Trapzilla TSS-95-ECA Installation and operating instructions

A THERMACO® Technology
Copyright ©2014 Trapzilla® Thermaco, Inc. • P.O.Box 2548 • Asheboro, NC 27204
Toll Free: (800) 633-4204 • V: (336) 629-4651 • F: (336) 626-5739
E-mail: [email protected] • www.trapzilla.com
Installation & Maintenance Instructions
For Trapzilla® Solids Separators
Part# MNL-TSS
AC-ver1
TSS-95
Trapzilla Solids Separator

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 2
A THERMACO® Technology
Section I: Trapzilla Solids Separators 3
System Overview 3
Section II: Models and Options 4
In-Ground Models 4
Above-Ground Models 5
Basic Models 6
Options 7
Section III: TSS Installation 8
Plumbing Installation 8
Congurations 11
Above-Ground Installation 15
In-Ground Installation 17
Hanging Installation 22
Section IV: System Maintenance 23
Limited Warranty 25
Table of Contents
Table of Contents

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 3
A THERMACO® Technology
Section I: Trapzilla®Grease Interceptors
Thermaco, Inc. also offers the TSS
Trapzilla Solids Separator that traps
incidental kitchen solids upstream of
the Trapzilla Grease Interceptor.
The proper installation of a Trapzilla®
Supercapacity Solids Separators can
reduce or eliminate solids problems
and costly sewer surcharges and
nes through efcient separation and
retention of incidental solids.
The unique compact design of the
Trapzilla allows for installation into
most facilities. Options are available
that enable a Trapzilla unit to be in-
stalled on the oor, suspended from
the ceiling or in-ground outside the
facility.
Trapzilla Solids Interceptor units are designed to treat high ows of kitchen drainwater with large
solids storage capacity within a small footprint unit. These units are easy to manueuver into
position and just as easy to plumb.
Grease interceptors, grease traps, automatic recovery units, grease removal devices, solids
separators and other similar plumbing devices receiving kitchen ows from sinks, oor drains,
woks and other food bearing sources may generate odors. There are many factors inuencing
odor evolution and dissemination. These include room ventilation, kitchen menu, ambient tem-
peratures, ware washing practices, grease/oil input, daily input uid volume, sanitizers, installation
plumbing design and product maintenance/upkeep. Odors are usually prevented by good area
ventilation, frequent uid inputs, good product maintenance practices and proper product instal-
lation. Additional steps, including aeration, chlorination, improved area ventilation and additional
maintenance control, may be needed at some sites.
System Overview

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 4
A THERMACO® Technology
Section II: Models and Options
TSS-95-ECA
TSS-70-ECA
In-Ground Models
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANGLE PRO JECTION
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANGLE PROJECT ION
95 gallons of solids retention capacity, capable of handling
ow rates of up to 150 gpm. Equipped with 4” inlet/outlet,
2” vessel vent connection, and 4” Low-Head Flow Control
Accessory to limit ow to 75 gpm.
Comes with: 18” tall Extension Collar Adapter Lid
Assembly with 22” diameter lid.
70 gallons of solids retention capacity, capable of handling
ow rates of up to 75 gpm. Equipped with 4” inlet/outlet,
2” vessel vent connection, and 4” Low-Head Flow Control
Accessory to limit ow to 75 gpm.
Comes with: 18” tall Extension Collar Adapter Lid
Assembly with 22” diameter lid.
TSS-27-ECA
27 gallons of solids retention capacity, capable of handling
ow rates of up to 35 gpm. Equipped with 3” inlet/outlet,
2” vessel vent connection, and 3” Low-Head Flow Control
Accessory to limit ow to 35 gpm.
Comes with: 22” diameter lid and 29” Telescoping
Extension Collar.
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINSPROPRIETARY AND PATENTED MATERIAL. THIS DRAWINGMAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENTFROM THERMACO, INC. POSSESSION OF THIS DRAWINGDOES NOT CONSTITUTE THE RIGHT TOMANUFACTURE.
POSSESSION OF THIS DRAWINGDOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENTBETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROYTHIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO,INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX+/- .03
.XXX+/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/-1 °
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRDANG LEPR OJECTION

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 5
A THERMACO® Technology
Section II: Models and Options
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANGLE PRO JECTION
TSS-95-SSA
TSS-70-SSA
Above-Ground Models
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANGLE PROJECTIO N
95 gallons of solids retention capacity, capable of handling
ow rates of up to 150 gpm. Equipped with 4” inlet/outlet,
2” vessel vent connection, and 4” Low-Head Flow Control
Accessory to limit ow to 75 gpm.
Comes with: Standard Adapter Top Cover with 22”
diameter lid, and SSOP-70/95 for above-ground
installation.
70 gallons of solids retention capacity, capable of handling
ow rates of up to 75 gpm. Equipped with 4” inlet/outlet,
2” vessel vent connection, and 4” Low-Head Flow Control
Accessory to limit ow to 75 gpm.
Comes with: Standard Adapter Top Cover with 22”
diameter lid, and SSOP-70/95 for above ground
installation.
TSS-27-SSA
27 gallons of solids retention capacity, capable of handling
ow rates of up to 35 gpm. Equipped with 3” inlet/outlet,
2” vessel vent connection, and 3” Low-Head Flow Control
Accessory to limit ow to 35 gpm.
Comes with: 22” diameter lid and Support Stand
SSA-160.
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. D WGN O.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANGLE PROJECTIO N

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 6
A THERMACO® Technology
Section II: Models and Options
TSS-95
TSS-70
Basic Models
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THISDRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANGLE PROJECTIO N
95 gallons of solids retention capacity, capable of handling
ow rates of up to 150 gpm. Equipped with 4” inlet/outlet,
2” vessel vent connection, and 4” Low-Head Flow Control
Accessory to limit ow to 75 gpm.
Comes with: Standard Adapter Top Cover with 22”
diameter lid.
70 gallons of solids retention capacity, capable of handling
ow rates of up to 75 gpm. Equipped with 4” inlet/outlet,
2” vessel vent connection, and 4” Low-Head Flow Control
Accessory to limit ow to 75 gpm.
Comes with: Standard Adapter Top Cover with 22”
diameter lid.
TSS-27
27 gallons of solids retention capacity, capable of handling
ow rates of up to 35 gpm. Equipped with 3” inlet/outlet,
2” vessel vent connection, and 3” Low-Head Flow Control
Accessory to limit ow to 35 gpm.
Comes with: 22” diameter lid.
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANGLE PROJECTIO N

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 7
A THERMACO® Technology
Section II: Models and Options
Options
ECA-TSS-29 (in yellow) for
Trapzilla Solids Separators.
These eld-modiable extension collars
available to provide additional depth for
existing kitchen drainage piping.
-ECA Models ship with built-in
0-18” extension collar.
ECA-TSS-29 adds 0-29” depth to -ECA
Models or 5-29” to Base Models.
SSOP-70/95
Support Stand for TSS-70 and TSS-95 models
Allows unit to be installed directly on the oor in a
basement or mechanical room.
*Included with -SSA Models
FTCA-36
Fabricated Top Cover Assembly with 36” diameter
for additional traction in high foot-trafc areas and 4”
Brass cleanout port.
FTCA-22 (not shown)
22” diameter cover available for In-Ground installations.
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANGLE PROJEC TION
ECALA-TSS-18
ECA-TSS-29

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 8
A THERMACO® Technology
Section III: TSS Installation
Plumbing Installation
Locating the Unit
The system should be visible and easily acces-
sible for maintenance and inspection. Options
are available to install Trapzilla Solids Separa-
tors in a basement, suspended from a ceiling
or in-ground in an exterior location. Make sure
adequate room is provided around the unit to
allow easy access for a pump truck operator.
Make sure the height above the Trapzilla access
cover is enough to properly service the system.
Inlet/Outlet Piping
The inlet and outlet piping connections require
exible sleeve pipe couplings. Keep outlet
piping as straight as possible. Thermaco, Inc.
recommends installation of 4” (100 mm) Two-
Way Cleanouts on both the Inlet and Outlet of
Trapzilla Interceptors and Solids Separators in
accordance with all applicable laws, regulations
and codes. Use only “sweep” connections. Do
not reduce the pipe sizing on the outlet piping.
Do not install “P” trap on outlet connection of
system. (Note: The system already has a in-
ternal gas trap)
Flow Controls
Trapzilla systems are supplied with a Low-Head
Flow Control module (LHFC-4). This should be
connected to the inlet of the Trapzilla unit in situ-
ations where ow rate needs to be restriced to
75 GPM or when vented ow control is required
by local code.
Venting the Outlet
An outlet vent or approved air admittance valve
of at least 1/2 the diameter of the system’s outlet
connection must be present as close as possible
to the Trapzilla outlet to prevent possible siphon-
age problems. The Vent on the Outlet piping is
to be installed in accordance with all applicable
laws, regulations and codes. Failure to provide
a vent for the system voids Thermaco’s Limited
Warranty for the system.
For High Head Height Applications
Over Six (6) Feet (1.95 m)
For installations where there is head height of
greater than 6 feet (1.95 meters), Thermaco,
Inc. recommends installation of a code-approved
Vented Flow Control Assembly.
Note: Drawings for reference only.
Equipment must be installed in
compliance with all applicable laws,
regulations and codes, includ-
ing plumbing codes. Installation
should be performed by a qualied
plumber.

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 9
A THERMACO® Technology
Section III: TSS Installation
Note: Drawing for reference only. Equipment must be installed in compliance with
all applicable laws, regulations and codes, including plumbing codes. Installation
should be performed by a qualied plumber.
Venting of the Trapzilla tank is recommended by the manufacturer and required for
in-door installations.
•Vent the tank through the provided 2” NPT threaded connector on the side of the tank
(This vent may be located above the outlet or on the side of the tank depending on
model).
•Remove and discard the 2” plug and connect 2” vent lines as indicated below.
Plumbing Installation
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANG LE PRO JECTION
Tank Vent/Air Intake
Must be independently vented to atmosphere
NEVER CONNECT TO FACILITY VENT

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 10
A THERMACO® Technology
Section III: TSS Installation
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANG LEPR OJECTION
Plumbing Installation (for one Solids Separator)
Each Trapzilla Solids Separator is shipped with a Low Head Flow Control module (see LHFC
box for additional instructions). This needs to be installed to the inlet of the Trapzilla and con-
nected to a code-approved air intake. Thermaco, Inc. recommends installation of 4” (100 mm)
Two-Way Cleanouts on both the Inlet and Outlet of Trapzilla® Models TSS-70 and TSS-95 in
accordance with all applicable laws, regulations and codes. A Vent on the Outlet piping is also
to be installed in accordance with all applicable laws, regulations and codes.
Plumbing Installation
Note: Drawing for reference only. Equipment must be installed in compli-
ance with all applicable laws, regulations and codes, including plumbing
codes. Installation should be performed by a qualied plumber.
*Use a 4” (100 mm) Two-Way Cleanout for TSS-70,
TSS-95, TZ-400 and TZ-600 Unit Installations
Outlet Vent
(Connect to
facility vent)
Cleanout*
Cleanout*
Outlet
Inlet

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 11
A THERMACO® Technology
Section III: TSS Installation
Congurations
Two Solids Separators
Two Trapzilla Solids Separators should be installed in parallel with a Flow Splitter diverting the
ow. Place Two-Way Cleanouts before, between and after the units as shown below, includ-
ing before and after the ow splitter. Make sure to connect an outlet vent after each Trapzilla
Grease Interceptor. A Low Head Flow Control (LHFC) is shipped with each unit, and if needed
should only be installed after the rst Cleanout and before the 4” Flow Splitter.
Note: Drawing for reference only. Equipment must be installed in compli-
ance with all applicable laws, regulations and codes, including plumbing
codes. Installation should be performed by a qualied plumber.
*Use a 4” (100 mm) Two-Way Cleanout for TSS-70,
TSS-95, TZ-400 and TZ-600 Unit Installations
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANGLE PR OJECTION
Cleanout*
Cleanout*
Cleanout*
Cleanout*
Outlet
Outlet
Inlet
Trapzilla
TZ-600 unit
Trapzilla
TZ-600 unit
*Use a 4" (100 mm) Two-Way Cleanout for TSS-70,
TSS-95, TZ-400 and TZ-600 Unit Installations
Outlet Vent
(Connect to
facility vent)
4" (100 mm) Flow Splitter

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 12
A THERMACO® Technology
Section III: TSS Installation
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANG LEPR OJECTION
*Use a 4" (100 mm) Two-Way Cleanout for TSS-70,
TSS-95, TZ-400 and TZ-600 Unit Installations
Outlet
Inlet
Cleanout*
Cleanout*
Cleanout*
Trapzilla
TZ-600 unit
Trapzilla
TSS-95 unit
One Solids Separator and One Trapzilla
A single Trapzilla Solids Separator and Trapzilla Grease Interceptor should be installed in
series. Place Two-Way Cleanouts before, between and after the units as shown below. Make
sure to connect an outlet vent after the Trapzilla Grease Interceptor. A Low Head Flow Control
(LHFC) is shipped with each unit, and if needed should only be installed after the rst Cleanout
and before the Trapzilla Solids Separator.
Note: Drawing for reference only. Equipment must be installed in compli-
ance with all applicable laws, regulations and codes, including plumbing
codes. Installation should be performed by a qualied plumber.
*Use a 4” (100 mm) Two-Way Cleanout for TSS-70,
TSS-95, TZ-400 and TZ-600 Unit Installations
Congurations

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 13
A THERMACO® Technology
Section III: TSS Installation
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANGLE PR OJECTION
Outlet
Outlet
Cleanout*
Cleanout*
Cleanout*
Cleanout*
Cleanout*
Cleanout*
Inlet
Trapzilla
TSS-95 unit
Trapzilla
TZ-600 unit
Trapzilla
TZ-600 unit
Outlet Vent
(Connect to
facility vent)
4" (100mm) Flow Splitter
*Use a 4" (100 mm) Two-Way Cleanout for TSS-70,
TSS-95, TZ-400 and TZ-600 Unit Installations
One Solids Separator and Two Trapzilla Units
A single Trapzilla Solids Separator and two Trapzilla Grease Interceptors should be installed
by placing the Solids Separator in line and then using a Flow Splitter to divert the water ow to
two separate Trapzilla units in parallel. Place Two-Way Cleanouts before, between and after
the units as shown below, including before and after the ow splitter. Make sure to connect an
outlet vent after the Trapzilla Grease Interceptor. A Low Head Flow Control (LHFC) is shipped
with each unit, and if needed should only be installed after the rst Cleanout and before the
Trapzilla Solids Separator.
Note: Drawing for reference only. Equipment must be installed in compli-
ance with all applicable laws, regulations and codes, including plumbing
codes. Installation should be performed by a qualied plumber.
Congurations
*Use a 4” (100 mm) Two-Way Cleanout for TSS-70,
TSS-95, TZ-400 and TZ-600 Unit Installations

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 14
A THERMACO® Technology
Section III: TSS Installation
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANGLE PRO JECTION
*Use a 4" (100 mm) Two-Way Cleanout for TSS-70,
TSS-95, TZ-400 and TZ-600 Unit Installations
Cleanout*
Cleanout*
Cleanout*
Cleanout*
Cleanout*
Cleanout*
Cleanout*
Outlet
Outlet
Inlet
Trapzilla
TZ-600 unit
Trapzilla
TSS-95 unit
Trapzilla
TZ-600 unit
Trapzilla
TSS-95 unit
Outlet Vent
(Connect to
facility vent)
4" (100mm) Flow Splitter
Two Solids Separators and Two Trapzilla Units
Two Trapzilla Solids Separator and two Trapzilla Grease Interceptors should be installed by
placing a Flow Splitter to divert the water ow to two separate Solids Separators and Trapzilla
units in parallel. Place Two-Way Cleanouts before, between and after the units as shown
below, including before and after the ow splitter. Make sure to connect an outlet vent after the
Trapzilla Grease Interceptor. A Low Head Flow Control (LHFC) is shipped with each unit, and
if needed should only be installed after the rst Cleanout and before the 4” Flow Splitter.
Note: Drawing for reference only. Equipment must be installed in compli-
ance with all applicable laws, regulations and codes, including plumbing
codes. Installation should be performed by a qualied plumber.
*Use a 4” (100 mm) Two-Way Cleanout for TSS-70,
TSS-95, TZ-400 and TZ-600 Unit Installations
Congurations

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 15
A THERMACO® Technology
Section III: TSS Installation
The SSOP Support Stand is a one-piece assembly with a conical center that sits
on the oor. It does not add appreciable height to the assembly.
Above-Ground Installation
Using a Support Stand, a Trapzilla Solids Separator may be installed directly on top
of the oor in a location such as a basement or mechanical room.
The SSOP-70/95 should be used with Models TSS-70 and TSS-95.
*This item ships with all -SSA models.
SSOP-70/95 Support Stand
TSS-95 Trapzilla
Base Model
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANG LE PRO JECTION

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 16
A THERMACO® Technology
Section III: TSS Installation
Above-Ground Installation
When installing multiple Trapzilla units in series, the change in elevation from the
inlet to the outlet of a unit requires that each preceeding unit be installed 1” higher
than the unit after it. For above-ground units, pressure treated plywood may be
placed fully beneath the support stand to create the height difference.
All installations inside of a building must have a vessel vent installed and
piped to atmosphere.
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739 Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED SIZE REV. NO. DWG NO.
PART NO. C
SCALE RELEASE DATE SHEET OF
ENGINEERING
DRAWN DATE
THIRD ANGLE PRO JECTION
TSS-95
TZ-600
SUPPORT STAND
SSOP-TSS-70/95
SUPPORT STAND
SSOP-TZ-400/600
2 WAY CLEAN OUT
(3 PLACES)
OUTLET VENT TO
FACILITY VENT TZ
UNIT ONLY
1" ELEVATION DIFFERENCE
(MINIMUM) BETWEEN TSS
AND TZ TO ENSURE FALL
BETWEEN UNITSAND TO
COMPENSATE FOR INLET/
OUTLET HEIGHT DIFFERENCES.
TZ-600-SSA
TZ-600-SSA
or
TSS-95-SSA
TZ-600-SSA
TZ-600-SSA
or
TSS-95-SSA

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 17
A THERMACO® Technology
Section III: TSS Installation
In-Ground Installation
Trapzilla units may also be installed in the ground outside of the facility. For instances where the
facility drainage piping requires an extension collar that is no more than 18”, use the instructions
for the full TSS-95-ECA unit. If the unit is to be deeper in the ground, the ECA-TSS-29 Extension
Collar Assembly may be installed to align the Trapzilla inlet with the drainage piping. The ECA-
TSS-29 may be trimmed in the eld to t. Trim both the inner and outer portions of the extension
collar to make shorter than collapsed height. Thermaco, Inc. also recommends embedding the
in-ground Trapzilla with concrete to provide additional structural strength and to off set buoyancy
effects. For Buoyancy Calculations & suggested concrete ll quantities please see the following
page. Use the full TSS-95-ECA for 0-18” of collar needed or purchase separately the TSS-95
and ECA-TSS-29 for 5-29” of collar needed.
In-Ground Installations inside of a building must have a vessel vent installed and piped
to atmosphere.
* Units using additional extension collars must use adapter lid and/or extension collars included
with unit.
TSS-95-ECA
Solids Separator
ECA-TSS-18
Extension Collar

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 18
A THERMACO® Technology
Section III: TSS Installation
In-Ground Installation
When installing multiple Trapzilla units in series, the change in elevation from the
inlet to the outlet of a unit requires each preceeding unit to be installed 1” higher
than the unit after it.
In-Ground Installations inside of a building must have a vessel vent installed
and piped to atmosphere.
* Units using additional extension collars must use adapter lid and/or extension collars included
with unit.
TZ-600 TSS-95

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 19
A THERMACO® Technology
Section III: TSS Installation
Trimming and Setting the ECA-TSS-18 Single-Piece Extension Collar
In-Ground Trapzilla Models ship with a
built-in, single-piece, 18” extension col-
lar that must be trimmed and then set to
the correct height to bring the Solid Top
Cover to grade.
Follow the steps below to set the exten-
sion collar prior to backlling the hole
with concrete.
In-Ground Installation
Amount of extension collar needed to bring
Solid Top Cover to grade.
Step 2: Remove the extension collar adapter ring from
the unit with the extension collar still in place. On the
underside of the cover, mark the excess extension col-
lar length at the bottom of the four (4) “skirt” portions
of the adapter ring. Check the extension collar height
dimension frequently during this marking to ensure that
the collar has not moved. Extend this mark between the
gaps in the “skirt” so that the collar is marked all around.
Step 1: With the Trapzilla unit installed in its perma-
nent location, raise the telescoping extension collar to
nished grade or oor level. Measure the height from
the top of the unit to this nished extension collar height
and record this dimension.
Note: If the oor will have a tile covering alow for the tile
thickness when determining the extension collar height.
8.25"
Extension collar
Skirt
Mark excess extension collar length
at the four (4) "skirt" portions of
the adapter ring.
8.25

©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651 MNL-TSS 20
A THERMACO® Technology
Section III: TSS Installation
In-Ground Installation
Step 5: Working from the bottom of the assembly, in-
stall eight (8) self-drilling, self-tapping screws (provided)
through the extension collar wall and into the adapter
ring. Two of these screws should be installed in each
of the four (4) skirt areas of the adapter ring. Check
the extension collar height dimension frequently during
this operation to ensure that the collar has not moved.
Note: Use caution when tightening these screws to en-
sure that they do not strip.
Step 6: Place the adapter ring/extension collar assem-
bly onto the Trapzilla unit. Position the small cover onto
the extension collar. Secure the adapter ring and the
small cover with the brass nuts and at washers provid-
ed. Seal the gap between the 18” extension collar and
extension collar adapter ring using a silicone sealant.
Step 3: Remove the extension collar from the adapter
ring and, with an appropriate saw, cut along the line cre-
ated in Step 2 to remove the excessive extension collar.
Step 4: Reinsert the extension collar into the adapter
ring ensuring that the cover alignment key on the ex-
tension collar is aligned with its recess in the adapter
ring. Reset the extension collar height to the dimension
determined in Step 1.
Line marking the bottom
of the "skirt" (adapter
ring has
been removed
for clarity)
Excess part of
extension collar
to be discarded
after cutting
along line
Reinsert extension collar into adapter
ring to insure alignment.
Adapter ring
Extension collar
Modified extension collar
Self-tapping screws
8 Places
Adapter ring
"Skirt"
5/16-inch Hex Nut
4 Places
5/16-inch Washer
4 Places
Note: Tighten down the flat
washers and brass nuts using
a 5/16-inch socket and rachet.
Do not over tighten.
This manual suits for next models
8
Table of contents
Popular Water Filtration System manuals by other brands

Vivaria
Vivaria VarioPress 8000 operating instructions

Steinbach
Steinbach 040050 instruction manual

Kessel
Kessel Ecolift L Series Installation and operating instructions

Hayward
Hayward S244SV owner's manual

Parker
Parker Balston SR Series Installation, operation and maintenance manual

Behringer
Behringer 904B quick start guide

B.David
B.David 9333 Instructions and operating manual

Winterhalter
Winterhalter Gastronom RoMatik 150 installation instructions

Oase
Oase BioMaster 250 operating instructions

Bestway
Bestway 58497 owner's manual

Newa Pond
Newa Pond PURE LIGHT UV-C 7 Instructions and guarantee

Zehnder Rittling
Zehnder Rittling ComfoAir Standard 300 Installer manual