Town & Country Fireplaces TCVT.WSPVB User manual

OPTIONAL
VERTICAL OR
HORIZONTAL
POWER VENT KIT
TCVT.WSPVB
INSTALLATION AND
OPERATING
INSTRUCTIONS
190907-12 TCVT.WSPVB 5056.425211
5 x 8 Pipe
(Simpson Duravent)
(Secure Vent)
(Selkirk Direct-temp)
IMPORTANT:
THESE INSTRUCTIONS ARE TO REMAIN
WITH THE APPLIANCE INSTRUCTIONS
These instructions are supplementary to the Installation and
Operating Instructions supplied with the replace and should
be kept together. Refer to the Installation and Operating
Instructions for proper gas supply, safety requirements and
operating instructions
Power Vent Terminal
(TCVT.502461)
Vent Adaptor
(5096.814)

VENTING CONFIGURATIONS
Maximum vent length is 110 ft
plus six 90-degree elbows or
combination of other elbows
equaling 90-degrees, with a
maximum 66 foot vertical rise.
Minimum vent length is 4 ft
plus one 90-degree elbow.
The vent can be installed
with any combination of rise
and run between the gures
including up to 3 ft below
the unit. Ensure vent pipe is
Maximum venting -
110 ft plus six
90-degree elbows.
Vertical Application must use TCVT.PVVCA Box in
conjunction with this kit
4 ft min. 6 ft min.
Max. 66 ft
Min. venting - 4 ft plus
one 90-degree elbow
3 ft below unit (Max) to
centerline of vent pipe
Fig. #1
Max Pipe
Length
2 TCVT.WSPVB 190907-12
Contents of Power Vent Kit
Power Vent Installation
Locate the replace as per the main instructions supplied.
Make the following modications to add the components used with the Power Vent Kits. This Kit can only be used in
conjunction with the Town and Country WS replaces. This installation must conform with local codes or, in the absence
of local codes, with the Natural Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code,
CSA B149.1. This appliance must be electrically grounded in accordance with local codes or, in the absence of local
codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical code, CSA C22.1.
MINIMUM CLEARANCES TO
COMBUSTIBLE
Vertical vent pipe:
1.5 in. (38mm)
Horizontal vent pipe:
Top 1.5 in. (38mm)
Sides 1.5 in. (38mm)
Bottom 1.5 in. (38mm)
All other clearances are as
per the replace installation
instructions. Fig. #1a
ITEM PART No. DESCRIPTION QTY. ITEM PART No. DESCRIPTION QTY.
1 TCVT.502461 Power Vent Terminal 1 7 5004.085 Tubing, TYSC-516316-100 1
2 5096.814 Venting Adaptor 1 8 5093.01 Hose Clamp 2
3 TCVT.5062515 Blower Wiring (pre wired to motor) 1 9 TCVT.507156C Relay Wiring Harness, PVC 1
4 TCVT.506271C Pressure Switch Wiring 1 10 TCVT.507156 On / Off switch wiring 1
5 9072.7 Pressure Switch Clip 1 11 TCVT.506271 Pressure switch wiring 1
6 5027.1 Pressure Switch 1 12 5071.5 On / Off switch 1
WALL TERMINATION VENTING CHART
49” 0” 110 feet 4 feet
57” 12” 109 feet 3 feet
65” 24” 108 feet 2 foot
Min Pipe
Length
A B C
Pipe
Length
Min.
Rise

MK
I
A
V
G
G
H
A
J
VG
A
B
C
AV
V
A
V
B
F
B
L
V
E
VVV
D
190907-12 TCVT.WSPVB 3
Fig. # 2 VENT TERMINAL MINIMUM
CLEARANCES
A= clearances above grade, veranda, porch, deck, or balcony [*
12 inches (30 cm) minimum]
B= clearance to window or door that may be opened [* 12
inches (30 cm) minimum]
C= clearance to permanently closed window [minimum 12
inches (30 cm) recommended to prevent condensation on
window]
D= vertical clearance to ventilated soft located above the ter-
minal within a horizontal distance of 2 feet (60 cm) from the
edge of the terminal [12 inches (30 cm) minimum]
E= clearance to unventilated soft [12 inches (30 cm) minimum]
F= clearance to outside corner [6 inches (15 cm) minimum]
G= clearance to inside corner [6 inches (15 cm) minimum]
H= * not to be installed above a meter/regulator assembly within
3 feet (90 cm) horizontally from the center-line of the regula-
tor
I= clearance to service regulator vent outlet [* 6 feet (1.8 m)
minimum]
J= clearance to nonmechanical air supply inlet to building or
the combustion air inlet to any other appliance [* 12 inches
(30 cm) minimum]
K= clearance to a mechanical air supply inlet [* 6 feet (1.8 m)
minimum]
L= ^ clearance above paved side-walk or a paved driveway
located on public property [* 7 feet (2.1 m) minimum]
M= clearance under veranda, porch, deck, or balcony
[12 inches (30 cm) minimum**]
^ a vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and
serves both dwellings*
** only permitted if veranda, porch, deck, or balcony is fully open on a minimum of 2 sides beneath the oor*
* as specied in CGA B149 Installation Codes, Note: local Codes or Regulation may require different clearances
* for U.S.A. Installations follow the current National Fuel Gas Code, ANSI Z223.1
AIR SUPPLY INLET
VENT TERMINAL GAS METER
FIXED
CLOSED
FIXED
CLOSED
OPEN-
ABLE
OPEN-
ABLE
INSIDE
CORNER
DETAIL
AREA WHERE TERMINAL
IS NOT PERMITTED

4 TCVT.WSPVB 190907-12
1. Locate the power vent termination following the clearance
to combustible table, venting conguration diagram (Fig. #1 &
1a), and terminal location diagram (Fig. #2).
2. Cut and frame an 11” x 11” opening. The centre of
the square hole should line up with the centre line of the
horizontal pipe.
3. Install the Simpson Duravent (or equivalent) Wall thimble,
part number 1247 (not supplied with kit) in the opening
to retain any insulation in the wall and maintain proper
clearances. If the wall being penetrated is constructed of
noncombustible material only (i.e.. Masonry block or concrete)
the wall thimble is not required and a hole with zero clearance
is acceptable. (8” hole)
4. Attach the terminal to the outside wall. Ensure that the
terminal is the right way up and that only the outer anges that
are used to secure the terminal to the building are covered by
the exterior wall or siding. (Fig.#3) Note: No other part of the
terminal can be recessed into the exterior wall or siding.
5. Attach the vent adaptor directly to the appliance with three
screws and seal outer pipe with aluminium tape provided.
Note: The inner pipe does not need to be sealed.
(Fig. #4)
6. Connect the high temperature silicone tube to the vacuum
pressure taps on the adaptor, secure with the hose clamp
provided and route the tube through any hole back to control
box. (Fig. #4) Tube may touch unit and be trimmed if required.
Note: Ensure that there are no blockages in this tube, as
this will cause the control to malfunction.
7. Run the required Simpson Duravent GS / Secure Vent
/ Selkirk Direct-temp pipe from the adaptor to the terminal
assembly. Assemble as per the vent pipe manufacturer’s
instructions.
Horizontal (Side wall) Venting
This kit uses either Simpson Duravent GS direct vent pipe, Secure Vent direct vent pipe or Selkirk Direct-temp
vent pipe with a 5” inner pipe and an 8” outer pipe. For part numbers see the table of venting components on
page 8 of this manual.
Fig.#4
Fig.#3
Blower
Outlet
Finished
Wall
Power Vent
Terminal
UPPER
PRESSURE
TAP
Power Vent Adaptor. Part # 5096.814
MUST BE INSTALLED AT THE UNIT
Secure with three screws and seal
with foil tape
Seal not required
LOWER
PRESSURE
TAP

190907-12 TCVT.WSPVB 5
Vertical (Through Roof) Venting
This kit uses either Simpson Duravent GS direct vent pipe, Secure Vent direct vent pipe or Selkirk Direct-
temp vent pipe with a 5” inner pipe and an 8” outer pipe. For part numbers see the table of venting
components on page 8 of this manual.
Vertical installations must use the optional TCCV.PVVCA vertical adaptor box in conjunction with this kit. The vertical
adaptor box can only be installed on a at surface. Sloped surfaces require the construction of a chase which provides the
minimum interior, square opening of 11” x 11” for the venting and wiring to pass through. Flat roofs may require a chase
depending on local codes and roof construction. (If in doubt check with local inspector)
All part numbers in the following section are shown in Fig.
#5.
1. Place the ashing (Part A) onto the chase and seal
using silicone.
2. Put a bead of silicone on the underside of the vertical
standoff (Part B) and place it on top of the ashing. Align
the eight holes and secure both parts to the chase using
eight #8 x 1 1/2” screws provided.
3. Install the drip shield (Part C) onto the top of the vertical
standoff using a bead of silicone between the two. Do not
screw this part in place.
4. Bring the 14-2 electrical wire (not supplied) up through
the holes in both the ashing and the drip shield leaving at
least 12” of excess wire above the drip shield.
5. IMPORTANT: Attach an appropriate length(s) of the
vent to the power vent terminal, sufcient to pass through
the chase.
NOTE: DO NOT CONNECT AN ADJUSTABLE LENGTH
VENT PIPE TO THE TERMINAL.
6. Seal the connection of the rst length of pipe at the
terminal and any other pipe to pipe joint by both screwing
and taping the outside joint using high temperature foil
tape.
7. Remove the junction box cover. (Part D)
8. Remove and discard the exhaust shield. (Part E)
9. Apply a bead of silicone on the bottom ange of the
power vent terminal (TCVT.WSPVB)
10. Slide the vent through the drip shield and at the same
time thread the electrical lead through the hole in the
bottom of the terminal.
11. With the power vent terminal resting on the drip shield,
align the eight holes in each of the vertical standoff, the
drip shield and the power vent terminal and then screw
them together using the eight #8 x 1/2” stainless screws
provided.
12. Join the 14-2 wire lead to the blower wires using
the appropriate connectors and attach the ground wire.
Reinstall the junction box cover.
13. Install the vertical rain cap (Part F) over the power vent
blower. ALIGN THE EXHAUST OUTLET ON THE POWER
VENT TERMINAL WITH THE EXHAUST PORT ON THE
VERTICAL RAIN CAP.
14. Secure the vertical rain cap to the power vent blower
with the remaining eight #8 x 1/2” stainless screws.
NOTE:
THERE ARE NO PILOT HOES IN THE BASE OF THE
POWER VENT TERMINAL. 1/8” DIAMETER PILOT
HOLES SHOULD BE DRILLED USING THE HOLES IN
THE VERTICAL RAIN CAP AS A GUIDE.
DO NOT SILICONE THE VERTICAL RAIN CAP TO
THE POWER VENT TERMINAL AS IT NEEDS TO BE
REMOVABLE FOR SERVICING.
15. Attach the vent adaptor directly to the appliance with
three screws and seal outer pipe with aluminium tape
provided. Note: The inner pipe does not need to be
sealed.
(Fig. #4)
16. Connect the high temperature silicone tube to the
vacuum pressure taps on the adaptor, secure with the
hose clamp provided and route the tube through any hole
back to control box. (Fig. #4) Tube may touch unit and
be trimmed if required. Note: Ensure that there are no
blockages in this tube, as this will cause the control to
malfunction.
17. Run the required Simpson Duravent GS / Secure Vent
/ Selkirk Direct-temp pipe from the adaptor to the terminal
assembly. Assemble as per the vent pipe manufacturer’s
instructions.
Installation:

18.000 11.000 11.000 18.000
Part E
Exhaust Shield
- DISCARD -
Part D
Junction Box Cover
Power Vent
TCVT.PVB
Part F
Vertical Rain Cap
TCVT.8074
Part C
Drip Shield
Part B
Vertical Standoff
Part A
Flashing
Site Fabricated Chase
MUST ALIGN
#8 x 1/2" S.S.
(16 Required)
#8 x 1-1/2" S.S.
(8 REQUIRED)
NOTE: Holes to
secure rain cap are
not predrilled
SILICONE ALL
CONNECTING FACES
14-2 Wire w/ Ground
Final Installation Height: 21"
6 TCVT.WSPVB 190907-12
Fig. #5
Vertical (Through Roof) Venting

190907-12 TCVT.WSPVB 7
The gas control system is located on the right hand side of
the rebox behind an access panel and the decorative brick
panel.
1) Remove burner grate, logs and brick panels if already
installed.
2) Remove access panel from right hand side of the rebox.
(Fig. #10)
3) Locate and disconnect the spade connectors in the black
wire loop on the right side of the module and in the orange wire
running from the module to the socket on the valve labelled
“pilot”. (Fig. #11 and 12)
4) Using the wires provided, connect the 120V “hot” supply
wire to one of the black wires from the control module. Then
connect the “hot” wire from the power vent blower to the other
black wire on the control module. (Fig. #13)
ACCESS PANEL
Fig. #10
SPADE CONNECTORS IN BLACK
WIRE LOOP
Fig. #13
Fig. #11
SUPPLIED WIRES TO
CONNECT TO BLACK
WIRE ON MODULE
HOT WIRE
FROM BLOWER
HOT WIRE FROM
120V SUPPLY
ORANGE WIRE
FROM MODULE
TO VALVE
Fig. #12
Control System Connections

Fig. #16
8 TCVT.WSPVB 190907-12
Fig. #14
PRESSURE
SWITCH
ORANGE WIRE
5) Connect the pressure switch pig tails to
the orange wire. (Fig. #14)
6) Secure the pressure switch in the control
box using the bracket provided with this
kit. (Fig. #14)
NOTE: Only use the screw provided
to secure the bracket to the valve. The
use of a sheet metal screw will damage
the valve.
7) Attach the silicone tube from the
upper pressure tapping to the low side
of the pressure switch and secure using
the hose clamp provided. (Fig. #15)
8) Attach the silicone tube from the lower
pressure tapping to the high side of the
pressure switch and secure using the hose
clamp provided. (Fig. #16)
9) Continue with installation and reassemble
all of the parts previously removed. Fig. #15
HIGH SIDE OF
SWITCH
LOW SIDE OF
SWITCH
LOW SIDE OF
SWITCH

White
Green
Orange
Black
Red
Black
AF-4000
Module
Wall Switch Receiver
SWI (+) (-)
Pressure Switch
Power Vent Fan
120 Volt Power
120 Volt Power
AC Adaptor
1/4” Male
Connector
1/4” Male
Connector
1/4” Female
Connector
1/4” Female
Connector
Optional Power Vent Kit provided by Town & Country
Communication Wires
1/4” Female
Connector
1/4” Male
Connector
120 Volt Common wire (White)
120 Volt Hot wire (Black)
Low volt relay
Inside the module
1/4” Female
Connector
1/4” Male
Connector
Pull connectors apart
to connect to optional
p
ower vent
190907-12 TCVT.WSPVB 9
Wiring Diagram
115V 60 Hz
1.8A

10 TCVT.WSPVB 190907-12
REPLACEMENT PARTS
ITEM PART NUMBER DESCRIPTION QTY ITEM PART NUMBER DESCRIPTION QTY
1 5004.085 TUBE, 5/16” OD, 1/16” THICK 1 20 INSIDE COVER 1
2 BLOWER POWER VENT 1 21 EXHAUST SHIELD 1
3 5027.1 PRESSURE SWITCH 1 22 SECONDARY RAIN SHIELD 2
*4 3/8” STRAIN RELIEF 2 23 JUNCTION BOX 1
5 #8 x 1/2” PAN HD SKT 18.8 STAINLESS STEEL 46 24 TOP COVER 1
6 ID x .379 OD x .062 THK 2 25 EXHAUST SCREEN 1
7 1/4 MED LOCKWASHER 18.8 SS 5 26 FLASHING 1
8 STANDARD 18-8 SS, #8 FLAT WASHER 6 27 OUTLET AIR CHANNEL 1
9 SP100 .25 x .75 AK 4 28 DRIP SHIELD 1
10 SCREW, #8-32 x1 1/4 RND HD 4 29 9072.7 PRESSURE SWITCH CLIP 1
*11 #8-32 x5/16 PAN QUADREX 1 30 VENT COLLAR 1
12 HEX NUT, STAINLESS 18-8 PLAIN 4 31 VENT EXHAUST ASSEMBLY 1
13 1/4-20 x1/2 NC GR 5 HEX C/S PLTD 5 32 VERTICAL RAIN CAP, TCVT 1
14 5096.814 VENTING ADAPTER 1 33 VERTICAL STANDOFF 1
15 1/4” LDF PAPER 1 34 TCVT.5062512 BLOWER WIRING 1
16 35 TCVT.506271C PRESSURE SWITCH WIRING 1
*17 BUSHING, SHORTY B625 500 2 36 TCVT.507156C RELAY WIRING 1
18 SIDE COVER, RIGHT 1 *37 TCVT.506271 PRESSURE SWITCH WIRING 1
19 SIDE COVER, LEFT 1 *38 TCVT.507156 ON/ OFF SWITCH WIRING 1
* NOT SHOWN
ITEM 35 AND 36 ARE USED WITH SERIES “C” FIREPLACES ONLY
ITEMS NOT SOLD SEPARATELY ITEMS 37 AMD 38 ARE UED ON SERIES “B” FIREPLACES ONLY
Table of contents
Popular Heater manuals by other brands

oventrop
oventrop Regucor Series quick start guide

Blaze King
Blaze King CLARITY CL2118.IPI.1 Operation & installation manual

ELMEKO
ELMEKO ML 150 Installation and operating manual

BN Thermic
BN Thermic 830T instructions

KING
KING K Series Installation, operation & maintenance instructions

Empire Comfort Systems
Empire Comfort Systems RH-50-5 Installation instructions and owner's manual

Well Straler
Well Straler RC-16B user guide

EUROM
EUROM 333299 instruction manual

Heylo
Heylo K 170 operating instructions

Eterna
Eterna TR70W installation instructions

Clarke
Clarke GRH15 Operation & maintenance instructions

Empire Heating Systems
Empire Heating Systems WCC65 Installation and owner's instructions





