Trane ReliaTel User manual

Trane® Commercial Touch Screen
Programmable Zone Sensor
for ReliaTel™ and Symbio® 400/700/800
Controls
Installation Guide
April 2022 BAS-SVN028K-EN
Part Number: Symbio® 400: X13790993001 (SEN02587)
ReliaTel™: X13790994001 (BAYSENS924)
Symbio® 700/800: X13791009001 (BAYSENS800)
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are
attached to the equipment.

© 2022 Trane BAS-SVN028K-EN
Introduction
Read this manual thoroughly before operating or servicing
this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required. Your personal safety and the proper operation of
this machine depend upon the strict observance of these
precautions.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment. Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
and HCFCs such as saturated or unsaturated HFCs and
HCFCs.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified according to local rules. For
the USA, the Federal Clean Air Act (Section 608) sets forth
the requirements for handling, reclaiming, recovering and
recycling of certain refrigerants and the equipment that is
used in these service procedures. In addition, some states
or municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
The three types of advisories are defined as follows:
WARNING Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
CAUTIONsIndicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
NOTICE Indicates a situation that could result in
equipment or property-damage only
accidents.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
Personal Protective Equipment (PPE)
Required!
Failure to wear proper PPE for the job being undertaken
could result in death or serious injury. Technicians, in
order to protect themselves from potential electrical,
mechanical, and chemical hazards, MUST follow
precautions in this manual and on the tags, stickers,
and labels, as well as the instructions below:
• Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being
undertaken (Examples; cut resistant gloves/sleeves,
butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Safety Data Sheets
(SDS) and OSHA guidelines for proper PPE.
• When working with or around hazardous chemicals,
ALWAYSrefer totheappropriateSDSandOSHA/GHS
(Global Harmonized System of Classification and
Labeling of Chemicals) guidelines for information on
allowable personal exposure levels, proper
respiratory protection and handling instructions.
• If there is a risk of energized electrical contact, arc, or
flash, technicians MUST put on all PPE in accordance
with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.

Introduction
BAS-SVN028K-EN 3
Copyright
This document and the information in it are the property of
Trane, and may not be used or reproduced in whole or in
part without written permission. Trane reserves the right
to revise this publication at any time, and to make changes
to its content without obligation to notify any person of
such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in
death or serious injury.
• All Trane personnel must follow the company’s
Environmental, Health and Safety (EHS) policies
when performing work such as hot work, electrical,
fall protection, lockout/tagout, refrigerant handling,
etc. Where local regulations are more stringent than
these policies, those regulations supersede these
policies.
• Non-Trane personnel should always follow local
regulations.

4BAS-SVN028K-EN
Table of Contents
Equipment/Software Supported . . . . . . . . . . . 5
ReliaTel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Symbio 400 . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Symbio 700 . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Symbio 800 . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Location Guidelines . . . . . . . . . . . . . . . . . . . . 6
Installing the Sensor . . . . . . . . . . . . . . . . . . . 6
Zone Sensor Wiring . . . . . . . . . . . . . . . . . . . . . . 7
Communication Wire . . . . . . . . . . . . . . . . . . 7
External Sensor Inputs . . . . . . . . . . . . . . . . . 7
ReliaTel Systems . . . . . . . . . . . . . . . . . . . . . . 8
Symbio 400/Symbio 400B Systems . . . . . . 9
Symbio 700 Systems . . . . . . . . . . . . . . . . . . 11
Symbio 800 Systems . . . . . . . . . . . . . . . . . . 12
General Information . . . . . . . . . . . . . . . . . . . . 13
Configuring Settings on the Home Screen 14
Cool/Heat Mode . . . . . . . . . . . . . . . . . . . . . . 14
Fan Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Schedule Menu . . . . . . . . . . . . . . . . . . . . . . 14
Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Touch Button Legend . . . . . . . . . . . . . . . . 14
Menu Navigation . . . . . . . . . . . . . . . . . . . . . . . 15
Interface Flowchart, Part 1 . . . . . . . . . . . . . 15
Interface Flowchart, Part 2 . . . . . . . . . . . . . 16
Interface Flowchart, Part 3 . . . . . . . . . . . . . 17
Interface Flowchart, Part 4 . . . . . . . . . . . . . 18
Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Menu Definitions . . . . . . . . . . . . . . . . . . . . . . . 19
Configuration . . . . . . . . . . . . . . . . . . . . . . . . 19
Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Clock, Schedule, Setpoints, and Options . 23
Service View. . . . . . . . . . . . . . . . . . . . . . . . . 24
Installation Instructions . . . . . . . . . . . . . . . . . 25
Symbio 400 . . . . . . . . . . . . . . . . . . . . . . . . . . 25
ReliaTel BCI-R . . . . . . . . . . . . . . . . . . . . . . . . 25
Symbio 700/800 . . . . . . . . . . . . . . . . . . . . . . 26
Zone Sensor Configuration . . . . . . . . . . . . .26
ReliaTel Field Upgrade Procedure . . . . . . . . .27
BCI-R Initialization Procedure . . . . . . . . . . .27
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . .28

BAS-SVN028K-EN 5
Equipment/Software Supported
The three zone sensor models are compatible with the
following HVAC equipment and control systems. The
sensor is designed for use with stand-alone space comfort
control equipment only. It is not designed for use in a
building automation system.
ReliaTel
The zone sensor controls Precedent™, Voyager™ 2,
Voyager 3, and Odyssey™ CV/SZVAV/Multi-speed indoor
fan equipment that uses the ReliaTel control system.
For proper operation, the ReliaTel RTRM board must be
installed in the equipment with software version 19.2 or
later. In addition, the BCI-R board must be installed with
software version 6.00 or later.
Multi-zone systems are not supported. In the field, Multi-
zone HVAC equipment can be identified by the presence of
the ReliaTel RTAM board installed in the equipment
Symbio 400
The zone sensor controls factory-programmed fan coil,
blower coil, and both staged and variable speed water
source heat pump equipment that uses the Symbio 400
control system. Field-programmed Symbio 400 controlled
equipment is not supported.
Symbio 700
The zone sensor controls any equipment that uses the
Symbio 700 control system. Multi-zone systems are not
supported.
Symbio 800
The zone sensor controls IntelliPak equipment that uses
the Symbio 800 control system.

6BAS-SVN028K-EN
Installation
Location Guidelines
• Do not install on an outside wall.
• Do not install in areas with direct heat source.
• Do not install near any air discharge grill.
• Do not install in areas exposed to direct sunlight.
• Ensure the sensor has sufficient air circulation.
• Ensure the mounting wall surface is flat and clean.
Installing the Sensor
1. Remove the security screw from the bottom of the
sensor (if present).
2. Firmly grasp the sensor and pull up on the bottom to
remove the front cover.
3. Feed the wires from the wall through the backside of
sensor base.
4. Ensure the sensor is oriented correctly. The word 'TOP'
is embossed on the backplate to indicate correct
orientation. Mark the top/bottom mounting hole
locations on the wall.
5. Install the provided wall anchors and then affix the
sensor base to the wall using the provided screws.
6. Strip the wire coating from the ends of each wire
approximately 0.25 inch.
7. Insert the wires into the wire terminals (per terminal
identification below) and tighten down the terminal
screws to secure wire.
8. Push any excess wire back into the wall and then
replace the sensor cover. Once the cover snaps on, the
sensor powers up.
9. Replace the security screw on the bottom of the sensor
to avoid tampering.

BAS-SVN028K-EN 7
Zone Sensor Wiring
Wiring the zone sensor to the HVAC equipment varies
based on the control system to which the sensor is
connected. Reference one of the following electrical
schematics for proper wiring installation of the zone
sensor to the HVAC equipment.
Communication Wire
Use the correct communication wire to ensure reliable
communication between the zone sensor and the HVAC
equipment. Trane recommends the following wire
supplier and wire type.
Important: This sensor can only be used with
standalone HVAC equipment. It cannot be
used on a BACnet/MSTP link connected to a
BAS.
Suggested Supplier: Windy City Wire
• Plenum rated P/N: 043005AL
• Non-plenum rated P/N: 108760
Other wire may be used if it conforms to the following
physical characteristics:
• Twisted pair (2-conductor) plus shield.
• Characteristic Impedance: 100 and 130 ohms.
• Distributed capacitance between conductors: < 100 pF/
m.
• Distributed capacitance between conductor and
shield: < 200 pF/m.
• Foil or braided shield is acceptable.
• Wire diameter: 22 to 18 AWG.
External Sensor Inputs
The zone sensor supports three external inputs that can be
used to control the behavior of the sensor.
• Demand shed signal. A dry contact relay can be wired
to terminals 16 and 18. Closure of the contact indicates
to the sensor that a demand shed request is present.
• Motion Sensor or external occupancy signal. A dry
contact relay can be wired to terminals 17 and 18.
Closure of the contact indicates to the sensor that the
space is not occupied.
When the sensor is configured for occupied standby
control and it is in occupied mode based on a time
schedule. Closure of the contact indicates the space is
not occupied and the sensor enters occupied standby
mode.
• Space temperature signal. Use a 10k ohm, type 2
thermistor/sensor when using a remote mounted
space sensor wired to terminals 17 and 18, or wired to
HVAC equipment.
Important: Configure the Temp Sensor parameter as
needed. See 2/4 Configuration menu for
details.

Zone Sensor Wiring
8BAS-SVN028K-EN
ReliaTel Systems
The zone sensor and the BCI-R form a two-node BACnet
MS/TP network. Wire the system as shown in the
schematic below while adhering to the following
recommendations:
• At the RTRM board, terminate the shield wire at J7-
COM terminal. The shield wire may need to be
extended to make this connection. Use an insulated
extension wire to prevent contact with the metal
enclosure and circuit boards.
• Set the link switch on the BCI-R to BACnet.
Important: Install a jumper wire between terminals J6-
1 and 2 when the internal temperature
sensor or a sensor wired to terminals 17 and
18 is used.
.

Zone Sensor Wiring
BAS-SVN028K-EN 9
Symbio 400/Symbio 400B
Systems
The zone sensor and the Symbio 400/Symbio 400B form a
two-node BACnet MS/TP network. Wire the system as
shown in the schematic below.

Zone Sensor Wiring
10 BAS-SVN028K-EN

Zone Sensor Wiring
BAS-SVN028K-EN 11
Symbio 700 Systems
The zone sensor and the Symbio 700 form a two node
BACnet MS/TP network. Wire the system as shown in the
schematic below.
Note:
•The Symbio 700 controller must be an advanced
version. The controller protocol must be set to BACnet
MS/TP.
•The Symbio 700 controller must be configured for a
single setpoint zone sensor for proper operation by
using the Symbio Service and Installation App:
(Settings > Edit Configuration > Space Controller =
Single Setpoint Zone Sensor)
or Local Display (Utilities > Unit Config > Edit Unit
Config > Space Controller = Single Setpoint Zone
Sensor).

Zone Sensor Wiring
12 BAS-SVN028K-EN
Symbio 800 Systems
The zone sensor and the Symbio 800 form a two node
BACnet MS/TP network. Wire the system as shown in the
schematic below.

13 BAS-SVN028K-EN
General Information
The sensor displays Power on during initial power-up and
advances to display the Home Screen.
All user accessible functions are easily set from the Home
screen:
• Occupancy Status: displays either Occupied,
Unoccupied, or Override to indicate current occupancy
mode.
• Fan Status: when fan is running, exterior circle
indicates current fan speed.
– No Segments: Fan is OFF
– One Segment: 1% to 33%
– Two Segments: 34% to 66%
– Three Segments: 67% to 100%
• Setpoint: When Heat/Cool Mode is Cool Only or Heat
Only, the current setpoint in use is displayed in the
center of the setpoint control bar.
When mode is Auto or Off, the cooling setpoint is
displayed just below the red bar and the heating
setpoint is displayed just above the blue bar.
• Message Line: Displays information regarding the
current state of the equipment.
– Please adjust clock: verify the date/time information
is correct.
– Shed demand: a demand shed signal is present.
The zone sensor controls to the demand shed
setpoints.
– Shed cancel: a demand shed signal is present and
the user has overridden the demand shed
signal.The zone sensor controls to the occupied
setpoints.
– Contact service: the zone sensor has detected an
HVAC equipment temperature sensor failure,
economizer fault, or loss of communication with the
HVAC equipment.
– Temperature sensor failure: displayed if any
temperature sensor in use has failed. If the 'remote'
or 'wired' space temperature sensor has failed, the
zone sensor switches to the internal temperature
sensor for temperature control.
– Temp sensor failure could be from OAT, MAT, RAT,
SAT (DAT) or space temp.
DAT SAT sensor is optional on CV units and is not
always installed.
• Single tap of or advances the setpoint value by
one. Holding down or rapidly advances through
the available range of values.
• Temperature: Displays either the current space
temperature or the temperature setpoint currently
being used to condition the space.
• If configured to do so, the Home screen will revert to a
blank standby screen after 2.5 minutes of user
inactivity.
• All settings are retained in sensor memory in the event
of a power outage.
Occupancy
Status
Temperature
Heat/Cool Mode
Fan Mode
Override
Message Line
Please adjust clock
Schedule Menu
Increment Down
Cooling Setpoint
Increment Up
Fan Status
Heating Setpoint

BAS-SVN028K-EN 14
Configuring Settings on the Home Screen
Icon buttons displayed on the Home screen can be
changed by selecting 1 of 3 available home screen
configurations. See menu 1/2 Setup > 1/2 Display > User
HMI.
Cool/Heat Mode
• Off: the system will not cool nor heat the space.
• Auto: the system switches between cooling and
heating automatically to condition the space.
• Cool: the system will only provide cooling to the space.
• Heat: the system will only provide heat to the space.
Fan Mode
• Auto: the system fan runs only when there is a call for
either cooling or heating.
• On: the system fan runs continuously in occupied
mode. The fan runs only when there is a call for heating
or cooling in unoccupied mode.
Schedule Menu
Tap to access the Schedule Menu. From this menu the
date/time, schedule events, and temperature setpoints can
be adjusted. The Options sub-menu allows the user to
override schedule control and change the schedule type.
Override
Tap to override/cancel occupancy mode, cancel
temperature setpoint overrides, and exit/enter demand
shed mode.
Touch Button Legend
Return to Home screen.
Previous and Next screen advancement.
Change setting values.
Reset the instance number on 2/2 Network Instance
screen.
Confirms the change to instance number.
R
R
RRR

15 BAS-SVN028K-EN
Menu Navigation
Interface Flowchart, Part 1
Tapping on one of the six selections on the 1/2 Setup page
or advancing to 2/2 Setup page allows the installer access
to set the device configuration parameters. The following
pages provide a flow chart of features.
.
Note: The installer password is 4017 and cannot be changed.

Menu Navigation
16 BAS-SVN028K-EN
Interface Flowchart, Part 2
.

Menu Navigation
BAS-SVN028K-EN 17
Interface Flowchart, Part 3

Menu Navigation
18 BAS-SVN028K-EN
Interface Flowchart, Part 4
There are no field configurable parameters in the Lua
menus. This menu is displayed to confirm that the version
of the sensor is correct for the application.
Note: Sensors that show UC400 are also compatible with
Symbio 400 controllers. Sensors that show Symbio
800 are also compatible with Symbio 700
controllers.
Network
Refer to the Zone Sensor Configuration section at the end
of this document for zone sensor configuration
instructions.
Sens. Address Defines the BACnet MAC address of the zone
sensor (0-127).
Unit address Defines the BACnet MAC address of the HVAC
equipment (0-127).
Baud rate
Defines the baud rate of the zone sensor. Default is
76800 (use default value unless directed by Trane
Technical Support).
Status Indicates if a network is established between the
zone sensor and the HVAC equipment.
2/2 Network
Instance
Defines the BACnet Device ID of the sensor. Tap
to Confirm and Save the value (0 - 4194302).
Tapping Ron this screen copies the sensor MAC
address number to the BACnet Device ID field. For
example, if the MAC address = 7, tapping R sets the
Device ID number to 7.

19 BAS-SVN028K-EN
Menu Definitions
Configuration
Installer pwd The installer password is fixed at the value 4017 and cannot be changed.
Schedule menu
Defines schedule menu user access and display of the clock value on the home screen:
• Enable – Schedule, Clock.
• Disable – No Schedule, Clock.
• En. no. clk (Enable No Clock) – Schedule, No Clock.
• Dis. no. clk (Disable No Clock) – No Schedule, No Clock.
When the schedule is enabled, if the user touches and holds either the upper left or right corner of
the display, the schedule menu will be displayed. When the clock is enabled, the current time is
displayed at the top of the Home screen.
Note: The installer password function does not prevent a user from accessing the schedule menu
via the corner touch method. It is recommended to disable this feature if there is intent to prevent
the user from changing the schedule.
Calib. temp. Provides a means to adjust the raw value measured by the temperature sensor internal to the
zone sensor. Used to calibrate the zone sensor to an external reference value.
Temp. occ. time Defines the length of time that a temporary override command remains in effect (15 min. to 240
min.).
Eco. enable(a)
Defines the source of the economizer enable temperature or enthalpy setpoint.
• On – Zone sensor setpoint in use.
• Off – HVAC equipment setpoint in use.
Note: The method of economizer control, OA temperature or OA enthalpy, is an HVAC equipment
control system configuration setting.
Eco. temp. SP(a) Defines the economizing temperature termination setpoint. If the outdoor air temperature is
above the setpoint, then the system will not economize.
(Range: 50°F to 140°F [10°C to 60°C])
Eco. enth. SP(a)
Defines the economizing enthalpy termination setpoint. If the outdoor air enthalpy is above the
setpoint, then the system will not economize.
(Symbio 800 range: 19 to 36 BTU/lb [26 to 66 kJ/kg])
(ReliaTel range: 19 to 28 BTU/lb [26 to 47 kJ/kg])
Opt. start/stop
Defines the use of schedule optimization.
• On – Optimal start: HVAC equipment will start a calculated amount of time prior to a schedule
occupied event. This enables the space temperature to reach the occupied temperature setpoint
at the beginning of the occupied period.
• On – Optimal stop: HVAC equipment will switch to unoccupied temperature setpoints a
calculated amount of time prior to the schedule unoccupied event. This enables the space
temperature to reach the unoccupied setpoint at the beginning of the unoccupied period.
• Off – HVAC equipment will start and stop based on the schedule events.
Shed perm. Defines the behavior of the zone sensor when a load shed signal is received.
• On – Upon receipt of demand shed signal, the load shed cooling/heating setpoints are used to
control the space.
• Off – the load shed signal is ignored.
Shed sys. off
Defines the load shed sequence in use when a load shed signal is present and Shed perm.
parameter is set to on.
• On – when a load shed command is received, the equipment will stop heating/cooling for 5
minutes and adjust the setpoints.
• Off – when a load shed command is received, the equipment will continue in its current mode
and adjust the setpoints.
Shed offset
Defines temperature offset applied to calculate load shed setpoints. The value is added to the
occupied cooling setpoint and subtracted from the occupied heating setpoint. The resultant values
are the load shed cooling/heating setpoints.
(Range: 4.0°F to 5.0°F [2.0°C to 2.5°C])

Menu Definitions
20 BAS-SVN028K-EN
Erase all? Resets the sensor back to factory settings.
Are you sure? Confirms the erase reset.
UC17 config
Defines the sensor connected to electrical terminals 17 and 18.
• None – terminal not in use.
• Motion – motion sensor or external dry contact.
• Temp – 10K temperature sensor.
Temp. sensor
Defines the location of the space temperature sensor used for control.
• Internal – sensor internal to the zone sensor.
• Remote – sensor wired to the HVAC equipment.
• Wired – sensor wired to zone sensor terminals 17 and 18.
Occupancy src Defines the source of the occupancy signal.
• Schedule – zone sensor time schedule.
• Motion – motion sensor or external dry contact wired to zone sensor.
(a)The parameter is only displayed when the zone sensor is connected to a ReliaTel or Symbio 800 control system.
Other manuals for ReliaTel
1
This manual suits for next models
4
Table of contents
Other Trane Touch Panel manuals