  9. Trace Engineering T240 - REV B User manual

Trace Engineering T240 - REV B User manual

Installation and Operation Guide
T240
Autotransformer
ã2000 Trace Engineering P/N 975-0002-01-02 Rev. B 04/00
©2000 Trace Engineering
©2000 Trace Engineering i
T240 Autotransformer
Table of Contents
Section Description Page
1. INTRODUCTION ..................................................................... 1
The T240 Autotransformer .................................................. 1
2. INSTALLATION ....................................................................... 2
Installation ........................................................................... 2
Required Tools ................................................................ 2
Mounting ......................................................................... 2
Wiring .................................................................................. 4
ervice Crimps ................................................................ 4
Connection Points ........................................................... 5
tep-up Configuration ..................................................... 8
Deep Well Pump Wiring .................................................. 9
tep-Down Configuration .............................................. 10
tep-Down Connection of tacked-pair Inverters ......... 11
Generator Output Balancing Autotransformer .............. 12
ingle 120 volt AC Load ........................................... 12
Dual 120 volt AC Loads ............................................ 13
Optional Circuit Breakers .............................................. 16
Wiring Check ................................................................. 17
3. OPERATION ......................................................................... 18
4. SERVICE INFORMATION .................................................... 19
5. SPECIFICATIONS ................................................................ 20
6. WARRANTY ..........................................................................21
©2000 Trace Engineering
IMPORTANT SAFETY INSTRUCTIONS
This manual contains important safety instructions that should be followed
during the installation and maintenance of this product.
To reduce the risk of electrical shock, and to ensure the safe installation and
operation of this product, the following safety symbols have been placed
throughout this manual to indicate dangerous conditions and important safety
instructions.
WARNING - A dangerous voltage or condition exists in this area.
Use extreme caution when performing these tasks.
AVERTISSEMENT - Une tension ou condition dangereuse existe dans cette
zone.
Faire preuve dextrême prudence lors de la réalisation de ces tâches.
CAUTION - This procedure is critical to the safe installation or operation of
the unit. Follow these instructions closely.
ATTENTION - Cette procédure est essentielle à linstallation ou lutilisation
de lunité en toute sécurité. uivre ces instructions de près.
NOTE - This statement is important. Follow instructions closely.
NOTE - Cette déclaration est importante. uivre les instructions de près.
 All electrical work must be done in accordance with local, national,
and/or international electrical codes.
 Before installing or using this device, read all instructions and cautionary
markings located in the T240 and the manual.
 Do not expose this unit to rain, snow or liquids of any type. This product is
designed only for indoor mounting.
 To reduce the chance of short-circuits when installing or working with this
product, use insulated tools.
 Remove all jewelry such as rings, bracelets, necklaces, etc., while installing
this system. This will greatly reduce the chance of accidental exposure to
live circuits.
ii
©2000 Trace Engineering
SAVE THESE INSTRUCTIONS
iii
 This product contains no user-serviceable parts. Do not attempt to repair
this unit.
 Do not mount this device in unventilated enclosures or in an engine
compartment.
 Protect the device from splashing when used in vehicular applications.
 To reduce risk of electric shock, disconnect all wiring before attempting any
maintenance or cleaning.
 Additional AC disconnects may be required as part of the system installa-
tion. Consult local and national electrical code requirements.
 Over-current Protection, provided by a 25 amp circuit breaker, protects the
AC input/output wiring. This circuit breaker is branch circuit rated and has a
10,000 AIC rating, suitable for residential and commercial applications.
 This unit is designed to be horizontally wall mounted.
 The AC input and output neutral conductors are not connected (bonded) to
the chassis.
 The AC input and output HOT conductor are not isolated from each other.
 The chassis housing of the T240 must be connected to a permanent
grounding system as required by the National Electric Code, AN I/NFPA 70-
1996. This is the responsibility of the system installer. A grounding terminal
strip is provided for connection of equipment grounding conductors.
 UL rated as an indoor enclosure.
 UL listed for sale in the U. . and Canada under Photovoltaic Power ystem
Accessaries (UL1741) and Canadian standard for general use power
supplies (C A C22.2 No. 107.1-95).
©2000 Trace Engineering
iv
Disclaimer of Liability
ince the use of this manual and the conditions or methods of installation,
operation, use and maintenance of the unit are beyond the control of Trace
Engineering, the Company does not assume responsibility and expressly
disclaims liability for loss, damage, or expense arising out of or any way
connected with such installation, operation, use, or maintenance.
©2000 Trace Engineering
1.0 INTRODUCTION
The T240 Autotransformer is designed to step-up 120 volt AC to 240 volt AC
or to step-down 240 volt AC into two 120 volt AC circuits. The T240 contains
two identical windings that can be used to step-up, step-down, or balance the
output voltage of an AC power source (such as an inverter, generator or
conventional AC source) to an AC load. The unit is sized to take advantage of
Trace Engineerings inverter/charger line. The exceptionally high efficiency of
the T240 Autotransformer makes it ideal for voltage conversion from an inverter,
generator or conventional AC source.
The T240 Autotransformer utilizes a highly-efficiency transformer constructed
of high temperature materials and M-6 grade steel laminations, meeting UL
Class-H standards.
The unit is housed in a powder coated, steel enclosure, suitable for indoor
installations and contains knockouts for 3/4 inch and 1 inch conduit connections
and additional breakers. One 25 amp dual breaker is supplied with the T240.
Up to six additional quare D QOU breakers can be added for additional input/
output wiring protection and control.
Figure 1
T240 Autotransformer
1
©2000 Trace Engineering
Installation
Required Tools
 Wire strippers
 Phillips screw driver
 lotted screw driver
 Torque wrench
Mounting
Place the T240 Autotransformer in a convenient location, close to the input
source (inverter, generator or utility). The T240 must be mounted horizontally
on a flat surface (such as a wall) in a clean, dry environment. Do not mount the
autotransformer where it will be exposed to the weather or in a wet location.
NOTE: The T240 weighs approximately 50 pounds. Use appropriate wall
anchors or backing material (plywood, 2 x 4s, etc.) that will support its weight.
Procedure:
 Use a level and mark the location for mounting the unit on the wall.
 Measure out the four mounting screw holes according to Figure 3.
 Drill out the mounting holes using a #18 (0.170 inch) drill bit.
 Remove the front cover of the autotransformer by removing the four
Phillips screws. Do not lose the screws!
 Use a #10 x 3/8 (or 1/2) inch long screw and washer (and appropriate
anchors if necessary) and mount the autotransformer securely to the wall
or backing material (plywood, 2 x 4s, etc.).
 Remove the appropriate knockouts for the conduit. Install the conduit
between the autotransformer and input source (inverter, generator, etc.)
and output to load. Use separate conduit for input and output wiring.
Figure 2
Mounting Holes
2.0 INSTALLATION
2
Mounting Hole
©2000 Trace Engineering
2.0 INSTALLATION
3
Figure 3
Installation Drawing






































©2000 Trace Engineering
iring
WARNING: WIRING SHOULD BE PERFORMED ONLY BY QUALIFIED
PERSONS.
WARNING: BEFORE WIRING THE AUTOTRANSFORMER, ENSURE THAT
ALL SOURCES OF POWER ARE DISCONNECTED. NEVER WORK ON A
LIVE CIRCUIT.
CAUTION: THE CONFIGURATION OF THE AUTOTRANSFORMER IS FOR
STEP-UP, STEP-DOWN OR CURRENT BALANCING. IT DOES NOT
PROVIDE ISOLATION BETWEEN INPUT AND OUTPUT. DO NOT USE THE
AUTOTRANSFORMER AS AN ISOLATION DEVICE.
NOTE: All source connections (inverter, generator or utility) are connected to
the left-hand side of the installed circuit breaker (see illustrations). All loads
connect to the service crimp on the right-hand side of the breaker.
Service Crimps
The service crimps provide a convenient means to connect the
autotransformer. Do not use the screw terminals on the breakers for making
connections. Do not remove factory wiring.
 Pull back the insulation on the TRAN FORMER wire so it is exposed
inside the service crimp.
 trip off approximately 1/2 inch of the insulation from the wire to be
installed and insert the bare wire into the crimp.
 lide the crimp up to the circuit breaker terminal as far as it will go.
 Place the wire in the crimp and ensure the existing wires insulation is fully
exposed. Torque the crimp screw to 45 inch/pounds.
 After torquing, ensure the service crimp is tight on both wires and is not
able to twist or be moved.
CAUTION: UNUSED SERVICE CRIMPS SHOULD BE TIGHTENED TO THE
EXISTING WIRE AND TAPED, SO IT CAN NOT SHORT TO OTHER
TERMINALS OR THE CASE.
2.0 INSTALLATION
4
Breaker Lug Service Crimp
Existing Factory Wiring
Added
LOAD
Wire
975-C00-004
Figure 4
Installation Drawing
©2000 Trace Engineering
2.0 INSTALLATION
5
Connection Points
The connection points for input/output wiring is as follows:
 All 240 volt AC (input or output) wires connect to the left-hand side of the
breaker, points A and C (Figures 6 and 7).
 All 120 volt AC wires connect to the service crimps located on the breaker,
points B and D (Figures 6 and 7).
 All neutral wires connect to the NEUTRAL block in the T240.
 All ground wires connect to the GROUND block in the T240.
 The ganged circuit breaker used in the T240 opens both circuit breakers if
either one receives a current draw in excess of its rating (i.e., 25 amps).
Any exceptions are noted in the procedure.
NOTE: Due to continued product improvement, parts availability, etc.,
photographs used in this manual may vary slightly from actual current
production models.
Figure 5
Step-up Configuration Connections
240 Volt AC
Input/Output
120 Volt AC Input/Output
ervice crimp
GROUND block NEUTRAL block
Factory Wiring  DO NOT
REMOVE OR ADD WIRES
TO THESE TERMINALS!
©2000 Trace Engineering
Connection Identification Points (continued)
Figures 6 and 8 identify the wiring points in the T240 Autotransformer:
AOnly 240 volt AC (L1) input/output connections are made on this
circuit breaker terminal.
BThis is the service crimp on the lower ganged breaker. Only 120
volt AC input/output wires connect to this service crimp.
COnly 240 volt AC (L2) input/output connections are made on this
circuit breaker terminal.
DThis is the service crimp on the upper ganged breaker. Only
120 volt AC input/output wires connect to this service crimp.
GROUND This is the ground block contained in the T240. All ground wires
connect to this block for both source and load.
NEUTRAL This is the neutral block contained in the T240. All neutral wires
connect to this block for both source and load (except as noted in
the procedures).
Figure 6
Connection Point Identification
GROUND
NEUTRAL
A
CD
B
2.0 INSTALLATION
6
©2000 Trace Engineering
NEUTRAL
L2
L1
975-S00-002A
GROUND
AB
CD
Service Crimp
Service Crimp
Ground Block
Neutral Block
Lower Breaker
Upper Breaker
Figure 7
Connection Point Identification Schematic
2.0 INSTALLATION
7
©2000 Trace Engineering
2.0 INSTALLATION
8
Step-up Configuration
This configuration allows for a 240 volt AC load to be supplied from a
120 volt AC input source. The voltage output of the autotransformer doubles
(from 120 to 240 volts AC) and the total output current available is one half.
Procedure
The wire terminals accept wire sizes from #14 AWG to #2 AWG. Use the
proper size wire for the load connected.
120 Volt AC Input (source)
NOTE: Refer to the previous instructions on connecting wires to the service
crimp.
 Connect the 120 volt AC HOT wire (from an inverter, generator or
utility) to service crimp (point B) of the breaker as shown in Figure 8.
 Connect the neutral wire (from an inverter, generator or utility) to the
NEUTRAL block in the autotransformer.
 Connect the ground wire (from an inverter, generator or utility) to the
GROUND block in the autotransformer.
240 Volt AC Outputs (load)
 Connect a black wire from the L1 connection on the breaker (point A),
to the loads L1 connection.
 Connect a red wire from the L2 connection on the breaker (point C),
to the loads L2 connection.
 Connect a white wire from the NEUTRAL block in the autotransformer
to the loads neutral connection.
 Connect a green wire from the GROUND block in the autotransformer
to the loads ground connection.
Figure 8
Step-up Configuration Schematic
NEUTRAL
L2
L1
975-S00-003
120 VAC
Source
Ground
240 VAC
Load
L2
OUT
L1
OUT
N
G
Service
Crimp
Service Crimp
HOT
AB
N
G
N
G
D
C
N
G
©2000 Trace Engineering
2.0 INSTALLATION
9
Figure 9
Control Switch Wiring for Deep Well Pump
Deep Well Pump Wiring
This wiring configuration allows the control switch for the pump to be
connected between the 120 volt AC source and the HOT input of the T240. In
this arrangement, there is no transformer idle power consumption when the
switch is open and the pump is not running. The control switch can be either a
float, pressure or manual type.
Procedure
120 Volt AC Inputs (source)
NOTE: Refer to the previous instructions for connecting wires to the service
crimp on page 4 and Figure 4.
 Connect the pumps control or pressure switch to the service crimp
(point B) on the lower breaker.
 Connect the 120 volt AC HOT wire (from an inverter, generator, or
utility) to the free end of the control switch.
 Connect the neutral wire (from an inverter, generator or utility) to the
NEUTRAL block in the autotransformer.
 Connect the ground wire (from an inverter, generator or utility) to the
GROUND block in the autotransformer.
240 Volt AC Outputs (load)
 Connect a black wire from the L1 connection on the breaker (point A),
to the pumps L1 connection.
 Connect a red wire from the L2 connection on the breaker (point C),
to the pumps L2 connection.
 Connect a white wire from the NEUTRAL block in the autotransformer
to the pumps neutral connection.
 Connect a green wire from the GROUND block in the autotransformer
to the pumps ground connection.
NEUTRAL
L2
L1
975-S00-005
120 VAC
Source
240 VAC
Deep
Well
Pump
L2
OUT
L1
OUT
N
G
Service
Crimp
Service
Crimp
Ground
Control Switch
D
B
A
N
N
G
G
C
L1
L2
N
HOT
©2000 Trace Engineering
2.0 INSTALLATION
10
240 Volt AC Source120 Volt AC to Loads (Step-down Configuration)
This configuration allows a 120 volt AC load to be supplied from a
120/240 volt AC input source such as a utility grid. The voltage output of the
autotransformer halves (from 240 to 120 volts AC) and the total output current
available for the 120 volt AC output doubles. This arrangement is useful for
splitting the current of a battery charger between each leg of the 240 volt AC
source, reducing losses in the wiring. This is especially important in long cable
runs or when charging from a 120/240 volt AC output generator.
240 Volt AC Input (source)
 Connect the L1 AC HOT wire (from the utility grid) to point A on the
lower breaker as shown in Figure 10.
 Connect the L2 AC HOT wire (from the utility grid) to point C on the
upper breaker as shown in Figure 10.
 Connect the neutral wire (from the utility grid) to the NEUTRAL block
in the autotransformer.
 Connect the ground wire (from the utility) to the GROUND block in the
autotransformer.
120 Volt AC Output (load)
 Connect a black wire from the service crimp (point B), to the loads
HOT connection.
NOTE: Refer to the previous instructions located on page 4 and Figure 4 for
connecting wires to the service crimp.
 Connect a white wire from the NEUTRAL block in the autotransformer
to the loads neutral connection.
 Connect a green wire from the GROUND block in the autotransformer
to the loads ground connection.
Figure 10
Step-down Configuration Schematic
NEUTRAL
L2
L1
975-S00-006
120 VAC
LOAD
(inverter/
charger)
L2
L1
N*
Service
Crimp
Service
Crimp
Ground
G
N
120 VAC HOT
OUTPUT TO LOAD
G
120/240 VAC
Source
(grid)
D
B
N*
N
A
GG
C
*NOTE: For 240 VAC only source
installations, the neutral wire is not
required.
©2000 Trace Engineering
2.0 INSTALLATION
11
Figure 11
Step-down Configuration Schematic (Dual Inverters)
Step-down Connection of Stacked-pair Inverters
The T240 can also be used to step down the voltage from a stacked pair of
DR or W eries inverters. In this configuration, the neutral of the inverters
must be isolated from the neutral block of the T240 Autotransformer, or the
inverters may over-current trip when they synchronize to an AC generator. This
configuration may not be in compliance with the NEC. Consult your local and
national electrical codes for requirements. This configuration provides double
the output current at 120 volts AC.
Procedure
Inverter Inputs to T240
 Connect the HOT output of Inverter #1 to point A on the lower
breaker.
 Connect the HOT output of Inverter #2 to point C on the upper
breaker.
 Connect the ground wire from the inverters to the GROUND block in
the T240.
T240 Output to 120 Volt AC Load
 Connect the ground wire from the load to the GROUND block in the
T240.
 Connect the neutral wire from the load to the NEUTRAL block in the
T240.
 Connect the HOT wire (120 volt AC) from the load to the service
crimp on lower breaker (point B).
 Connect the inverters as specified in the inverters operation manual
for stacked (120/240 volt AC) operation.
NEUTRAL
L2
L1
975-S00-007A
120 VAC
LOAD
(high
current)
HOT
N
Service
Crimp
Service
Crimp
G
N
120 VAC HOT
OUTPUT TO LOAD
G
HOT
Out
Neutral
Ground
I
nverter #2
120 V ac Output
HOT
Out
Neutral
Ground
I
nverter #1
120 V ac Output
Ground
240 VAC
L2
L1
G
N
HOT
240 VAC
Generator
HOT
In
HOT
In
N
G
L1
L2
D
C
N
B
A
G
G
©2000 Trace Engineering
2.0 INSTALLATION
12
Generator Output Balancing Autotransformer
Single 120 Volt AC Load
This configuration allows the 120/240 volt AC generator output to be
equally divided (balanced) between its L1 and L2 outputs. In this example, the
generator is using both its L1 and L2 outputs to supply a high current 120 volt
AC load. Balancing the generator in this way improves generator performance
and life, plus results in higher battery charge rates.
Procedure
 Connect the L1 output of the generator to the lower breaker (point A).
 Connect the L2 output of the generator to the upper breaker (point C).
 Connect the ground wire from the generator to the T240 GROUND block.
 Connect the neutral wire from the generator to the T240 NEUTRAL block.
 Connect the inverters 120 volt AC input to the service crimp on the lower
breaker (point B).
 Connect a ground wire from the inverter to the GROUND block in the
T240.
 Connect a neutral wire from the inverter to the NEUTRAL block in the
T240 .
 Follow the instructions for wiring the inverter to the loads as specified in
the inverters operation manual.
©2000 Trace Engineering 13
Figure 12
Generator Output Balancing (single 120 volt AC load)
2.0 INSTALLATION
NOTE: The ability of the T240 to balance the load depends upon the generators
windings and voltage regulation it receives on each leg. If the voltages are not
equal, or if there are other loads on the legs, then the currents in each leg will not
be equal.
To absolutely equal the load, disconnect the neutral connection of the T240 to the
generator. This un-bonds the output neutral from ground. This neutral should be
considered as a HOT wire and treated as such. This configuration may not be
compliant with the NEC, but will balance the load on the 240 volt AC side.
NEUTRAL
L2
L1
975-S00-008
Service
Crimp
Service
Crimp
120/240 VAC
Generator
N
G
L1
L2
Ground
Inverter/Charger
HOT In
Ground
Neutral In
HOT Out
Neutral Out
120 VAC Loads
HOT
Neutral
Ground
D
C
B
A
N
N
G
G
©2000 Trace Engineering
14
Generator Output Balancing Autotransformer
Dual 120 Volt AC Loads
This configuration allows the 120/240 volt AC generator output to be
equally divided (balanced) between its L1 and L2 outputs. In this case, the
generator is using both its L1 and L2 outputs to supply two separate 120 volt
AC loads. If one leg of the generator is pulling a heavier load than the other,
both legs equally divide the current, thereby balancing the generators output.
Procedure
240 Volt AC Inputs From the Generator
 Connect the L1 (HOT) output of the generator to the terminal on the
lower breaker (point A).
 Connect the L2 (HOT) output of the generator to the terminal on the
upper breaker (point C).
 Connect the ground wire from the generator to the GROUND block in
the T240.
 Connect the neutral wire from the generator to the NEUTRAL block in
the T240.
120 Volt AC Outputs to Inverters or Loads
 Connect the 120 volt AC input wire for Inverter #1 to the service crimp
(point B) on the lower inverter.
 Connect the ground wire from the inverter #1 to the GROUND block
in the T240.
 Connect the neutral wire from Inverter #1 to the NEUTRAL block in
the T240.
 Connect the 120 volt AC input wire for Inverter #2 to the service crimp
(point D) on the upper inverter.
 Connect the ground wire from the inverter #2 to the GROUND block
in the T240.
 Connect the neutral wire from Inverter #1 to the NEUTRAL block in
the T240.
 Connect the inverters outputs as specified in the inverters operation
manual.
2.0 INSTALLATION

This manual suits for next models

1

Popular Transformer manuals by other brands

Monacor CARPOWER FGA-40 operating instructions

Monacor

Monacor CARPOWER FGA-40 operating instructions

Inovonics EN5040 Installation and operation manual

Inovonics

Inovonics EN5040 Installation and operation manual

Daystrom Heathkit IP-22 Assembly manual

Daystrom

Daystrom Heathkit IP-22 Assembly manual

Shure A15BT user guide

Shure

Shure A15BT user guide

Haws VRKHO7 Installation, operation & maintenance instructions

Haws

Haws VRKHO7 Installation, operation & maintenance instructions

Monacor FGA-22 manual

Monacor

Monacor FGA-22 manual

BRAHMA TSM manual

BRAHMA

BRAHMA TSM manual

DV Power TRT30C manual

DV Power

DV Power TRT30C manual

AB Quality Allen-Bradley 1609-5000CCT user manual

AB Quality

AB Quality Allen-Bradley 1609-5000CCT user manual

Audio Note AN-S3 Owner's Information

Audio Note

Audio Note AN-S3 Owner's Information

ELEQ TQ105 installation guide

ELEQ

ELEQ TQ105 installation guide

Toa MT-200 operating instructions

Toa

Toa MT-200 operating instructions

Griven AL3350 instruction manual

Griven

Griven AL3350 instruction manual

Arteche CA user manual

Arteche

Arteche CA user manual

France P5G-2UE Series installation guide

France

France P5G-2UE Series installation guide

Graco 248113 instructions

Graco

Graco 248113 instructions

Jung Tronic SNT 150 operating instructions

Jung

Jung Tronic SNT 150 operating instructions

L&S 50,583.50 manual

L&S

L&S 50,583.50 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.