Trane Technologies Tracer TD7 User manual

CG-SVU010C-GB
Tracer™ TD7 with UC 800
for CGAF / CXAF chillers and heat pumps
July 2020
Confidential and proprietary Trane information
Original instructions

Table of Contents
CG-SVU010C-GB
2
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m3/h) 490 980 1400 1800 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Copyright............................................................................................................ 3
Trademarks ............................................................................................... 3
General Recommendations .............................................................................. 4
Installer-Supplied Components / Interconnecting Wiring.............................. 6
Installer-Supplied Components............................................................... 6
Interconnecting Wiring ............................................................................ 6
Programmable Relays....................................................................................... 8
Relay Assignments Using Tracer™ TU............................................................ 9
Low Voltage Wiring / Ice Making (Optional).................................................. 10
Low Voltage Wiring ............................................................................... 10
Ice Making (Optional)............................................................................. 10
External setpoints & capacity outputs (Optional) ......................................... 12
External Chilled/Hot Water Setpoint (ECHWS) .................................... 12
External Demand Limit Setpoint (EDLS) .............................................. 13
ECHWS and EDLS Analog Input Signal Wiring Details....................... 14
Chilled Water Reset (CWR) ............................................................................. 15
Functional Description ........................................................................... 15
Diagnostic ............................................................................................... 18
Hot Water Reset............................................................................................... 19
Hot Water Reset (HWR) - CXAF only..................................................... 19
Smart Communication Protocol..................................................................... 21
LonTalk™ Interface (LCI-C) .................................................................... 21
BACnet Interface (BCNT)........................................................................21
BACnet Testing Laboratory (BTL) Certification.................................... 21
ModBus RTU Interface........................................................................... 21
Wiring and Port Descriptions for MODBUS, BACnet and LonTalk.............. 22
Smart Com protocol............................................................................... 22
Rotary Switches...................................................................................... 22
LED Description and Operation............................................................. 23
Tracer TD7 Operator Interface........................................................................ 24
Tracer™ TU ...................................................................................................... 25
Notes................................................................................................................. 27

3
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVU010C-GB
Copyright
All rights reserved
This document and the information in it are the property of Trane and may not be used or reproduced in whole or in
part, without the written permission of Trane.
Trane reserves the right to revise this publication at any time and to make changes to its content without obligation
to notify any person of such revision or change.
Trademarks
TD7, the Trane logo, and Tracer are trademarks of Trane. All trademarks referenced in this document are the
trademarks of their respective owners.

4
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m3/h) 490 980 1400 1800 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
CG-SVU010C-GB
General Recommendations
As you review this manual, keep in mind that:
• All field-installed wiring must conform to European guidelines and any applicable local codes. Be sure to satisfy
proper equipment grounding requirements per European guidelines.
• Compressor motor and unit electrical data (including motor kW, voltage utilization range, rated load amps) is listed
on the chiller nameplate.
• All field-installed wiring must be checked for proper terminations, and for possible shorts or grounds.
Note:
Always refer to wiring diagrams shipped with chiller or unit submittal for specific electrical schematic and connection
information.
WARNING:
Proper field wiring and grounding required!
All field wiring MUST be performed by qualified personnel.
Improperly installed or improperly grounded machines can cause FIRE and ELECTROCUTION hazards.
To avoid these hazards, you MUST follow requirements in local electrical codes.
Failure to follow code could result in death or serious injury.
WARNING:
Hazardous voltage w/capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run and AFD
(Adaptive Frequency™ Drive) capacitors before servicing.
Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized.
• For variable frequency drives or others energy storing component provided by Trane or others, refer to the
appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an
appropriate voltmeter that all capacitors have discharged.
• DC bus capacitors retain hazardous voltages after input power has been disconnected. Follow proper lockout/
tagout procedures to ensure the power cannot be inadvertently energized. After disconnecting input power,
wait five (5) minutes for units which are equipped with EC fans and wait twenty (20) minutes for units which are
equipped with variable frequency drive (0V DC) before touching any internal components.
Failure to follow these instructions could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see “Adaptive Frequency™ Drive (AFD3)
Capacitor Discharge,” p. 28 and BAS-SVX19B-E4.
WARNING!
Hazardous Voltage - Pressurized Burning Fluid:
Before removing compressor terminal box cover for servicing, or servicing power side of control panel, CLOSE
COMPRESSOR DISCHARGE SERVICE VALVE and disconnect all electric power including remote disconnects.
Discharge all motor start/run capacitors. Follow lockout/tagout procedures to ensure the power cannot be
inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged.
The compressor contains hot, pressurized refrigerant. Motor terminals act as a seal against this refrigerant.
Care should be taken when servicing NOT to damage or loosen motor terminals.
Do not operate compressor without terminal box cover in place. Failure to follow all electrical safety precautions
could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see “Adaptive Frequency™ Drive (AFD3)
Capacitor Discharge,” and BAS-SVX19B-E4.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in
equipment damage.
Important:
To prevent control malfunctions, do not run low voltage wiring (<30 V) in conduit with conductors carrying more
than 30 volts.

5
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVU010C-GB
WARNING!
Discharge Time:
Frequency converters contain DC-link capacitors that can remain charged even when the frequency converter is not
powered. To avoid electrical hazards, disconnect AC mains, any permanent magnet type motors, and any remote DC
link power supplies, including battery backups, UPS and DC-link connections to other frequency converters.
Wait 15 minutes for the water pump AFD capacitors to fully discharge before performing any service or repair work.
General Recommendations

6
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m3/h) 490 980 1400 1800 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
CG-SVU010C-GB
Installer-Supplied Components
Customer wiring interface connections are shown in the electrical schematics and connection diagrams that are
shipped with the unit. The installer must provide the following components if not ordered with the unit:
• Power supply wiring (in conduit) for all field-wired connections.
• All control (interconnecting) wiring (in conduit) for field supplied devices.
• Fused-disconnect switches or circuit breakers.
Interconnecting Wiring
Chilled Water Pump Control
NOTICE:
Equipment Damage!
If the microprocessor calls for a pump to start and water does not flow, the evaporator may be damaged
catastrophically. It is the responsibility of the installing contractor and/or the customer to ensure that a pump will
always be running when called upon by the chiller controls.
An evaporator water pump output relay closes when the chiller is given a signal to go into the Auto mode
of operation from any source. The contact is opened to turn off the pump in the event of most machine level
diagnostics to prevent pump overheat.
The relay output is required to operate the Evaporator Water Pump (EWP) contactor. Contacts should be compatible
with 115/240 VAC control circuit. Normally, the EWP relay follows the AUTO mode of the chiller. Whenever the chiller
has no diagnostics and is in the AUTO mode, regardless of where the auto command is coming from, the normally
open relay is energized. When the chiller exits the AUTO mode, the relay is timed to open in an adjustable (using TU)
0 to 30 minutes.
The non-AUTO modes, in which the pump is stopped, includes Reset, Stop, External Stop, Remote Display Stop,
Stopped by Tracer, Start Inhibited by Low Ambient Temp, and Ice Making complete.
Table 1 –
Pump relay operation
Chiller Mode Relay Operation
Auto Instant Close
Ice Making Instant Close
Tracer Override Close
Stop Timed Open
Ice Complete Instant Open
Diagnostics Instant Open
When going from Stop to Auto, the Evaporator Water Pump relay is energized. Water flow switch is activating, and
flow status information back after 15 seconds.
Installer-Supplied Components / Interconnecting Wiring

7
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVU010C-GB
If evaporator water flow is not established in 20 minutes (for normal transition), the UC800 generates a non-latching
diagnostic. If flow returns (e.g. someone else is controlling the pump), the diagnostic is cleared and normal control
resumed.
If evaporator water flow is lost once it had been established, a non-latching diagnostic is generated. If flow returns,
the diagnostic is cleared and the chiller returns to normal operation.
Lead Lag Dual Pump
The running pump is changed each time the unit is switched on.
Installer-Supplied Components / Interconnecting Wiring

8
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m3/h) 490 980 1400 1800 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
CG-SVU010C-GB
Programmable Relays
A programmable relay concept provides for enunciation of certain events or states of the chiller, selected from a list
of likely needs, while only using four physical output relays, as shown in the field wiring diagram.
The four relays are provided (generally with a Quad Relay Output LLID) as part of the Programmable Relay Option.
The relays contacts are isolated Form C (SPDT), suitable for use with 120 VAC circuits drawing up to 2.8 amps
inductive, 7.2 amps resistive, or 1/3 HP and for 240 VAC circuits drawing up to 0.5 amp resistive.
The list of events/states that can be assigned to the programmable relays can be found in Table 2 Chiller events/
Status description. The relay will be energized when the event/state occurs.
Table 2 –
Chiller event/status descriptions
Alarm - Latching This output is true whenever there is any active latching shutdown diagnostic that targets the Unit, Circuit,
or any of the Compressors on a circuit.
Alarm - NonLatching This output is true whenever there is any active non-latching shutdown diagnostic that targets the Unit,
Circuit, or any of the Compressors on a circuit.
Alarm This output is true whenever there is any active latching or non-latching shutdown diagnostic that targets
the Unit, Circuit, or any of the Compressors on a circuit.
Alarm Ckt 1 This output is true whenever there is any active latching or non-latching shutdown diagnostic that targets
Circuit 1, or any of the Compressors on Circuit 1.
Alarm Ckt 2 This output is true whenever there is any active latching or non-latching shutdown diagnostic that targets
Circuit 2, or any of the Compressors on Circuit 2.
Unit Limit Mode This output is true whenever a circuit on the unit has been running in one of the limit modes continuously
for the Limit Relay debounce time. A given limit or overlapping of different limits must be in effect
continuously for the debounce time prior to the output becoming true. It will become false if no limits are
present for the debounce time.
Compressor Running The output is true whenever any compressor is running.
Circuit 1 Running The output is true whenever any compressor of Circuit 1 is running.
Circuit 2 Running The output is true whenever any compressor of Circuit 2 is running.
Ice Making This output is true when Ice Building status is active.
Maximum Capacity The output is true whenever the unit has reached maximum capacity continuously for the Max Capacity
Relay s time. The output is false when the unit is not at maximum capacity continuously for the lter time.
Evaporator Water
Freeze Avoidance
Request
This relay output is energized any time either the Low Evaporator Water Temperature – Unit Off or the
Low Evaporator Temperature Ckt x – Unit Off diagnostics are active. This relay is intended for use as an
external interlock for a eld engineered and provided solution to mitigate the freeze danger implied by
these diagnostics. Generally, this would be used in cases where operation of the evaporator water pump is
unacceptable due to the system constraints, (i.e. such as mixing unconditioned warm water with controlled
supply water as provided by other parallel chillers. The relay’s output can provide the method to close
bypass valves so the circulation becomes local to the evap and excludes the load, or can be used to defeat
the evap pump override entirely while initiating an independent source of heat / ow to the evap.
None: This selection is desirable to provide an easy way for a customer to defeat the effect of the relay, if it has
already been wired. For instance, if the relay was normally programmed as an “alarm” relay, and was
wired to a claxon, it may be desirable to temporarily defeat the feature without changing wiring.
Service request (for
Unit, Compressor(s)
or water pump):
This relay will be energized when at least one Maintenance alert condition (refer to Service required
message specication) occurs, as long as at least one of associated informational diagnostic(s) will be
active.
Hot Water Control: The output is true if capacity control is in Hot Water Control mode (water temperature being controlled
to the Active Hot Water Setpoint). The output is false in any other capacity control mode (Chilled Water
Control, Ice Making, etc...)
Warning
The output is true whenever there is any active warning diagnostic that is associated with the Unit, Circuit, or any of
the compressors on a circuit.

9
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVU010C-GB
Relay Assignments Using Tracer™ TU
Tracer™ TU Service Tool is used to install the Programmable Relay Option package and assign any of the above lists
of events or status to each of the four relays provided with the option. (See “Tracer™ TU,” for more information on
the Tracer TU service tool) The relays to be programmed are referred to by the relay’s terminal numbers on the LLID
board 1A18.
The default assignments for the four available relays of the Programmable Relay option are:
Table 3 –
Programmable Relay option Default assignments
Relay
Relay 0 Terminals J2 - 1,2,3: Evaporator Freeze Avoidance Request
Relay 1 Terminals J2 - 4,5,6: Maximum Capacity
Relay 2 Terminals J2 - 7,2,3: Compressor Running
Relay 3 Terminals J2 – 10,11,12: Latching Alarm
The eight available relays in the Lead/Lag Chiller Sequence Option are assigned with the following defaults as follows:
Table 4 –
Lead/Lag Chiller Sequence Option Default assignments
LLID Name LLD Software
Relay Designation Output Name Default
Operating Status
Programmable Relays
Module 1
Relay 0 Status Relay 1, J2-1,2,3 Evaporator Water Freeze Avoidance Request
Relay 1 Status Relay 2, J2-4,5,6 Maximum Capacity
Relay 2 Status Relay 3, J2-7,8,9 Compressor Running
Relay 3 Status Relay 4, J2-10,11,12 Latching Alarm
Operating Status
Programmable Relays
Module 2
Relay 4 Status Relay 5, J2-1,2,3 Alarm Ckt 2
Relay 5 Status Relay 6, J2-4,5,6 Alarm Ckt 1
Relay 6 Status Relay 7, J2-7,8,9 Alarm (Latching or Non latching)
Relay 7 Status Relay 8, J2-10,11,12 Non Latching Alarm
If any of the Alarm/Status relays are used, provide electrical power, 115 VAC with fused-disconnect to the panel
and wire through the appropriate relays (terminals on 1A10). Provide wiring (switched hot, neutral, and ground
connections) to the remote annunciation devices. Do not use power from the chiller’s control panel transformer
to power these remote devices. Refer to the field diagrams which are shipped with the unit.

10
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m3/h) 490 980 1400 1800 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
CG-SVU010C-GB
Low Voltage Wiring
The remote devices described below require low voltage wiring. All wiring to and from these remote input devices
to the Control Panel must be made with shielded, twisted pair conductors. Be sure to ground the shielding only at
the panel.
Important:
To prevent control malfunctions, do not run low voltage wiring (<30 V) in conduit with conductors carrying more
than 30 volts.
Emergency Stop
UC800 provides auxiliary control for a customer specified/installed latching trip out. When customer furnished
remote contact 6S2, the chiller will run normally when the contact is closed. When the contact opens, the unit will
stop and a manually resettable diagnostic is generated. This condition requires manual reset at the chiller switch
on the front of the control panel.
This customer-furnished contact must be compatible with 24 VDC, 12 mA resistive load.
External Auto/Stop
If the unit requires external Auto/Stop function, the installer must provide remote contact 6S1.
The chiller will run normally when the contact is closed. When contact opens, the compressor(s), if operating,
will go to the RUN: UNLOAD operating mode and cycle off. Unit operation will be inhibited. Closure of the contact
will permit the unit to return to normal operation.
Field-supplied contacts for all low voltage connections must be compatible with dry circuit 24 VDC for a 12mA
resistive load. Refer to the field diagrams that are shipped with the unit.
Ice Making (Optional)
When the Ice Making Command is removed (i.e. all the installed Ice Making inputs are set to “auto”), the
compressors shall be stopped after the run unload period (if not already stopped due to Ice Making Complete).
The chiller shall return to normal Auto mode of operation, and allowed to restart only after enforcing a 2 minute
delay called the “Ice to Normal Transition time”. During this inhibit, the Evaporator water flow request shall be
commanded on. After the delay, the chiller can restart again per the differential to start and the normal Chilled Water
Setpoint (or Hot Water Setpoint – if in Heating Mode). The Ice To Normal Transition inhibit shall be annunciated as a
Chiller Submode and a countdown timer showing the remaining time left shall be displayed.
Ice Making Configuration:
Ice Making is configured through TU, by the Evaporator Application item ‘Ice’.
If the Evaporator Application is set to ‘Ice’, the application will require the following LLID:
• External Ice Making Input (Dual Low Voltage Binary Input)
Ice Making Setpoints:
After Ice Making is configured, there shall be three Ice Making Settings or Setpoints:
1. Ice Making Command
2. Ice Making Enable/Disable
3. Ice Making Termination Setpoint
The ice making setpoints can all be manipulated through TU. Some of the Setpoints can be manipulated with User
Interface on the Display, the External Hardware Interface BAS (if a BAS is installed).
The setpoints associated with ice making are explained in more detail below.
Low Voltage Wiring / Ice Making (Optional)

11
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVU010C-GB
Ice Making (Optional)
Ice Making Command
This is the command to enter ice making. This setting is defined as an Auto/On settings. Setting this to On will
command the application into ice building if ice building is enabled and the Chiller is in the “Auto” command mode.
Setting the Ice Making command to Auto will command the application to follow the next priority functional mode.
Regardless of the setting of the Setpoint Source any of the following 3 signals can combine to comprise the Ice
Building Command (assuming they are each installed).
– Contact closure input for External Ice Making Command
– Front Panel Ice Making Command (also writable from TU)
– Lontalk Communicated Ice Making Command (LCI-C, BACnet, Modbus)
All ice making signals have to be turned to “auto” to be able to turn back Ice Making Command to “Auto” mode.
The overall Ice Making Command, must be toggled from “Ice Making”, to “Auto” to “Ice Making” again, before
Ice Making can be entered a second time.
Ice Making Enable/Disable setting
This setting does not start or stop ice building. This is the command to enable or disable the entire ice building
feature. It can only be set through the Display or TU. The Ice Making Command starts and stops ice building.
Ice Making Termination setpoint
This setpoint controls when Ice Making is complete. If the Entering Water Temperature decreases below this setpoint
with no deadband Ice Making will be deemed complete. This setpoint has a range of –6.7°C (20°F) to 0°C (32°F) with
a default of -2.8°C (27°F).
If Programmable Relay Option is included with Evaporator Application item ‘Ice’ then UC800 provides auxiliary
control thanks to Ice Making Status Relay. The normally open contact will be closed when ice making is in progress
and open when ice making has been normally terminated either through Ice Termination setpoint being reached
or removal of the Ice Making command. This relay inform customer equipment with chiller mode changes from
“ice making” to “ice complete”
When contact is provided, the chiller will run normally when the contact is open.
Note:
When the unit runs in Ice Making mode, and the evaporator entering water temperature drops below the ice
termination setpoint, the chiller terminates the Ice Making mode and changes to the Ice Making Complete Mode.
NOTICE:
Equipment Damage!
Freeze inhibitor must be adequate for leaving water temperature unless system components can be damaged.
Tracer™ TU must also be used to enable or disable Ice Machine Control. This setting does not prevent the Tracer
from commanding Ice Making mode. Upon contact closure, the UC800 will initiate an ice making mode, in which
the unit runs fully loaded at all times. Ice making shall be terminated either by opening the contact or based on the
entering evaporator water temperature. UC800 will not permit the ice making mode to be entered again until the unit
has been switched out of ice making mode.
If, while in ice making mode, the unit gets down to the freeze stat setting (water or refrigerant), the unit will shut
down on a manually resettable diagnostic, just as in normal operation.
Connect leads to the proper terminals. Refer to the field diagrams which are shipped with the unit. This customer
supplied contacts must be compatible with 24 VDC, 12 mA resistive load.

12
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m3/h) 490 980 1400 1800 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
CG-SVU010C-GB
External setpoints & capacity outputs (Optional)
External Chilled/Hot Water Setpoint (ECHWS)
The UC800 provides inputs that accept either 4-20 mA or 2-10 VDC signals to set the ECHWS. This is not a reset
function. The input defines the setpoint. This input is primarily used with generic BAS (building automation
systems).
Functional Description
When the unit is in cooling mode, the external water setpoint (EWS) corresponds to the chilled water setpoint. When
the unit is in heating mode, the external water setpoint (EWS) corresponds to the hot water setpoint. The external
water setpoint shall have a configurable minimum and maximum set for cooling, and another one for heating.
2-10 VDC and 4-20 mA shall each correspond to an EWS range with a configurable minimum and maximum EWS.
The following relationships exist:
Input Signal External Water Setpoint
< 1 VDC Invalid
1 VDC to 2 VDC min
2 VDC to 10 VDC min + (max – min) *
(Signal – 2) / 8
10 VDC to 11 VDC max
> 11 VDC Invalid
< 2 mA Invalid
2 mA to 4 mA min
4 mA to 20 mA min + (max – min) *
(Signal – 4) / 16
20 mA to 22 mA max
> 22 mA Invalid
If the ECHWS input develops an open or short, the LLID will report either a very high or very low value back to the
main processor. This will generate an informational diagnostic and the unit will default to using the Front Panel
(TD7) Chilled Water Setpoint.
Tracer TU Service Tool is used to set the input signal type from the factory default of 2-10 VDC to that of 4-20 mA.
Tracer TU is also used to install or remove, enable or disable the External Chilled Water Setpoint.
Examples
The following graphs are examples for min = -12.2°C and max = 18.3°C:

13
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVU010C-GB
External setpoints & capacity outputs (Optional)
External Demand Limit Setpoint (EDLS)
Like previously, either 2-10 VDC (default) or 4-20 mA inputs are available as option to set External Demand Limit
Setpoint. The Demand Limit Setting can also be set via the Tracer TD7 or through digital communication with Tracer
(Comm4). The arbitration of the various sources of demand limit is described in the flow charts at the end of this
section. The External Demand Limit Setpoint may be changed from a remote location by hooking up the analog input
signal to the 1A19 LLID terminals 5 and 6. Refer to the following paragraph on Analog Input Signal Wiring Details.
Functional Description
The UCM shall accept either a 2-10 VDC or 4-20 mA analog input suitable for customer connection to set the unit
external demand limit set point (EDLS).
If the EDLS input develops an open or short, the LLID will report either a very high or very low value back to the
main processor. This will generate an informational diagnostic and the unit will default to using the Front Panel
(Tracer TD7) Demand Limit Setpoint.
The Tracer™ TU Service Tool must be used to set the input signal type from the factory default of 2-10 VDC to that of
4-20 mA current. Tracer TU must be also be used to install or remove the External Current Limit Setpoint Option for
field installation, or can be used to enable or disable the feature (if installed).
If the Demand Limit Setpoint is set at 100%, the controller will allow every available compressors on the unit to run.
Number of compressors allowed = round ( Demand Limit Setpoint * Number of Compressors on Unit ).
The minimum active value is 100% / Number of Compressors on Unit.
Current limit Setpoint via 2-10 VDC signal
0
1
2
3
4
010 20 30 40 50 60 70 80 90 100
Active Demand Limit Setpoint (%)
Number of allowed compressors
(4 compressors unit)
Current limit Setpoint via 4-20 mA signal
0
1
2
3
4
5
6
010 20 30 40 50 60 70 80 90 100
Active Demand Limit Setpoint (%)
Number of allowed compressors
(6 compressors unit)

14
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m3/h) 490 980 1400 1800 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
CG-SVU010C-GB
External setpoints & capacity outputs (Optional)
ECHWS and EDLS Analog Input Signal Wiring Details
Both the ECHWS and EDLS can be connected and setup as either a 2-10 VDC (factory default), 4-20 mA, or resistance
input (also a form of 4-2OmA) as indicated below. Tracer TU must be used to set Analog Input Signal LLID type.
This is done by a setting change on the Custom Tab of the Configuration View within Tracer TU.
Priority
When Not Installed, external chilled hot water setpoint analog input, external demand limit setpoint analog input and
auxiliary binary input setpoint enable will not be used (Front panel or BAS sources used, depending which one is
valid).
Setpoint Source selections are: BAS/Ext/FP, Ext/FP, or Front Panel
When Installed, both analog I/O and binary will be used, with respect of following status:
• External chilled hot water setpoint: IF it is the highest priority and it is a valid source THEN use this external
setpoint for active chilled water setpoint.
• External demand limit setpoint: IF it is the highest priority and it is a valid source THEN use this external setpoint
for active demand limit setpoint.
• External auxiliary chilled hot water setpoint enable input: IF setpoint source is set to external/Front Panel or
Front Panel THEN:
− IF input open, use the next highest priority setpoint source (see priority list below)
− IF input closed, use the auxiliary chilled water setpoint
Priority (from highest to lowest):
• BAS communication (Bacnet, Lonworks or Modbus)
• Ice Making
• External setpoints
• Front Panel setpoints
Important:
For proper unit operation, BOTH the EDLS and ECHWS settings MUST be the same (2-10 VDC or 4-20mA), even if
only one input is to be used.

15
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVU010C-GB
Chilled Water Reset (CWR)
Functional Description
The UC800 shall reset the chilled water temperature setpoint based on return water temperature or outdoor air
temperature. The Return Reset and Outdoor Reset functions are standard.
The chilled water reset settings are as follows:
1. Reset Type – The following options are selectable: No Chilled Water Reset, Outdoor Air Temperature Reset,
Return Water Temperature Reset, or Constant Return Water Temperature Reset.
2. Reset Ratio – For Outdoor Air Temperature Reset, both positive and negative reset ratios will be allowed.
3. Start Reset
4. Maximum Reset – The maximum resets shall be with respect to the chilled water setpoint.
All parameters shall be factory set to a pre determined set of values. Field adjustment of two, three and four above
is expected to be very infrequent. Pre determined factory settings shall be set for all Reset Types.
Variable definitions:
CWS – Arbitrated chilled water setpoint, before any reset has occurred
CWS’ – Active chilled water setpoint, includes the effect of chilled water reset
CWR – Amount of chilled water reset (also called Degrees of Reset)
The above quantities are related by the equation:
CWS’ = CWS + CWR
or
CWR = CWS’ – CWS
With the chiller running and any type of chilled water reset enabled, CWR is allowed to change at a maximum rate of
1°F every 5 minutes until the actual CWR equals the desired CWR. When the chiller is not running, actual CWR shall
be set equal to the desired CWR within one minute (no maximum rate is in effect).
If Chilled Water Reset is disabled, desired CWR is 0.
Additional variable definitions:
RESET RATIO – User adjustable gain
START RESET – User adjustable reference
TOD – Outdoor air temperature
TWE – Evaporator entering water temperature
TWL – Evaporator leaving water temperature
MAXIMUM RESET – User adjustable limit providing the maximum amount of reset.
The equations for each type of reset:
Outdoor Air Temperature Reset
CWR = RESET RATIO * (START RESET – TOD)
With limits:
CWR > 0
CWR < Maximum Reset
Return Water Temperature Reset
CWR = RESET RATIO * (START RESET – (TWE – TWL))
With limits:
CWR > 0
CWR < Maximum Reset
Constant Return Water Temperature Reset
CWR = 100% * (Design Delta Temperature –
(TWE – TWL))
With limits:
CWR > 0
CWR < Design Delta Temperature

16
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m3/h) 490 980 1400 1800 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
CG-SVU010C-GB
Chilled Water Reset (CWR)
Using the Equations for calculating CWR
Notes for doing calculations:
Equation used to get Degrees of Reset:
Outdoor Air:
Degrees of Reset = Reset Ratio * (Start Reset - TOD)
Return Reset:
Degrees of Reset = Reset Ratio * (Start Reset -
(TWE - TWL))
Const Return:
Degrees of Reset = 100% * (Design Delta Temp -
(TWE - TWL))
To obtain Active CWS from Degrees of Reset:
Active CWS = Degrees of Reset + Arbitrated CWS
Note: Arbitrated CWS can either be Front Panel, BAS, or External
Reset Ratio calculation:
The Reset Ratio on the User Interface is displayed as a percentage. To use it in the above equation it must be
converted to its decimal form.
Reset Ratio percent / 100 = Reset Ratio decimal
Example of converting Reset Ratio:
If the Reset Ratio displayed on the User Interface is 50% then use (50/100) = .5 in the equation
TOD = Outdoor Air Temp
TWE = Evap Entering Water Temp
TWL = Evap Leaving Water Temp
The following graph shows the reset function for Outdoor Air Temp:
Note: This graph assumes that Maximum Reset is set to 11.11 °C
Example of Calculating Reset for Outdoor AirTemp:
If:
Reset Ratio = 35%
Start Reset =26.67 °C
TOD = 18.33 °C
Maximum Reset = 5.83 °C
How many Degrees of Reset will there be?
Degrees of Reset = Reset Ratio*(Start Reset - TOD)
Degrees of Reset = .35*(26.67-18.33)
Degrees of Reset = 2.92

17
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVU010C-GB
Chilled Water Reset (CWR)
If:
Reset Ratio = -70%
Start Reset =32.22 °C
TOD =37.77°C
Maximum Reset =9.44 °C
How many Degrees of Reset will there be?
Degrees of Reset = Reset Ratio*(Start Reset - TOD)
Degrees of Reset = -.7*(32.22-37.77)
Degrees of Reset = 3.89
The following graph illustrates the reset functions of the above examples:
The following graph shows the reset function for Return Chilled Water Reset:
Note: This graph assumes Maximum Reset is set to -6.7°C.
TWE-TWL is the difference between the evaporator entering water temp and the evaporator leaving water temperature.
Using the Equation for calculating CWR for Return Water Temp
Example of Calculating Reset for Return WaterTemp:
If:
Reset Ratio = 50%
Start Reset = -6.67°C
TWE = 18.3°C
TWL = 7.22°C
Maximum Reset = 4.44°C

18
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m3/h) 490 980 1400 1800 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
CG-SVU010C-GB
Chilled Water Reset (CWR)
How many Degrees of Reset will there be?
Degrees of Reset = Reset Ratio*(Start Reset - (TWE-TWL))
Degrees of Reset = .5*(-6.67-(18.3-7.22))
Degrees of Reset = -8.875
If:
Reset Ratio = 70%
Start Reset = -6.67°C
TWE = 15.55°C
TWL = 11.67°C
Maximum Reset = -10°C
How many Degrees of Reset will there be?
Degrees of Reset = Reset Ratio*(Start Reset - (TWE-TWL))
Degrees of Reset = .7*(-6.67-(15.55-11.67))
Degrees of Reset = -18.12
The following graph illustrates the Reset Actions of the above examples:
The following graph illustrates the Reset Action of Constant Return temperature:
Note: This graph assumes a Design Delta Temp of -12.2°C.
Diagnostic
If any sensor measurement needed to perform the currently selected chilled water reset type is invalid due to loss of
communication or sensor failure, the desired CWR will be set to 0. The actual CWR is subject to maximum rate limits
described earlier.

19
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVU010C-GB
Hot Water Reset
Hot Water Reset (HWR) - CXAF only
Functional Description
The UC800 shall reset the hot water temperature setpoint based on outdoor air temperature.
The hot water reset settings are as follows:
1. Reset Type – The following options are selectable: No Hot Water Reset, or Outdoor Air Temperature Reset.
2. Reset Ratio – both positive or negative reset ratios will be allowed.
3. Start Reset
4. Maximum Reset
Variable definitions:
HWS – Arbitrated hot water setpoint , before any reset has occurred
HWS’ – Active hot water setpoint, includes the effect of hot water reset
HWR – Amount of hot water reset (also called Degrees of Reset)
The above quantities are related by the equation:
HWS’ = HWS - HWR
or HWR = HWS – HWS’
With the chiller running and hot water reset enabled, HWR is allowed to change at a maximum rate of 1°F every 5
minutes until the actual HWR equals the desired HWR. When the unit is not running, actual HWR shall be set equal to
the desired HWR within one minute (no maximum rate is in effect).
If Hot Water Reset is disabled, desired HWR is 0.
Additional variables definitions:
RESET RATIO – User adjustable gain
START RESET – User adjustable reference
TOD – Outdoor Air Temperature
MAXIMUM RESET – User adjustable limit providing the maximum amount of reset
The equation for Outdoor Air Temperature Reset:
HWR = RESET RATIO * ( TOD – START RESET )
With limits:
HWR >= 0
HWR <= Maximum Reset
Example of calculating reset for outdoor air Temp:
If:
Reset Ratio = 30%
Start Reset = 10°C
Maximum Reset = 5°C
TOD = 15°C

20
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m3/h) 490 980 1400 1800 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
CG-SVU010C-GB
How many degrees of reset will there be?
Degrees of Reset = Reset Ratio*(TOD – Start Reset)
Degrees of Reset = 0.30 *( 15 – 10)
Degrees of Reset = 1.5
The following graph illustrates the reset function of the above example:
39.5
40.5
41.5
42.5
43.5
44.5
45.5
0
1
2
3
4
5
6
-15 -10 -5 0 5 10 15 20 25 30 35 40
Active Setpoint (°C)
Reset value (°C)
Outdoor Air Temp (°C)
Reset Active Setpoint (FPSP=45°C)
Example
Reset ratio = 30%
Start reset = 10°C
Maximum reset = 5°C
Hot Water Reset
Other manuals for Tracer TD7
1
Table of contents
Popular Control Panel manuals by other brands

Victron energy
Victron energy CCGX manual

Mitsubishi Electric
Mitsubishi Electric E1041 installation manual

Genius
Genius iTouch Series installation guide

Honeywell
Honeywell Silent Knight SKE Series Installation and operation manual

Zooper
Zooper Premier M+ installation manual

Mitsubishi Electric
Mitsubishi Electric GT1020 Series Startup guide