
6
2. Component names and functions (continued)
SHC
OS
0
0
0
000
12341234 1234 12
312 4
RST
COM
NONC65L2L1
Printed circuit
board
1. Error determinations
2. Special settings
3. Remote communication
4. Oil-back settings
Operation control
selection
Operational speed
selection
Cut-off pressure setting
Setting pressure
(low-pressure constant control)
Cut-in pressure setting
Cut-off pressure difference
(low-pressure constant control)
Pipe connection port (liquid)
Pipe connection port (gas)
Analog signal selection switch
This switch sets the type of analog signal.
Maximum operating speed setting switch
This switch sets the maximum operating speed for the
inverter.
Sets the operating speed for low-pressure differential
control and test operation mode.
Operating control setting switch
Sets the operating control method for the inverter.
(Set this switch before switching the power supply
ON. Cannot be switched during operation.)
Auxiliary control switch
Can set the number of retries until error determination,
special settings, external device communication, and
whether or not to use oil-back operation.
System setting switch
This switch sets the control system. This switch is pre-set upon leaving
the factory. Do not change the factory default.
Display setting switch
This switch can set and change LED display functions.
Cut-in pressure setting switch
This switch sets the cut-in pressure for low-pressure differential control.
When low-pressure constant control is used, this switch sets the
pressure difference with respect to the stopping pressure.
Operating pressure and cut-off pressure
setting switch
This switch sets the operating low-pressure value for low-pressure
constant control. Also sets the cut-off pressure when low-pressure
differential control is used.
Compressor delay duration reduction switch
This switch reduces the duration of the compressor restart delay by
causing a short. Should not be used during normal operation. (Use
only during checks, such as test operation)
Power supply terminals (L1, L2, L3, N)
Connect to a 380-415 V 3N~ (50 Hz) power supply.
Analog input terminals (7, 8)
Connect analog input signals (4 mA to 20 mA, 1 mA to 5 mA, 1 V to
5 V DC) if used for control.
Error reset terminals (9, 10)
These terminals can perform an error reset when shorted.
(may not always succeed in resetting, depending on the error type)
Remote operation / stop terminals (11, 12)
Start when shorted, stop when released. (can be used for emergency
stops, pump-out stops, and analog signal control stops)
Communication terminals (S1, S2, SG)
Connect a dedicated Toshiba controller, if used.
(Use a shielded wire of at least 0.3 mm2)
Solenoid valve power terminals (L, N)
Power supply (220-240 V AC) for a solenoid valve.
(Maximum capacity: 4 A or less)
Error output terminal (NC, NO, COM)
Used for no-voltage contact output during a condensing unit error.
(Maximum capacity: 220-240V AC, 4 A or less)
Defrost heater control terminals (5, 6)
Can provide a voltage-less connection if switched ON while the
compressor is stopped.
(Maximum capacity: 220-240 V AC, 4 A or less)
Display LEDs
Normally displays the discharge pressure (MPa) and intake pressure
(MPa).
Also displays error codes when errors occur.
Changing the display mode enables the operating frequency, various
operational data, and past error history to be displayed.
Controller selection switch
This switch is pre-set to the right-hand side upon leaving the factory.
Do not change the factory default.
*This model does not allow refrigerant selection setting.
Power switch
Can be switched OFF to force-stop the condensing unit.
*Note: The original power source is not interrupted. Exercise caution.
Operation switch
Can force-close the line solenoid valve via pump-down stop.
Grounding screw
Frontal cabinet removed