed to that of ON/OFF control.
Life span of relay is shorter,as output exists freduently with relay contact.
Merit
Demerit
Merit
Demerit
ON/OFF Control
Life span of relay is generally longer,as it is ON when temperature is below SV
and it is OFF when temperature is over SV ( For heating control ).
Control value is worse in comparison with that of PID control.
・Setting program is stored after power OFF,as non-volatile memory is equipped with
・Either thermocouple or R.T.D ( Pt100 / JPt100 ) is selectable input type.
For suitable apprication,please select most appropriate input type and adjust input setup.
・PID or ON/OFF control is selective for the optimal performance and each detail of features is
specified in the table as bellow.
TTM-i4N SERIES controllers for setting storage.
NO C
NO CNO C
When having the purchased controller at hand,please be sure that its correct model.
See the following “Model Configuration” .
The following symbol marks provide to prevent incident or damage.Kindly refer to the details
of the WARNING/CAUTION when using for the first time.
For prevention of its malfanction,do not push the front key with sharp points.
Spare terminal must not be used for other purposes.
CAUTION
Make sure the correct wiring connection before turning on electricity.
Mis-wiring may cause malfunction of the unit and fire.
Never modify the unit to prevent damage or incident such as malfunction and fire etc.
・Please put this user's manual aside for your reference,when operating the unit.
・Copy or reprint of this manual,wholly or partially,is not allowed.
・The contents of this manual may change without notice in future.
WARNING
INSTALLATION CONDITIONS
・Indoor use
・Altitude up to 2000m
・Pollution Degree 2
・Installation Attachment ( For installation,please see “PANEL CUTOUT & INSTALLATION” on the right.)
・This user's manual : 1 copy
Code
・This product is intended for use with industrial machineries,machine tools and measurement
instruments.(It is not to be used with medical equipment which involves human lives).
CAUTION
& backface portion to the product and the peripheral device or plates.
・When you use compressed lead wire to install multiple units,please be careful sufficiently
not to touch the other lead wires.
CAUTION
Relay Output AC250V 1A (Load resistance)
WARNING
・This Controller is not equipped with overcurrent protection device ( Fuse ).
when making power source wiring. A Fuse is connected to the live side.
Please prepare semi-time lag fuse ( rated voltage : 250V, rated current : 1A )
48
( 2)
4 59
48
Single Unit Istallation
Multiple Unit Installation
45
+0 .6
0
60(ormore)
45
0
(48×n−3)
+ 0 .6
0
+ 0 .6
PARTS INDICATION
AL2
RDY lamp(It appears in Ready condition)RDY
※OUT2 / EV2 is not available when Option-B is not specified.
CAUTION
Alarm2 monitor(appears when EV2 is ON)
It also lights when OUT2 is ON in Heating/Cooling Control mode.
It lights-up when the set value in the Temp. data is Celsius.
It lights-up when the set value in the Temp. data is Fahrenheit.
℃
℉
when Option-B is not specified.
WARNING

<SET1 : Input setting mode>
SET1
INP
1. Setting item selection screen
2. Input type setting
Select input type
00
INP
3. PV compensation gain setting
0.50 ~2.00
PVG
100
4.
PV compensation zero setting
-199 ~999
-199.9 ~999.9
PVS‘
0
5. PV Filter setting
0.0 ~99.9
PDF
00
6. Decimal point setting
0:Not required
0.1:Required
(Except R/S/B Thermocouple)
DP
0
7. Temperature unit setting
℃:
Celsius
℉
:Fahrenheit
C/F
*C
<SET2 : Key function setting mode>
SET2
KEY
1. Setting item selection screen
Setting related to
<SET3 : Control setting mode>
SET3
CNT
1.Setting item selection screen
<SET4 : EV1 setting mode>
SET4
AL1
Setting related to controlSetting related to input
key functions
<SET5 : EV2 setting mode>
SET5
AL2
<SET6 : Timer setting mode>
SET6
TIME
<SET7 : LCD setting mode>
SET7
LCD
<SET0 :
Priority screen setting mode
>
SET0
PR1
Setting for priority screen
(Refer to Ex.1.)
M key
2.
Priority screen 1 setting
PRI1
OFF
Select 1st screen on
Run mode B
Select 2nd screen on
Select 3rd screen on
Select 4th screen on
Select 5th screen on
3.
Priority screen 2 setting
PRI2
OFF
4.
Priority screen 3 setting
PRI3
OFF
5.
Priority screen 4 setting
PRI4
OFF
6.
Priority screen 5 setting
PRI5
OFF
7.
Priority screen 6 setting
PRI6
OFF
8.
Priority screen 7 setting
PRI7
OFF
9.
Priority screen 8 setting
PRI8
OFF
10.
Priority screen 9 setting
PRI9
OFF
<When select PID control> <When select ON/OFF control>
KThermocouple
J
R
T
N
S
00
01
02
03
04
05
B
Pt100
JPt100
06
10
11
●Setting mode●POWER ON
●RUN mode
A.Primary screen
Measured value
Set the temperature
required
Set value
(Press for 4 seconds)
▲KEY
▼KEY
▲KEY
▼KEY
●Protect setting mode
Setting screen
Mode to set the protection level
“Input type setting screen” appears for 4seconds,
then it will oriceed to “Run mode” .
PTLV
0
Non-Protect
0
1
2
3
parameters except for the following:
Setting Change not possible.
PV compasation zero setting
Alarm reset
AT start/reset
Proportional band setting for OUT1/OUT2
Integral time setting
Deviative time setting
Control sensitivity setting for OUT1/OUT2
Upper limit setting for EV1/EV2
Lower limit setting for EV1/EV2
・The Setting Mode Parameter blinds
・Setting change for SV/Priority Screen is Possible
B.Priority screens (1 ~9)
Priority displays by setting
and shows max.9 screens by setting.
●EX1.Priority screens & its setting
This function enables the selection of the most necessary screen indication
from all the screen indication found in the setting mode,and assign it to
eg:Basic screen → OUT1 manipulated value → Setting high limit for EV1
*Screen is shifted when pressing M key each time.
the RUN mode on priority basis.
Please select priority screen indication through the priority screen setting mode.
●EX2.Function key works
This function is to enable F key to use as a specific key,for the following actions
selected in F key setting belonging to setting mode.
1. Digit shift
Setting digit shift is enabled when setting value is changed.
2. RUN/READY
Control stop(READY) and control performance(RUN) are
alternately switched by F key.
3. AT Start / Reset
AT(Auto -Tuning) starts instantly after pressing F key.
Start and Reset are alternately switched by F key.
4. Timer Start / Reset
Press once for function.
Press once for function.
5. Alarm Reset
6. Enter
Function
Effective
in all modes
Effective only
in Operating mode
●EX3.
To select PID
Features of type A,B,FUZZY
TypeA
If control is unstable under self-tuning,
please change to type A ,B or FUZZY and also ON/OFF control.
TypeB
FUZZY
the RUN mode on priority basis.
Basic PID
Over shoot protection PID
Effectively control the over shoot in the beginning of PID control.
●EX4. ARW (Anti-Reset-Windup)
ARW take effect for overshooting by over-integral of PID action.
・ARW controls integral action (PV accords with SV).
・If integral value goes down,it takes effects.
If integral value is set “0” ,it stops integral action.
Table1. To select input sensors and setting range. unit : ℃
Symbol
K
Thermocouple
Low limit
~
High limit
-200 ~ 1372
0.0 Setting
J -200 ~ 850
R 0 ~ 1700
T -200 ~ 400
N -200 ~ 1300
S 0 ~ 1700
B 0 ~ 1800
Pt100 -200 ~ 500
JPt100 -200 ~ 500
OPERATION FLOW AND SETTING MENU
*12*13
(Press for 2 seconds)
・Setting change is possible with SV only.
・The priority screen is with indication/
・All setting mode parameters will be blinded.
・SV is with indication / setting change not possible.
not possible.
・Priority Screen is with indication / setting change
・All setting mode parameters will be blinded.
Press for
2 seconds
Effective
in all modes
"
"
"
"
"
"
Select 6th screen on
Select 7th screen on
Select 8th display on
Select 9th screen on
M key
M key
M key
M key
M key
M key
M key
M key
M key , return to 1
M key , return to 1
M key
M key
M key
M key
M key
"
"
"
"
"
"
M key
M key
M key
M key
M key
seconds
times
-199.9 ~ 999.9
-199.9 ~ 850.0
-199.9 ~ 400.0
-199.9 ~ 999.9
-
-
-199.9 ~ 500.0
-199.9 ~ 500.0
-
*1
No indication when the type of control OUT1 is ON/OFF Control.
*2
No indication when the type of control OUT1 is PID Control.
*3
No indication when the OUT1 loop error determination time is “0” .
*4
No indication when the type of control OUT2 is either “None” or “EV2” .
*5
No indication when the type of control OUT2 is ON/OFF Control.
*6
No indication when the type of control OUT2 is PID Control.
*7
No indication when the OUT2 loop error determination time is “0” .
*8
No indication when the EV1 Function is set at “No Function” .
*9
No indication when the EV1 Function is not used in the Upper Limit Alarm.
*10
No indication when the EV1 Function is not used in the Lower Limit Alarm.
*11
No indication when the EV1 & 2 Functions to “No Function” .
*14
No indication when EV2 Function is set at “No Function” .
*15
No indication when the EV2 Function is not used in the Upper Limit Alarm.
*16
No indication when the EV2 Function is not used in the Lower Limit Alarm.
*17
No indication when the EV 1 & 2 Functions to “No Function” .
*12
No indication when Option-B is not specified.
*13
No indication when the type of Control OUT2 is set to anything other than “EV2” .
*18
No indication when the Timer Output is set to “Timer Not Used” .
*19
No indication when the Timer Function is set to other than “SV Start” .
2. Function key function setting
FU
00++
① Function setting
0 : None
1 : Digit shift
2 : RUN/READY
3 : AT start/stop
4 : Timer start/stop
5 : Alarm reset
6 : ENTER
②
Pressing time setting
0 : None
1 : Pressing time 1 second
2 : Pressing time 2 seconds
3 : Pressing time 3 seconds
4 : Pressing time 4 seconds
5 : Pressing time 5 seconds
3. Key-lock setting
0
LOC
Lock OFF
Lock all
Lock run mode
Lock except run mode
※Protect Level Setting is not subjected to
Key-Lock Setting.
0
‘1
‘2
‘3
4. Alarm reset
0 0
ALRS
No alarm occurrence
Only EV1 is occurring
Only EV2 is occurring
0 0
0 1
1 0
1 1
Both EV1/EV2 are occurring
Screen for Alarm reset of EV1/EV2
※Press F key for 1 second to reset the alarm.
(The indication momentarily disappears as
the Alarm reset is executed).
2. SV limiter upper limit
SLH‘
1200
3. SV limiter lower limit
SLL‘
0
4. Control mode setting
RUM
MD
Control start
Control stop
Manual
RUN
RDY
MAN
Setting for control mode
5. Control type setting
CNT
‘020++
①Function
0 : TypeA
1 : TypeB
2 : Fuzzy
③Control type of OUT2
0 : None
1 : PID control
2 : ON/OFF control
3 : EV2 output
②Coutrol type of OUT1
1 : PID control
2 : ON/OFF control
①
②
③
②
①
※When Option B is not specified,Control type of
OUT2 shall be fixed at “None” .
6. Forward/reverse operation setting
0:Reverse operation
DIR‘
0
1:Forward operation
7. Operating amount for OUT1
MV1‘
00
M key M key
8. Tuning type setting
1
TUN
*1
Auto-tuning
Self -tuning
Auto-tuning
Self -tuning
Auto-tuning
1
2
3
4
5
:OUT1
: OUT1
: OUT2
: OUT2
: OUT1/OUT2
9. AT coefficient setting
ATG
10
10. AT sensitivity setting
ATC
2
11. AT start/stop
AT
OFF
AT stop
AT start
※ATstart and ATstop are alternately switched
OFF
ON
12.
Proportional band setting for OUT1
P1
30
13. Integral time setting
I
0
14. Deviative time setting
D
0
15.
Proportional cycle setting for OUT1
T1
20
16. ARW setting (see Ex.4)
ARW
1100
17. Operating amout limiter upper limit for OUT1
MLH1
1000
18. Operating amout limiter lower limit for OUT1
MLL1
00
19. Sensitivity setting for OUT1
C1
1
21. Loop anormaly time setting for OUT1
LOP1
0
seconds
22.
Loop anormaly PV change threshold for OUT1
PS1
0
23.
Loop anormaly PV threshold for OUT1
TS1
0
24.
Protection OFF timer time setting for OUT1
FDT1
0
25.
Protection ON timer time setting for OUT1
NDT1
0
26. Operating amount for OUT2
Displays operating amount for OUT2
and set the amount on manual control.
MV2‘
00
0.0 ~100.0(%)
MLL2 ~MLH2
(%)
27.
Proportional band setting for OUT2
0.10~10.00
P2
100
28.
Proportional cycle setting for OUT2
T2
20
29.
Operating amout limiter upper limit for OUT2
MLH2
1000
MLL2 ~
100.0
%
30.
Operating amout limiter lower limit for OUT2
MLL2
00
0.0
~MLH2
%
20. OFF point position setting for OUT1
CP1
0
*1
*2
*3
*3
*2
*2
*4
*4 *5
*4 *5
*4 *5
*4 *5
*1
*1
*1
*1
*1
*1
*1
*1
*1
*2
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
Mkey (Go to 21)
31. Sensitivity setting for OUT2
C2
1
32. OFF point position setting for OUT2
CP2
0
*4 *6
*4 *6
33.Loop anormaly time setting for OUT2
LOP2
0
※At “0” setting,there is no loop error determination.
34.
Loop anormaly PV change threshold for OUT2
PS2
0
35.
Loop anormaly PV threshold for OUT2
TS2
0
36.
Protection OFF timer time setting for OUT2
FDT2
0
37.
Protection ON timer time setting for OUT2
NDT2
0
*4 *7
*4
38. Balance less / Bump less
BMP
1
No Balance less / Bump less function
With Balance less / Bump less function
0
1
39. Manual reset setting
PBB
00
0.0 ~100.0%
-100.0 ~100.0% (
Heat / Cool
)
*1
40. Dead band setting
DB
0
-100 ~100
*4
41. Ramp time setting
RMP
00
※Ramp function OFF at 0.0
42. Control back up function setting
PWZ
00
0.0 ~10.0
*4 *7
*6 *4
2. EV1 setting mode
EV1 alarm function 1 setting
A1F1
000++
①Function
0 : None
1 : Deviation upper and lower limits
2 : Deviation upper limit
3 : Deviation lower limit
4 : Deviation range
5 :
Absolute value upper and lower limits
6 : Absolute value upper limit
7 : Absolute value lower limit
8 : Absolute value range
③
②
①
③Control mode interlocking function
②Add-on function
0 : None
1 : Hold
2 : Standby
3 : Delay
4 : Hold+Standby
5 : Hold+Delay
6 : Standby+delay
7 : Hold+standby+delay
3. EV1 alarm upper limit setting
A1H
0
-1999 ~3276 or -199.9 ~999.9
※In case of thermocouple R/S/B : -1999 ~3276
4. EV1 alarm lower limit setting
A1L
0
5. EV1 alarm sensitivity setting
A1C
0
0~999 or 0.0 ~999.9
6. EV1 alarm delay timer setting
A1T
0
0〜9999
seconds
7. EV1 alarm function 2 setting
EV1 alarm function 2 setting
for PV error
A1F2
000++
①Function
0 : None
1 : PV error
③
②
①
②Add-on function
0 : None
1 : Hold
2 : Delay
3 : Hold+Delay
8. EV1 alarm function 3 setting
EV1 alarm function 3 setting
A1F3
00++
①Function
0 : None
1 : Loop error
②
①
②Add-on function
0 : None
1 : Hold
for loop anormaly
9. EV1 alarm polarity setting
A1P
0
Normal open
Normal close
0
1
*8 *9
*8 *10
*8
*11
*12*14
*15
*12*14
*12*14
*12*17
*12
*12
*12
*16
0 : All modes
1 : RUN/ MANUAL mode only
2 : RUN mode only
*12
M key
M key
M key
M key
M key
2. Timer output setting
0
TMO
Non-use timer function
Control
EV1 output
EV2 output
※“3” is not selectable when Option-B is not specified.
0
‘1
‘2
‘3
3. Function setting
1
TMF
Auto start
Manual start
EV1 start
Auto start
Manual start
1
2
3
4
5
EV1 start
SV start
EV2 start
6
7
8
EV2 start
9
( ON delay )
( ON delay )
※“8” and “9” are not selectable
when Option-B is not specified.
4. Unit setting
H/M
1
Hour / Minute
Minute / second
1
2
5. Start SV permissible range setting
TSV
0
6. Time setting
TIM
00 :00 ~99 :59 (Hour/Minute)
00 :00 ~99 :59 (Minute/second))
7. Remaining time monitor
TIA
00 00
Screen for remaining time monitor
2. Brightness setting
LLV
100
5~100
%
3. Dimming function setting
LRFT
0
0~9999
seconds
※No dimming function when set to “0” .
4. Dimming Brightness setting
LRLV
5
0~100
%
:
00 00
:
*18
*18*19
*18
*18
*18
M key
M key
M key
M key
M key , return to 1
M key
M key
0.1 ~10.0
times
% per
SLL
〜
SLH
seconds
1〜120
%
0.0 ~110.0
%
MLL1 ~
100.0
%
0.0
~MLH1
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
0.1 ~200.0
seconds
0~3600
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
*6 *4
1.
Setting item selection screen
Start and Reset are alternately switched by F key.
Digit under selection will blink.
M key , return to 1
M key
M key
Setting range
:
Setting range
:
Setting unit
:
Setting unit
:
Setting range
:
Setting unit
:
by F key.
0 〜999 or 0.0 〜999.9
Setting range
:
Setting unit
:
-199 ~999 or -199.9 ~999.9
Setting range
:
Setting unit
:
0~9999
seconds
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
※At “0” setting,there is no loop error
PV change determination.
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
※At “0” setting,there is no loop error determination.
Setting range
:
Setting unit
:
seconds
Display amount
:
Setting amount
:
Setting range
:
Setting unit
:
Low to high limit
※Keep the difference of more than 5 degrees(℃or℉)
Setting range
:
Setting unit
:
Low to high limit
betweenLowand high limit of the SV limiter.
※At “0” setting,there is no loop error
PV threshold determination.
※At “0” setting,there is no loop error
PV change determination.
※At “0” setting,there is no loop error
PV threshold determination.
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
0~99
Minuites
Setting range
:
Setting unit
:
0~99
Minuites
Setting range
:
Setting unit
:
Setting range
:
Setting range
:
-100.0 ~100.0
℃or ℉
Setting unit
:
℃/min. or ℉/min.
Setting range
:
Setting unit
:
※Control back up function OFF at 0.0
Setting range
:
Setting unit
:
℃or ℉
℃or ℉
℃or ℉
℃or ℉
℃or ℉
℃or ℉
℃or ℉
℃or ℉
℃or ℉
℃or ℉
℃or ℉
℃or ℉
℃or ℉
1.Setting item selection screen
Setting range
:
Setting unit
:
℃or ℉
-1999 ~3276 or -199.9 ~999.9
※In case of thermocouple R/S/B : -1999 ~3276
Setting range
:
Setting unit
:
℃or ℉
Setting range
:
Setting unit
:
℃or ℉
Setting range
:
Setting unit
:
M key
M key
M key
③
Control mode interlocking function
0 : All modes
1 : RUN/ MANUAL mode only
2 : RUN mode only
M key , return to 1
M key , return to 1
2. EV2 setting mode
EV2 alarm function 1 setting
A2F1
000++
①Function
0 : None
1 : Deviation upper and lower limits
2 : Deviation upper limit
3 : Deviation lower limit
4 : Deviation range
5 :
Absolute value upper and lower limits
6 : Absolute value upper limit
7 : Absolute value lower limit
8 : Absolute value range
③
②
①
③Control mode interlocking function
②Add-on function
0 : None
1 : Hold
2 : Standby
3 : Delay
4 : Hold+Standby
5 : Hold+Delay
6 : Standby+delay
7 : Hold+standby+delay
3. EV2 alarm upper limit setting
A2H
0
-1999 ~3276 or -199.9 ~999.9
※In case of thermocouple R/S/B : -1999 ~3276
4. EV2 alarm lower limit setting
A2L
0
5. EV2 alarm sensitivity setting
A2C
0
0~999 or 0.0 ~999.9
6. EV2 alarm delay timer setting
A2T
0
0〜9999
seconds
7. EV2 alarm function 2 setting
EV2 alarm function 2 setting
for PV error
A2F2
000++
①Function
0 : None
1 : PV error
③
②
①
②Add-on function
0 : None
1 : Hold
2 : Delay
3 : Hold+Delay
8. EV2 alarm function 3 setting
EV2 alarm function 3 setting
A2F3
00++
①Function
0 : None
1 : Loop error
②
①
②Add-on function
0 : None
1 : Hold
for loop anormaly
9. EV2 alarm polarity setting
A2P
0
Normal open
Normal close
0
1
0 : All modes
1 : RUN/ MANUAL mode only
2 : RUN mode onl
M key
M key
M key
M key
M key
Setting range
:
Setting unit
:
℃or ℉
-1999 ~3276 or -199.9 ~999.9
※In case of thermocouple R/S/B : -1999 ~3276
Setting range
:
Setting unit
:
℃or ℉
Setting range
:
Setting unit
:
℃or ℉
Setting range
:
Setting unit
:
M key
M key
M key
③
Control mode interlocking function
0 : All modes
1 : RUN/ MANUAL mode only
2 : RUN mode only
M key , return to 1
1.Setting item selection screen
EV2 output function setting
1.Setting item selection screen
Setting concerned with
timer parameters
EV1 output function setting
1. Setting item selection screen
Setting related to LCD
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
M key
M key
M key
M key , return to 1
( ON delay )
( OFF delay )
( OFF delay )
( OFF delay )
( OFF delay )
( ON delay )
( OFF delay )
0~999 or 0.0 ~999.9
Setting range
:
Setting unit
:
℃or ℉
Setting range
:
0 〜999 or 0.0 〜999.9
0 〜999 or 0.0 〜999.9
0 〜999 or 0.0 〜999.9
0 〜999 or 0.0 〜999.9
0 〜999 or 0.0 〜999.9
-199 ~999 or -199.9 ~999.9
0~9999
0.0 〜999.9
0 〜999 or 0.0 〜999.9
Setting range
:
Setting unit
:
0~3600
1〜120
Setting range
:
Setting unit
:
seconds
Setting range
:
Setting unit
:
Setting range
:
Setting unit
:
M key (Go to 33)
M key
M key
M key
※Timerstart and stop are alternately
switched by F key.
0~99
Minuites
0~99
Minuites
~~~~
Displays whenever input value exceeds the high limit of display range.
Also displays when the wire is snapped off thermocouple and that of R.T.D.
____
Displays whenever input value exceeds the low limit of display range.
ERR0cv
Displays at memory error.
ERR1cv
Displays at input circuit error.
ERR2cv
Displays when auto-tuning does not end after 3 hrs.,
or when error occurs during the auto-tuning.
Displays when the parameter change is attempted during key lock mode.
LOC
Displays when the control mode change is attempted
FUNC
during which function keys are allocated to RUN/READY.
Displays during auto-tuning.
AT
Displays when the control mode change is attempted
TIME
Other Display Indication
during which the timer is in use..
TOHO ELECTRONICS INC.
2-4-3 NISHIHASHIMOTO MIDORI-KU SAGAMIHARA KANAGAWA
252-0131 JAPAN
Phone: +81-50-3535-9960 Fax: +81-42-700-2118
http://www.toho-inc.com
Head office:
E-Mail:
URL:
▲KEY
▼KEY
▲KEY
▼KEY
▲KEY
▼KEY
▲KEY
▼KEY
▲KEY
▼KEY
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
M key
Run mode B
Run mode B
Run mode B
Run mode B
Run mode B
Run mode B
Run mode B
Run mode B
Magnification to
MV1
Displays operating amount for OUT1
and set the amount on manual control.
0.0 ~100.0(%)
MLL1 ~MLH1
(%)
Display amount
:
Setting amount
:
※Keep the difference of more than 5 degrees(℃or℉)
betweenLowand high limit of the SV limiter.
M key
<When select PID control>
<When select ON/OFF control>
Blind setting mode
****
ON
Value is indicated.
No indication
ON
OFF
**** :
Selected parameter is indicated.
M key (Press for 10 seconds)
Indication disappears momentarily
SET0
ON
SET1
ON
▲
▼
SET2
ON
▲
▼
SET3
ON\
▲
▼
SET4
ON
▲
▼
SET5
ON
▲
▼
SET6
ON
▲
▼
▲
▼
SET7
ON
PRI1
ON
INP
ON
FU
ON
SLH
ON\
A1F1
ON
A2F1
ON
TMO
ON
LLV
ON
▲
▼
M key M key M key M key M key M key M key M key
to
SET0
M key (Press for 2 seconds)
Reset the power for Blind setting mode OFF.
Shift to Blind setting mode
※
ON/OFF is changed by F key.
●POWER ON
“Input type setting screen” appears for 4 seconds,
then it will procceed to “Run mode” .
●RUN mode
F
key (Press for once)
M
key (Press for once)
●RUN mode
Please select parameters to be blinded
through the Blind setting mode.
Table of contents
Other Toho Electronics Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Conotec
Conotec FOX-301 Series user manual

Tense
Tense DT-36Y manual

Franke
Franke ZAQUA017 Installation and operating instructions

Ranco
Ranco ETC Series Installation data

S+S Regeltechnik
S+S Regeltechnik THERMASGARD TF 43 Dimensions and installation information

meitav-tec
meitav-tec MTS/V50 Owner manual and technician settings

CommScope
CommScope FDH 3000 user manual

Xetron
Xetron STC-1000Pro user manual

AERMEC
AERMEC CXS 1207 H TECHNICAL AND INSTALLATION

IFM Electronic
IFM Electronic efector 600 TN21 Series operating instructions

ABB
ABB Caldion FCR-F-2-4.2.21.1 Series product manual

ABB
ABB i-bus 6108/18-BS-500 Technical reference manual