Toky SD Series User manual

Ⅳ.
Specification
Ⅲ
.Order Information
Ⅱ.Model Illustration
1
2 3
2.Signal parameters
2.Cable caution:
1)Please use specified compensation wire in the place of TC input;Please use insulated TC if the measured device is heated metal.
2)Please use the cable of lesser resistance in the place of RTD input,and the cable(3 wire) must be no resistance difference,but the total
length is within 5m.
3)In order to avoid the effect of noise,please put the input dignal away from meter cable,power cable,load cable to wiring.
4)In order to reduce the power cables and the load power cables on the effect of this product,please use noise filter in the place
where easy to effect.You must install it on the grounding of the disk if you use the noise filter,and make the wiring to be shortest
between noise filter output side and power connectors.Don`t install fuse and switch on the wiring of noice filter output side,otherwise it
will reduce the effect of noise filter.
5)It takes 5s from input power to output.If there is a place with interlocking actions circuit signal,please use timer relay.
6)Please use twisted pair with a shield for analog output line,to ensure the reliabilty of signal.
7)Please use twisted pair with a shield for remote RS485 communication cable,and deal with the shield on the host side earth,
otherwise it will reduce the effect of noise filter.
8)This product is not the fuse;please set according to rated voltage 250V,rated current 1A if you need;fuse type:relay fuse.
9)Please use the suitable screw force and crimp terminal.
The screw terminal size:
M3X8 (
with
6.8X6.8
square base)
Recommended tightening torque:
0.4N.m
Proper cables:0.25~1.65mm single cable/multiple core cable
10)Please don`t put the Crimp terminal or bare wire part contact with adjacent connector.
Sensor Meter User Manual
Features:
●The red LED display value of real time,maximum & minimum on the upper row,and the green LED
display meansure unit or alarm value.
●The maximum 3 loop alarm output
●Many kinds of linear signal inputs or temperature sensor signals
●Analog analog,enabling conversion and calibration functions of measure range
●RS485 communication and Modbus-RTU protocol
●Power supply 100 ~240V AC/DC。
●Isolate DC24V feed output(30mA)。
●Peak Hold function,to facilitate record maximum, minimum measurement data
●easy to operate, economical and practical.
1)If the fault of the product or abnormal system lead to a serious accident, please set the appropriate circuit protection outside.
2)Before the connection completely, please do not power. Otherwise it may result in electric shock, fire, malfunction.
3)Do not use the product out of scope of specifications range. Otherwise, it may result in fire, malfunction.
4)Do not use in places with flammable and explosive gas.
5)Do not touch the site of high voltage power terminal site after power. Otherwise, there is danger of electric shock.
6)Do not disassemble, repair and modify this product. Otherwise,it may result in electric shock, fire, malfunction.
1)This product should not be used in a nuclear plant and medical equipment which associated with human life.
2)Some time,it will happen radio interference when the product uses in home environment.It should take adequate
countermeasures.
3)This product has electric shock protection through improved insulation.And when using the product and connecting,it
subject to compliance with specifications.
4)In order to avoid lighting surge,it should set appropriate surge suppression circuits when the product uses in the
environment where the total cable lengh more than 30 metre.
5)The product uses in disk,and avoid to touch the part of high voltage,please take the necessary measure on the final product.
6)Please observe the precautions in this manual, otherwise there is risk of causing significant harm or accident.
7)Please abserve the regulation when wiring.
8)To prevent to damage the machine and prevent to machine failure, the product is connected with power lines or large capacity input and
output lines and other methods please install proper capacity fuse or other methods of protection circuit.
9)Please don't put metal and wire clastic mixed with this product,otherwise it may lead to electric shock, fire, fault.
10)Please tighten screw torque according to the rules.If not,it may lead to electric shock and fire.
11)In order not to interfere with this products to dissipate heat, please don't plug casing around the cooling vent hole and equipment.
12)Please don`t knock or rub the panel with rigid thing.
13)The readers of this manual should have basic knowledge of electrical,control, computer and communications.
14)The illustration, example of data and screen in this manual is convenient to understand,instead of guaranteeing the result of
the operation.
15)In order to use this product with safety for long-term,regular maintenance is necessary. The life of some parts of the equipments
are by some restrictions, but the performance of some will change for using many years.
16)Without prior notice, the contents of this manual will be change. We hope these is no any loopholes, if you have questions or objections,
please contact us.
Caution of Install & Connection
1.Installation:
1)This product is used in the following environmental standards.
(IEC61010-1)[Overvoltage categoryⅡ、class of pollution 2]
2)This product is used in the following scope:surrounding environment, temperature, humidity and environmental conditions.
Temperature:0~50℃;Humidity:45~85%RH;Environment condition:Indoor warranty,The altitude is less than 2000m.
3)Please avoid using in the following places:
The place will be dew for changing temperature;with corrosive gases and flammable gas;with vibration and impact;with water, oil, chemicals, smoke and
steam
facilities with Dust, salt, metal powder;and with clutter interference, static electric and magnetic fields, noise;where has air conditioning or heating of air
blowing
directly to the site.
4)On the occasion of the installation, please consider the following before installing several.
In order to protect heat saturated, please ensure adequate ventilation space.
Please consider connections and environment,and ensure that the products below for more than 50mm space.
Please avoid to installed over the machine of the calorific value(Such as heaters, transformer, semiconductor operations, the bulk resistance).
When the surrounding is more than 50℃, please using the force fan or cooling fans.But don't let cold air blowing directly to the product.
I. Safety Caution
SD□-A10
SD□-A10B
SD□-RC10B
SD□-RC18B
SD□-IRC10B
SD□-IRC18B
SD□-A10-T
SD□-RC10B-T
SD series sensor meter
C:Version
B: DC 24V auxiliary voltage Blank:No
T:Temperature sensor input Blank:Voltage, current input
10: single input without RS485 18:Single input with RS485
I: DC 4-20mA analog output Blank:No alalog
4: 48W*48H 6: 48W*96H 7: 72W*72H 8: 96W*48H
9: 96W*96H 16:80W*160H 80:160W*80H
A: No alarm C: 2 loop alarm D: 3 loop alarm
Blank: No alarm R: Relay alarm output
Signal input
4~20mA/0~10V
4~20mA/0~10V
4~20mA/0~10V
4~20mA/0~10V
4~20mA/0~10V
4~20mA/0~10V
TC/RTD/mV/RT
TC/RTD/mV/RT
2
2
2
2
2
●
●
●
●
●
●
●
●
●
●
Alarm Auxiliary voltage Analog output Analog output
SD 8 - l R C 10 B T - C
Input
K
J
E
T
N
B
R
S
PT100
CU50
CU100
0~50mV
0~400Ω
0~10V
4~20mA
0~5V
1~5V
0~20mA
Range
-50~1200℃
0 ~1200℃
0 ~850℃
-50~400℃
-50~1200℃
600 ~1800℃
0 ~1600℃
-10~1600℃
-200.0~600.0℃
-50.0~150.0℃
-50.0~150.0℃
-1999~9999
-1999~9999
-1999~9999
-1999~9999
-1999~9999
-1999~9999
-1999~9999
ratio
1℃
1℃
1℃
1℃
1℃
1℃
1℃
1℃
0.1℃
0.1℃
0.1℃
0.01%FS
0.01%FS
0.01%FS
0.01%FS
0.02%FS
0.02%FS
0.01%FS
Accuracy
0.5%FS±3digits
0.5%FS±3digits
0.5%FS±3digits
0.5%FS±2℃
0.5%FS±3digits
0.5%FS±2℃
0.5%FS±2℃
0.5%FS±2℃
0.5%FS±3digits
0.5%FS±3℃
0.5%FS±1℃
0.5%FS±3digits
0.5%FS±3digits
0.5%FS±3digits
0.5%FS±3digits
1%FS±3digits
1%FS±3digits
0.5%FS±3digits
Input impedance/
auxiliary current
>500KΩ
>500KΩ
>500KΩ
>500KΩ
>500KΩ
>500KΩ
>500KΩ
>500KΩ
0.2mA
0.2mA
0.2mA
>500KΩ
0.2mA
>500KΩ
100Ω
>500KΩ
>500KΩ
100Ω
Code
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
K.0 -50.0 ~500.0℃0.1℃0.5%FS±3digits >500KΩ
Symbol
Model
1.Electrical parameters
Sample rate
Relay capacity
Power supply
Power consumption
Environment
Storage environment
4SPS
AC 250V /3A life of rate load>100 thousand times
<6VA
Indoor temperature:0 ~50℃ no condensation; Humidity:<85%RH; Altitude<2000m
-10 ~60℃, no condensation
AC/DC 100 ~240V(85-265V)
SD Series
KKSDE03-A/0-20151208
The instruction explain instrument settings, connections,name and etc,please read carefully before you use the temperature
controller.
Warning
Caution
Current output
Communication port
Insulation impedance
ESD
Pulse traip anti-interference
Lightning surge
Frequency drop
Dielectric strength
Total weight
Material of case
Material of mark
Power-off data protection
Protection level of panel
Safety Standard
DC 4 ~20mA load < 500Ω,Temperature drift 250PPM
RS485 port Modbus-RTU procotol, maximum input:30 units
Input,output,power cabinet>20MΩ
IEC/EN61000-4-2 Contact ±4KV /Air ±8KV perf.Criteria B
IEC/EN61000-4-4 ±2KV perf.Criteria B
IEC/EN61000-4-5 ±2KV perf.Criteria B
IEC/EN61000-4-29 0%~70% perf.Criteria B
Signal input & output & power 1500VAC 1min,below 60V Low voltage circuit between DC500V,1min
About 400g
The case and panel frame PC/ABS (Flame Class UL94V-0)
PET(F150/F200)
10 years,times of writing:1 million times
IP65(IEC60529)
IEC61010-1 Overvoltage category Ⅱ,pollution level 2,levelⅡ(Enhanced insulation)

4
6
5
7
3.Isolation diagram
Power supply
MCU(Ⅱ)
Measure input
Relay
alarm output
Analog output
Communication port
(Ⅰ) Auxiliary power
“ ”:Isolation
Note:when the auxiliary power use for power of external sensor and if the sensor is isolated,it is not isolated between (Ⅰ) and (Ⅱ)
Ⅴ.Name of universal panel
Ⅵ.Unit symbol comparision
20
21
0
1
2
3
4
5
6
7
8
9
10
No
M
cm
mm
kg
g
mg
Mpa
pa
ba
mba
12
11
13
14
15
16
17
18
19
20
21
N
W
KW
RPM
RPS
MPM
MPS
Hz
KHz
mV
V
22
23
24
25
26
27
28
29
30
KV
mA
A
KA
Ω
KΩ
℃
℉
K
1) In the normal measurement mode and when the MME=Y, press “ ” key can switch the max/min/current value circularly.
2) Enter MME, and when it displays “Y” , press “ ” key to restart recording max/min value.
3) In the normal measurement mode,press “ ” key can lock current value,and press again to unlock.
4) Before CAS, CAK calibration functions are used, long press “SET” + “ ” (make sure PSB=0).
Menu shield function,the specification of function symbol as below:
AL1:AD1,AL1,HY1,AE1,DL1A,DL1B;
AL2:AD2,AL2,HY2,AE2,DL2A,DL2B;
AL3:AD3,AL3,HY3,AE3,DL3A,DL3B;
BS:BRL,BRH,OLL,OLH,TEST;
When it display one of function symbol,bottom row will display “Y” or “N” (Y means start the function;N means stop the function)
For example:if the meter have no first alarm circuit,please set the AL1 to “N” and then exit menu.
But now,the menu and submenu will not display AL1,AD1,HY1,AE1,DL1A,DL1B and the alarm function stop to work.
COMM:BAUD,ADDR,DTC;
SF1:CAS , CAK , SQRT;
SF2:DREF,STEP,CJC,RLMR;
-1999~9999
OFF,FL ~ FH
OFF,FL ~ FH
1000/1200
0
2.Directions of menu
HY1
AL2
HY2
AD2 Optional 4 types alarm,if it is 0,the alarm close
Choice of display on botton row:no display,
engineering unit,1loop/2loop/3loop alarm value.
filter coefficient of digital filters.
The higher of value, the greater the filter effect.
0~1000
FL~FH
0、L 、H、Int、Out
0~1000
FL~FH
0~1000
Non、Unit、AL1、
AL2、AL3
1~255
0~5
0~3
1
2
3
4
No.
9
10
11
12
13
14
15
16
17
18
19
AD1
MME
AL1
AH1
6
7
8
5
Max/min value record function activiation. Y:start, N:close
Optional 4types alarm.0:alarm close;L:low limit alarm;
H:high limit alarm;Int:interval alarm;
Out:outside the interval
0(N),1(Y)
FL~FH
FL~FH
0、L、H、
Int、Out
N
200
1000
AH2 FL~FH 1000
AH3 FL~FH 1000
L
1
600
H
AD3 Optional 4 types alarm,if it is 0,the alarm close 0、L 、H、Int、Out H
1
800
1
Unit
10
0
0
0~10V/K
0/-50
AL3
HY3
LDSP
FT
DREF
DP
INP
FL
FH
PS
26
28
27
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Max/min power failure protection.Y:open, N:Close
0~3
-1999~9999
0(N),1(Y)
0(N),1(Y)
1~10
FL~FH
FL~FH
-500~1000
0~1050
4.8K、9.6K、19.2K
1~255
0~11
0~11
0~11
0~999.9
0~999.9
0~999.9
o_SL
PSb
MEMO
SQRT
STEP
BRL
BRH
OLL
OLH
BAUD
ADDR
DTC
AE1
AE2
AE3
DL1A
DL1B
DL2A
0
0
N
N
1
FL
FH
0
1000
9.6K
1
0
0
0
0
0.0
0.0
0.0
44
0~999.9
DL2B 0.0
1.Operation of normal menu and shielding menu
Press SET key for 3s
SET
PRE
PRE
SET
PRE SET
PRE SET
PRE SET
PRE SET
PRE SET
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
PRE
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
PRE
SET
PRE
SET
PRE
SET
PRE
SET
PRE
PRE
PRE
PRE
SET
SET
PRE
SET
SET
SET
PRE
SET
SET
PRE
SET
PRE
SET
PRE
SET
Press SET key for 3s
Ⅶ.Operation and Menu Direction
PRE
SET
PRE
SET
PRE
SET
PRE
SET PRE
SET
PRE
SET
PRE SET
PRE SET
PRE SET
PRE SET
22
24
23
25
Displayed value of high-input point, setting corresponding
value of high-input point, press to decrease CAK
until CAK= OFF , this function is disabled.
Displayed value of low-input point, setting corresponding
value of low-input point, press to decrease CAS
until CAS= OFF , this function is disabled.
Password, LCK=01,unit lock; LCK=10,menu lock;
LCK=11, unit & menu lock; LCK=33, it can enter class 2
menu; LCK=5555, it will restore factory setting.
Small Signal Elimination,please refer description of o_SL for details
0~9999
-1999~9999
OFF
OFF
0
5
CAS
CAK
LCK
SCUT
No. Symbol Name Function
1
2
AL1
AL2
AL3
3
5
4
6
7
HOLD
PV
SV
MIN
MAX
1
6
27 3 54
LCK≠33
LCK=66
Press SET key for 3s
SET
LCK=33
PRE SET
Zero value,long press + key to clear the display value,
now,zero value will save on PSb. If you preset the zero value,
please long press + key or modify PSb to zero.
(The function is non-effective on temperature signal )
Alarm 1 indicator light
Alarm 2 indicator light
Alamr 3 indicator light
Light of max value
Light of min value
Light of hold value
SET key
Shift key
Add/hold key
Reduce/reverse key
Upper display window
Lower display window
1st loop alarm output indication,alarm output with light,no alarm output without light
3rd loop alarm output indication,alarm output with light,no alarm output without light
when the MAX value indicator light,PV display the max value
when the MIN value indicator light,PV display min value.
when HOLD value indicator light,PV display hold value.
Menu/ensure key,switch max/min/current value.
Parameters modify and activate,left shift
Increase the flashing value, hold measuring the instantaneous value
Reduce the flashing value,reverse to browse menu.
Display current/max/min value and parameter symbol,error indication
Display measure unit,parameter and alarm value
2nd loop alarm output indication,alarm output with light,no alarm output without light
No. Symbol Unit No. Symbol Unit No. Symbol Unit
1st alarm backlash value
1st alarm setting value
Scope of setting value for 1st alarm
2nd alarm backlash value
2nd alarm setting value
Scope of setting value for 2nd alarm
3rd alarm backlash value
3rd alarm setting value
Scope of setting value for 3rd alarm
Decimal location for linear signal
Input signal types
Measured low limit,the setting value must less than
measured high limit
Display refresh cycles,unit:s
Menu name Directions Setting range Factory default
Refer signal sheet page 3
Refer signal sheet page 3
Refer signal sheet page 3
Refer remarks(page 14)
Display of choice.o_SL=0, no function , o_SL=1, measured
value<FL, display FL; measured value>FH, display FH.
o_SL=2, measured value< SCUT/FL and display FL;
measured value>FH,display FH.
o_SL=3,measured
value<SCUT, display the min value between FL & SCUT;
measured value>FH, display FH.
linear signal Square root
Display jumping interval
Analog output low limit
Analog output high limit
Adjust analog output low limit
OLL=(preset analog low limit - actual analog low limit)/
actual analog range*1000
Adjust analog output high limit adjustment
OLH=(preset analog high limited - actual analog high limit)/
actual analog range *1000+1000
Communication baud rate
Meter communication address
Communication delay time
AL1 extensions
AL2 extensions
AL3 extensions
AL2 close delay(unit:s)
AL2 start delay(unit:s)
AL1 close delay(unit:s)
AL1 start delay(unit:s)
Measured high limit,the setting value must more than
measured low limit
Display translation correction value

8
10
8
(A10B)
(A10B)
11
SD4 SD6/8
SD7 SD9
1 2 3 4 5 6 7 8
0x01 0x03 0x32 0x01 0x00 0x01 0xDB 0x72
XI. Exclusive methods of simple fault
XII. Communication procotol
47
-1(Auto),0(Off),
1~50
CJC Auto
49
51
50
52
53
48
RLMR
TEST
CAL
CAE
CAH
VER
User set the low-limit input by themselves; after input
the low-limit signal, flash display YES, press “ ” to
confirm, when it display OK, the input signal low-limit
is set.
Software version
FL~FH
YES/OK
YES/OK
OFF
YES
YES
V1.0
45
46
0~999.9
0~999.9
DL3A
DL3B
0.0
0.0
1. High/low point display setting function
Example: use electronic ruler or others to measure distance, if want position 5mm display 500, position 6mm display 600, firstly
enter function shielding menu to set SF1= Y(open CAS, CAK parameter), then while the position is at 5mm, enter the menu to set
CAS=500; while the position is at 6mm, enter the menu to set CAS=600. After exit the menu, it will corresponding indicate 500~600
between 5mm and 6mm.
2. Linear signal self-calibration function
a)Set INP type, and make sure it is one of the linear signal.
b)The input signal should be applied to the correct input channel.
c)Enter low limit calibration menu CAL, press “ ” to flash “YES” ; after adjusting the input signal to the minimum value, then
input it to the meter.
d)When “YES” flashing, and the minimum value of input signal has been inputed into the meter; press “ ” to confirm and save
calibration value.
e)After the low limit is calibrated, enter high limit calibration menu CAH, and flash “YES” in the same way.
f)Adjust the input signal to the maximum value, and input it into the meter. And when “YES” flashing, press “ ” to confirm
and save calibration value of high limit.
g)After calibration, enter CAE to change “N” into “Y” to enable self-calibration; otherwise, it will use the default calibration value.
h)The calibrated high limit input value of linear signal should not fall outside the input standard range ±10%.
i)After the calibration, if the result is not satisfactory, it can be recalibrated.
3. Analog range calibration function
Example: actual high limit is 20.4mA, low limit is 3.97mA. To calibrate the analog range through the modification of OLL, OLH.
OLL= (Preset analog low limit - actual analog low limit)/ actual analog range*1000 =( 4.0 - 3.97)/(20.4 - 3.97) * 1000 = 2
OLH= (Preset analog high limit - actual analog high limit)/ actual ananlog range*1000+1000 = (20.0 - 20.4)/( 20.4 - 3.97) * 1000 +
1000 =976
Ⅷ. Alarm parameters and output logic diagram
Absolute value
low limit alarm
Interval alarm
HY
AL AH
AL AH
HY
HY
HY
AL
AL
HY
HY
Alarm extension function table
0
1
2
5
6
7
8
9
10
11
3
4
Alarm mode when show
over limit
AE1/AE2/AE3 value Whether restrain alarm when power on
4:(48*48)
6:(96*48)
7:(72*72)
8:(48*96)
9:(96*96)
80:(80*160)
16:(160*80)
ANo. H(Min)GB C D EF
J
48
96
72
48
96
80
160
48
48
72
96
96
160
80
97.5
97.5
97.5
97.5
97.5
96
96
6.5
9
9
9
9
13
13
91
88.5
88.5
88.5
88.5
83
83
45.5
45
67.5
92
92
155.5
76
25
25
25
25
25
30
30
45.5
92
67.5
45
92
76
155.5
45
89.5
67
44.5
91.5
75.5
155
K
(Min)
25
25
25
25
25
30
30
A
B
C
E
D
F
G
K
J+0.5
-0
+0.5
-0 H
1 2 3 4 5
0x01 0x83 0x02 0xC0 0xF1
1 2 3 4 5 6 7
0xC8 0xB9 0xD2
0x01 0x03 0x02
0x00
87654321
0x590xD70x640x000x010x320x060x01
87654321
0x590xD70x640x000x010x320x060x01
(A10B)
SD80
0~9999 0
N
0(N),1(Y)
OFF
OFF OFF
OFF
OFF
PV
PV
PV
PV
ON
ON
ON
ON ON
Alarm control fineness
AL3 start delay(unit:s)
AL3 close delay(unit:s)
Thermocouple cold end compensation method,
auto-compensation, close compensation, manual
compensation
linear resistance value, useable when linear resistance is
high (Unit: mΩ)
Analog input test, used to test output function
Enable user’ s self-calibration, this parameter is for
linear signal only; Y: use the parameter self-calibrated by
user; N: don`t use the parameter self-calibrated by user
User set the high-limit input by themselves; after input
the high-limit signal, flash display YES, press “ ” to
confirm, when it display OK, the input signal high-limit
is set.
Unable to set
Alarm code Type Logic diagram
Absolute value
high limit alarm
Deviation alarm
State invariant
Forced alarm output
Forced alarm close
Forced alarm output
Forced alarm close
Forced alarm output
Forced alarm close
Forced alarm output
Forced alarm close
State invariant
State invariant
State invariant
Do not inhibit
(As long as it meets the requirement of
alarm, alarm output)
Inhibit
(Forced alarm close when power on;alarm
does not output until the alarm condition
from noncoincidence to coincidence. )
Do not inhibit
(As long as it meets the requirement of
alarm, alarm output)
Inhibit
(Forced alarm close when power on;alarm
does not output until the alarm condition
from noncoincidence to coincidence. )
Alarm control with
display resolution
Alarm control with
highest resolution of
the meter
Ⅸ.Dimension
Panel Size Side Face Size Mounting Size
Ⅹ.Connection drawing
Note: If there is any change, please subject to the drawing on the meter
Display
HHHH/LLLL
Methods
Checks whether the input signal connects or not, whether the figure of FH/FL value is too small, whether
input signal is selected correctly, whether working environment is normal.
Meter adopt Modbus RTU communication protocol, RS485 half duplex communication.Read function code:0x03,
write function code 0x06 or 0x10. Adopts 16 digit CRC check, the meter does not return for error check.
Data frame format:
Start bit
Data bit
1 8 1No
Stop bit Check bit
Abnormal communication processing:
When abnormal response,put 1 on the highest bit of function code. For example: when host request function code is 0x03, slave
response function code should be 0x83.
Error code:
0x02---Illegal address: the register address designated by host beyond the address range of meter.
Communication cycle:
Communication cycle is the time from host request to slave response data . ie: communication cycle= time of request data sending
+slave preparation time + response delay time + response return time.
Eg: 9600 Baud rate: communication cycle of single measured data ≥ 250ms.
1 Read register(0x03)
For example: Host reads integer AL1(AL1=200)
The address code of AL1 is 0x3201, because AL1 is integer( 2 dyte), seizes 1 data register. The memory code of decimal integer
200 is 0x00C8.
Note:It should read DP value or confirm DP menu value first to ensure the decimal point postion when reading data,and converse
the reading data to get the actual value. On the contrary ,it should converse the data to corresponding ratio first before writing the
data into meter.
Host request(Read multi-register)
Function
code
Start ADD
High bit
Start ADD
Low bit
Data byte
length
high bit
CRC code
low bit
CRC code
high bit
Meter ADD
Data byte
length
low bit
Slave normarl answer(
Read multi-register
)
Data
low bit
Function
code
Meter ADD Data byte
number
Data
high bit
CRC code
low bit
CRC code
high bit
Address error abnormal answer: (For example, host request address is 0x2101)
Slave error answer
CRC code
low bit
CRC code
high bit
Meter ADD
Function code Error code
2 Write multi-register (0x06)
For example: Host writes AL1(First alarm set value 100)
The address code of AL1 is 0x3201, because AL1
is integer ( 2 dyte), seizes 1 data register. The hexadecimal memory code for decimal
integer 100 is
0x0064.
Host request(Write single-register)
CRC code
high big
CRC code
low bit
Meter ADD
Function
code
Data ADD
High bit
Data ADD
Low bit
Data
High bit
Data
Low bit
Slave normarl answer(
Write single-register
)
Meter ADD
Function
code
Data ADD
High bit
Data ADD
Low bit
Data
High bit
Data
Low bit
CRC code
low bit
CRC code
high big

10 corresponding to 1.0 second
10 corresponding to 1.0 second
12
14
13
15
1 2 3 4 5
0x01 0x86 0x02 0xC3 0xA1
Slave answer error code
0x01 0x10 0x32 0x01 0x00 0x01 0x02 0x00 0x64
0xB5 0xA9
※16 digit CRC check code to get C program
□ □ □
DTC:
unsigned int Get_CRC(uchar *pBuf, uchar num)
{
unsigned i,j;
unsigned int wCrc = 0xFFFF;
for(i=0; i<num; i++)
{
wCrc ^= (unsigned int)(pBuf[i]);
for(j=0; j<8; j++)
{
if(wCrc & 1){wCrc >>= 1; wCrc ^= 0xA001; }
else
wCrc >>= 1;
}
}
return wCrc;
}
D7 D6 D5 D4 D3 D2 D1 D0
AL3 AL2 AL1HHHH LLLL MIN HOLD MAX
1 2 3 4 5
0x01 0x90 0x02 0xCD 0xC1
87654721
1234567891011
0x000x010x320x100x01 0xB10x5E0x01
2
3
4
6
7
8
0x3001
0x3002
0x3003
0x30045
0x3100
0x3101
0x3102
2
2
2
10x3000
0x310392 R/W
R/W
R/W
R/W
30
32
31
33
34
35
36
0x3206
0x3207
0x3208
0x3209
0x320A
0x320B
0x320C
2
2
2
2
2
2
2
R/W
R/W
R/W
R/W
R/W
R/W
R/W
37
38
0x320D
0x320E
2 R/W
39
40
41 0x320F
20
21
22
23
24
25
26
27
28
29
0x310E
0x310F
0x3110
0x3111
0x3112
0x3113
0x3200
0x3201
0x3202
0x3203
0x3204
0x3205
2 R/W
2
2
2
2
2
2
2
2
2
2
R/W
R/W
R/W
R/W
R/W
R/W
2 R/W
R/W
R/W
R/W
R/W
10 0x3104 2 R/W
0x3105
0x3106
2 R/W11
0x3107
0x3108
0x3109
0x310A
0x310B
0x310C
0x310D
2
2
2
2
2
2
2
2
2
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
12
13
14
15
16
17
18
19
0~1000
2 R/W
配合 DP 值读数
42
43
44
45
46
47
48
49
0x3301
0x3211
0x3212
0x3213
0x3214
0x3302
0x3303
0x3304
0x3305
0x3306
0x3400
0x3401
2
2
2
2
2
2
2
2
R/W
R/W
R/W
R/W
R
R
R/W
R/W
-500~1000
0~1050
50
51
52
53
54
55
56
57
58
0x3402
0x3403
0x3404
0x3405
2
2
2
2
R/W 1~255
0:4.8K、1:9.6K、2:19.2KR/W
2 R/W
R
R
208: SD8
10 : V1.0
0x3210
2 R/W
2
2
R/W
R/W
2 R/W
Address error abnormal answer:( for example, host request address is 0x2101)
Error code CRC code
high big
CRC code
low bit
Meter ADD
Function
code
3、Write register(0x10)
For example: host writes AL1 (First alarm set value 100)
Host request(Write register)
Function
code
Start ADD
High bit
Start ADD
Low bit
Data byte
length
high bit
CRC code
low bit
CRC code
high bit
Meter
ADD
Data byte
length
low bit
Data byte
length
Data
high bit
Data
low bit
Slave normarl answer(
Write register
)
Function
code
Start ADD
High bit
Start ADD
Low bit
Data byte
length
high bit
Meter
ADD
Data byte
length
low bit
CRC code
low bit
CRC code
high bit
Data location error response:(For example:Host request write ADD index is 0x2100)
Slave answer error code
Meter ADD
Function
code
Error code
CRC code
low bit
CRC code
high bit
4、Address Mapping Table of Meter Parameters
No. ADD mapping Variable name Register
number Read/write Remark
MAX Maximum measure value
MIN Minimum measure value
HOLD Hold measured value
STA Output status word
PV Measure value
Note①(Page 15)
2
2
2
2
R
2 R
R
R
R
Collocate with DP value to read value
Collocate with DP value to read value
Collocate with DP value to read value
Collocate with DP value to read value
Reserve
FL Measuring range low limit
FH Measuring range high limit
INP Input signal type
DP Decimal point
Refer to measure signal parameter
table(Page 3)
Effective for all quantities-related
parameter
Collocate with DP value to read
value
Collocate with DP value to read
value
MME Maximum/minimum value
record function
MEMO Enable power failure memory
SQRT Enable linear signal square root
CJC Thermocouple cold end
compensation method
UNIT Unit setting
PS Translation correct
CAS limit point display value
setting
FT Filter constants
DREF Display refresh cycle
SCUT Small Signal Elimination
PSb Zero clearing value
oSL Display method option
LDSP Lower line display content option
STEP Display jumping interval
RLMR linear resistance value
CAK high point display value
setting
Refer to symbol table (Page 4)
Set the low input point
corresponding display value
1~255
Unit: second
Set the minimum step value of
display change
0:N;1:Y
0:N;1:Y
0:N;1:Y
Unit: mOhm
Non(0)、Unit(1)、AL1(2)、
AL2(3)、AL3(4)
-1: Auto compensation、0: No
compensation、(1~50) Manual
input cold end temperature
Collocate with DP value to
read value
Collocate with DP value to
read value
Collocate with DP value to
read value
Set the high input point
corresponding display value
Refer to menu illustration (Page 7)
Reserve
AD1 1st loop alarm type
HY1 1st loop alarm backlash value
AE1 1st loop alarm extended function
DL1A 1st loop alarm start delay
DL1B 1st loop alarm close delay
AL1 1st loop alarm value
AH1 1st alarm interval high limit value
AL2 2nd loop alarm value
AD2 2nd loop alarm type
HY2 2nd loop alarm backlash value
DL2A 2nd loop alarm start delay
DL2B 2nd loop alarm close delay
AL3 3rd loop alarm value
AD3 3rd loop alarm type
AH2 2nd alarm interval high limit value
AE2 2nd loop alarm extended function
FL~FH Collocate with DP value
to read value
FL~FH Collocate with DP value
to read value
0:no alarm、1:L、2:H、
3:Int、4:Out
Refer to alarm extention table
(Page 9)
10 corresponding to 1.0 second
10 corresponding to 1.0 second
0:no alarm、1:L、2:H、
3:Int、4:Out
FL~FH Collocate with DP value
to read value
FL~FH Collocate with DP value
to read value
0~1000 Collocate with DP value
to read value
Refer to alarm extention table
(Page 9)
0:no alarm、1:L、2:H
FL~FH Collocate with DP value
to read value
R:Read only;R/W:Read/Write
Note①:measurement status indication, when data byte is 1, it means execution; when data byte is 0, it means no execution.
Note②:DTC communication configuration byte illustration
Hundreds place, reserve
Tens place, byte transfer sequence: when it is 0, from high to low; when it is 1, from low to high
One place, respon delay: 0 ~9 respectively stand for 10 ~100ms
Reserve
Reserve
LCK Lock
ADDR Meter communication address
BAUD Baud rate
DTC Communication configuration
byte
NAME meter name
VER Software version code
When LCK=11, other parameter
can not be written
Note②(Page 15)
TESE Analog input test enable
TEST Analog input test
BRL analog output low limit
BRH analog ouptut high limit
OLL analog output low limit adjustment
OLH analog output low limit adjustment
FL~FH Collocate with DP value
to read value
10 corresponding to 1.0 second
10 corresponding to 1.0 second
0~1000 Collocate with DP value
to read value
Refer to alarm extention table
(Page 9)
FL~FH Collocate with DP value
to read value
FL~FH Collocate with DP value
to read value
0:close、1:open
Analog display input, test output
function
HY3 3rd loop alarm backlash value
DL3A 3rd loop alarm start delay
DL3B 3rd loop alarm close delay
AE3 3rd loop alarm extended function
AH3 3rd alarm interval high limit value
Other Toky Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Photon Systems Instruments
Photon Systems Instruments AquaPen-C AP 110-C Instruction guide

EXFO
EXFO IQS-1500 brochure

BW Technologies
BW Technologies BW Clip Operator's manual

Micran
Micran R42 Series Installation and quick start guide

Maxwell Digital Multimeters
Maxwell Digital Multimeters 25629 user manual

Charder
Charder HM201M user manual

Campbell
Campbell DataView II product manual

PCB Piezotronics
PCB Piezotronics 338C04 Installation and operating manual

Endress+Hauser
Endress+Hauser Liquicap M FTI51 operating instructions

Gira
Gira 2265 Series user manual

Ripley
Ripley Miller UPM100 user guide

PRECISION DIGITAL
PRECISION DIGITAL Helios PD2-6200 quick start guide