TriangleTube CTRLMax Prestige Series Owner's manual

DHW Demand
DHW
Instinct
DHW Demand
DHW
Instinct
This document is intended to be used
by a factory trained and qualified
heating contractor or service technician
only. Read all Instructions within this
document and within the relevant Boiler
Installation and Maintenance Manual
before proceeding. It is recommended
to follow the procedures in the steps
given. Skipping or missing procedural
steps could result in substantial property
damage, serious injury, or death.
WARNING
THE
ORIGINAL
INNOVATORS
SOLO 80, 110, 155, 175, 250, 299, 399 &
EXCELLENCE 110
TC 240299
SOLO 110155199 & COMBI 155199
CTRLMax
Supplement
222171 A01 - July 2019
2019-15
CTRLMax_w Instinct_UK version_222171_A01.indd 1 18/07/2019 18:37

INTENTIONALLY LEFT BLANK
CTRLMax_w Instinct_UK version_222171_A01.indd 2 18/07/2019 18:37

iii
TABLE OF CONTENTS
CHAPTER 1 - OPERATING INFORMATION ......................................................................... 1
1.1. General............................................................................................................................................. 1
1.1.1 PRESTIGE and HEATMASTER Control Panel Description ................................................. 1
1.1.2 Main settings of the PRESTIGE and HEATMASTER CTRLMax Display ............................ 1
1.1.3 INSTINCT Control Panel Description...................................................................................2
1.1.4 Main settings of INSTINCT CTRLMax Display ....................................................................3
1.1.5 Main Icons of CTRLMax display ...........................................................................................3
1.2. Installer Access Code .....................................................................................................................3
1.3. CTRLMax Installer Menu Structure ...............................................................................................4
CHAPTER 2 - CH SETTINGS ...............................................................................................5
2.1. Heating Operation...........................................................................................................................5
2.2. Demand Type ..................................................................................................................................5
2.3. CH Maximum Capacity...................................................................................................................6
2.4. CH Minimum Capacity....................................................................................................................7
2.5. Abs. max. CH setpoint ....................................................................................................................7
2.6. CH1 max. setpoint ...........................................................................................................................7
2.7. CH1 min. setpoint............................................................................................................................7
2.8. Outd. Curve Coldest Day................................................................................................................8
2.9. Outd. Curve Warmest Day..............................................................................................................8
2.10. CH2 circuit .......................................................................................................................................8
2.11. CH2 max. setpoint ..........................................................................................................................8
2.12. CH2 min. setpoint ...........................................................................................................................9
2.13. Warm Weather Shutdown ..............................................................................................................9
2.14. Circulation Pump Permanent.........................................................................................................9
2.15. CH Post Pump Time........................................................................................................................9
2.16. Freeze Protection ..........................................................................................................................10
2.17. Frost Protection Setpoint .............................................................................................................10
2.18. Parallel Shift Value .........................................................................................................................11
2.19. CH Call Blocking.............................................................................................................................11
2.20. Appliance Min CH Setpoint ...........................................................................................................11
CHAPTER 3 - DHW SETTINGS (PRESTIGE, HEATMASTER AND INSTINCT SOLO).... 13
3.1. DHW Operation .............................................................................................................................13
3.2. Demand Type ................................................................................................................................13
3.3. DHW Maximum Capacity ............................................................................................................. 14
3.4. DHW Boiler Setpoint..................................................................................................................... 14
CTRLMax_w Instinct_UK version_222171_A01.indd 3 18/07/2019 18:37

iv
TABLE OF CONTENTS
3.5. DHW Setpoint................................................................................................................................ 14
3.6. DHW on Differential ...................................................................................................................... 14
3.7. DHW Storage Adder ..................................................................................................................... 15
3.8. DHW Post Pump Time .................................................................................................................. 15
3.9. DHW Priority Timeout .................................................................................................................. 15
3.10. DHW Priority.................................................................................................................................. 15
3.11. DHW Call Blocking ........................................................................................................................16
3.12. DHW to CH Call Blocking.............................................................................................................. 16
3.13. Antilegionella Function ................................................................................................................. 17
3.14. DHW Ramp Up .............................................................................................................................. 17
CHAPTER 4 - DHW SETTINGS (INSTINCT COMBI ONLY)............................................. 19
4.1. DHW Operation .............................................................................................................................19
4.2. DHW MAximum Capacity.............................................................................................................19
4.3. DHW Temp.....................................................................................................................................19
4.4. DHW On Differential..................................................................................................................... 20
4.5. DHW Warmstart Temperature.................................................................................................... 20
4.6. DHW Warmstart Hysteresis........................................................................................................ 20
4.7. DHW Post Pump Time ................................................................................................................. 20
4.8. DHW Priority Timeout .................................................................................................................. 21
4.9. DHW Call Blocking ........................................................................................................................ 21
4.10. DHW to CH Call Blocking.............................................................................................................. 21
4.11. DHW Ramp Up .............................................................................................................................. 21
CHAPTER 5 - BOILER SETTINGS......................................................................................23
5.1. Model ............................................................................................................................................ 23
5.2. Lockout Temp............................................................................................................................... 23
5.3. Modbus Address .......................................................................................................................... 23
5.4. Pump Settings.............................................................................................................................. 24
5.4.1 Preset Pump Config ............................................................................................................24
5.4.2 Flexible Pump Config ..........................................................................................................24
5.4.3 Error Relay........................................................................................................................... 26
5.5. Ignition Level................................................................................................................................. 26
5.6. Mix zone high limit.........................................................................................................................27
5.7. WP Diff Trigger ..............................................................................................................................27
5.8. Appliance Setting..........................................................................................................................27
5.9. Altitude.......................................................................................................................................... 28
CTRLMax_w Instinct_UK version_222171_A01.indd 4 18/07/2019 18:37

v
TABLE OF CONTENTS
CHAPTER 6 - MANUAL OPERATION ................................................................................ 51
CHAPTER 7 - RESET ALL SETTINGS................................................................................53
7.1. Factory CTRLMax Settings ......................................................................................................... 53
CHAPTER 8 - CASCADE.....................................................................................................55
8.1. Operating Principles of an CTRLMax-Controlled Cascade (Prestige and INSTINCT only).... 55
8.2. Cascade Algorithm ...................................................................................................................... 55
8.2.1 Boiler Enabling Algorithm ...................................................................................................55
8.2.2 Boiler Disabling Algorithm..................................................................................................55
8.3. CTRLMax Cascade menu structure ........................................................................................... 56
8.4. Cascade Installation .................................................................................................................... 56
8.4.1 System Piping ..................................................................................................................... 56
8.4.2 System Sensor Installation................................................................................................ 56
8.4.3 Cascade Communication Cable.........................................................................................57
8.4.4 Low Voltage Wiring Connections .......................................................................................57
8.4.5 Line Voltage Wiring Connections ...................................................................................... 58
8.4.6 Cascade Autodetection ..................................................................................................... 58
8.4.7 Lockouts.............................................................................................................................. 58
8.5. Cascade Autodetection ............................................................................................................... 59
8.6. Cascade Info................................................................................................................................. 60
8.6.1 Cascade Role ...................................................................................................................... 60
8.6.2 System Temp. ..................................................................................................................... 60
8.6.3 Active Boilers ...................................................................................................................... 60
8.6.4 Total Boilers ........................................................................................................................ 60
8.6.5 Cascade Firing Ratio .......................................................................................................... 60
8.7. Cascade Settings .......................................................................................................................... 61
8.7.1 Stage Delay .......................................................................................................................... 61
8.7.2 Min. Firing Rate................................................................................................................... 62
8.7.3 Max. Firing Rate .................................................................................................................. 62
8.7.4 CH / DHW Boilers............................................................................................................... 62
8.7.5 Auto Rotation...................................................................................................................... 64
8.7.6 CH Prop. Gain...................................................................................................................... 64
8.7.7 CH Integral Gain.................................................................................................................. 65
8.7.8 DHW Prop. Gain .................................................................................................................. 66
8.7.9 DHW Integral Gain .............................................................................................................. 66
CHAPTER 9 - MODBUS INTERFACE................................................................................. 73
CTRLMax_w Instinct_UK version_222171_A01.indd 5 18/07/2019 18:37

vi
TABLE OF ILLUSTRATIONS
Fig. 1 - PRESTIGE and HEATMASTER Control Panel ............................................................................... 1
Fig. 2 - INSTINCT Control Panel ................................................................................................................2
Fig. 3 - System Piping with Solo Preset Config. 1 ................................................................................. 29
Fig. 4 - System Pipingwith Solo Preset Config. 2 ................................................................................. 30
Fig. 5 - System Piping with Solo Preset Config. 3.................................................................................. 31
Fig. 6 - System Piping with Solo Preset Config. 4................................................................................. 32
Fig. 7 - System Piping with Solo Preset Config.5.................................................................................. 33
Fig. 8 - System Piping with Solo Preset Config. 6 ................................................................................ 34
Fig. 9 - System Piping with Solo Preset Config. 7................................................................................. 35
Fig. 10 - System Piping with Solo Preset Config. 8............................................................................... 36
Fig. 11 - System Piping with Solo Preset Config. 9 ................................................................................37
Fig. 12 - System Piping with Solo Preset Config. 13 ............................................................................. 38
Fig. 13 - System Piping with Excellence Preset Config. 1 ..................................................................... 39
Fig. 14 - System Piping with Excellence Preset Config. 2 .................................................................... 40
Fig. 15 - System Piping with Excellence Preset Config. 3 ..................................................................... 41
Fig. 16 - System Piping with Excellence Preset Config. 4 .................................................................... 42
Fig. 17 - INSTINCT Solo System Piping - Multi Zone System with Single System/Boiler Circulator 43
Fig. 18 - INSTINCT Solo System Piping - Indirect Water Heater installation...................................... 44
Fig. 19 - INSTINCT Combi System Piping - Zoning w Valves ............................................................... 45
Fig. 20 -INSTINCT Combi - System Piping - Multi Zone Valve - Single Circulator ............................. 46
Fig. 21 - INSTINCT Combi - System Piping - Single Zone with Single Circulator .................................47
Fig. 22 - INSTINCT Combi System Piping - Single Zone System with Single System/Boiler Circulator.........48
Fig. 23 - INSTINCT Combi System Piping - Domestic piping - Storage tank installation.................. 49
Fig. 24 - System Sensor Direct Immersion.............................................................................................57
Fig. 25 - System Sensor Dry well Installation .........................................................................................57
Fig. 26 - Lockouts in a cascade.............................................................................................................. 58
Fig. 27 - Primary Secondary Cascade Piping ........................................................................................67
Fig. 28 - Primary Secondary Cascade Wiring....................................................................................... 68
Fig. 29 - Reverse Return Cascade Piping.............................................................................................. 69
Fig. 30 -Reverse Return Cascade Wiring .............................................................................................. 70
Fig. 31 - Split Cascade System ............................................................................................................... 71
Fig. 32 - Split Cascade Wiring .................................................................................................................72
CTRLMax_w Instinct_UK version_222171_A01.indd 6 18/07/2019 18:37

vii
SAFETY
PRODUCT AND SAFETY INFORMATION
Triangle Tube accepts no liability for any damage,
injury, or loss of life resulting from incorrect
installation, alteration of any factory supplied
parts, or the use of parts or ttings not specied by
Triangle Tube. If there is a conict or doubt about the
proper installation of the unit or any factory supplied
replacement parts please contact Triangle Tube
Technical Support.
DEFINITIONS
The following terms are used throughout this manual
to bring attention to the presence of potential hazards
or to important information concerning the product.
Indicates the presence of a hazardous situa-
tion which, if ignored, will result in substantial
property damage, serious injury, or death.
Indicates a potentially hazardous situation
which, if ignored, can result in substantial
property damage, serious injury, or death.
Indicates a potentially hazardous situation
which, if ignored, can result in minor property
damage, or injury.
Indicates special instructions on installation,
operation or maintenance, which are import-
ant to the equipment but not related to person-
al injury hazards.
Indicates recommendations made by Triangle
Tube for the installers, which will help to ensure
optimum operation and longevity of the equip-
ment.
DANGER
WARNING
CAUTION
NOTICE
BEST PRACTICE
This document is intended to be used by a
factory trained and qualified heating con-
tractor or service technician only. Read all
instructions within this document and within
the relevant Boiler Installation and Mainte-
nance Manual before proceeding. It is recom-
mended to follow the procedures in the steps
given. Skipping or missing procedural steps
could result in substantial property damage,
serious injury, or death.
This Control Application Supplement applies to
CTRLMax controls with the following software
version numbers:
PRESTIGE and HEATMASTER TC:
Display SW v.4.03 & v.4.04
Burner Controller SW v.0.53 & v.0.54
INSTINCT:
Display SW v.0.23 and up
Burner Controller SW v.0.54
The software version numbers are displayed on
the initial screen after turning on the unit.
NOTICE
IMPORTANT SAFETY INFORMATION
WARNING
CTRLMax_w Instinct_UK version_222171_A01.indd 7 18/07/2019 18:37

INTENTIONALLY LEFT BLANK
CTRLMax_w Instinct_UK version_222171_A01.indd 8 18/07/2019 18:37

1
CHAPTER 1
CHAPTER 1 - OPERATING INFORMATION
1.1. General
The ControlMax (CTRLMax) system control is designed
to be exible yet easy to use. It monitors and controls
the boiler to operate as eciently as possible. CTRLMax
monitors the appliance supply, return and ue gas tem-
peratures and operates the ignitor, gas valve and blow-
er. It uses this information to modulate the appliance
ring rate to maintain the required setpoint. CTRLMax
oers many advanced control options, which may be
adjusted for various applications to achieve optimum
appliance eciency and operation:
• Two central / space heating (CH) call inputs with
separate outdoor curves.
• A Domestic Hot Water (DHW) call input with op-
tional priority.
• System temperature sensing and control with an
optional system temperature sensor.
• A cascade function (Prestige and Instinct Solo appli-
ances only). It allows, for example, up to six boilers
to operate together in a single heating system.
• A Modbus interface for integrating with building
management systems.
Accessing the functions is done through the user inter-
face, that presents itself in two dierent versions:
1.1.1 PRESTIGE and HEATMASTER Control Panel
Description
1. CTRLMax LCD Display - It is the setup interface of
the appliance and indicates the parameter values, the
error codes and the set-up status of the parameters. It
displays a series of screens, each showing information
and/or icons.
2. Installer button - Allows the installer to open the ac-
cess code window of the CTRLMax controller and set
up the system once the code has been entered.
3. Arrow keys and OK key - To browse through
the screens of the CTRLMax controller, set up
the appliance, increase and decrease the dis-
played values and validate the selections.
The OK key is also used to RESET the appliance after
a blocking (following the instructions on the screen).
1.1.2 Main settings of the PRESTIGE and HEAT
MASTER CTRLMax Display
Screen backlight - it will illuminate when any key is
depressed, and remain illuminated for ve minutes.
Screen contrast - it can be adjusted at the Home screen
by pressing and holding the OK key, then pressing and
holding the LEFT key along with the OK key. Press the
UP and DOWN key to increase or decrease the contrast
while holding the OK and LEFT keys depressed. All keys
must be released and the procedure performed again
to switch between increasing and decreasing contrast.
Fig. 1 - PRESTIGE and HEATMASTER Control Panel
1 2 3
CTRLMax_w Instinct_UK version_222171_A01.indd 1 18/07/2019 18:38

2
CHAPTER 1
CHAPTER 1 - OPERATING INFORMATION
1.1.3 INSTINCT Control Panel Description
1. CTRLMax LCD Display - It is the setup interface of
the appliance and indicates the parameter values, the
error codes and the set-up status of the parameters. It
displays a series of screens, each showing information
and/or icons.
2. Installer function - By touching simultaneously the
up and down arrow keys for 3 seconds, the installer
can open the access code window of the CTRLMax
controller and set up the system once the code has
been lled in.
3. Arrow soft keys and OK/Reset key - To browse
through the screens and menus of the CTRLMax con-
troller, set up the appliance, increase and decrease the
displayed values and validate the selections. The OK/
Reset key is also used to RESET the appliance after a
blocking (following the instructions on the screen).
4. On-O soft key - To shut down the unit.
When touching the soft key, the unit shuts
down but is not isolated from power supply.
Therefore, live current is still present in the
unit. For your safety, disconnect electrical
power supply to the unit before servicing or
making any electrical connections to avoid
possible electric shock hazard. Failure to do
so can cause serious injury, or death.
DANGER
DHW Demand
DHW
Instinct
DHW Demand
DHW
Instinct
Fig. 2 - INSTINCT Control Panel
• When shutting down using the soft key,
the appliance will not react to any heat de-
mand. However, the basic appliance pro-
tection functions (such as frost protection,
etc.) remain active.
• In addition, the arrow soft keys are no lon-
ger illuminated, and the soft key light-
ing is dimmed.
The CTRLMax navigation is performed through soft keys
that react to the touch and emit a short beep when tapped.
Exert a light and short touch (tap) on the soft
keys to activate their function. Holding the
touch too long will not generate any reaction
from the CTRLMax, unless it is a combination of
soft keys meant to be touched simultaneously
for a determined duration, as instructed in this
manual. The arrow keys can also be held longer
to increase or decrease values faster.
Navigation through the menus and selection of items/
modication of values is performed through four arrow
soft keys , , , . The center soft key is used
for validation (and for Reset in some cases).
The installer is provided with full access to all available
features after simultaneously touching the and
soft keys for 3 seconds and entering a code.
NOTICE
NOTICE
1 2 3 4
CTRLMax_w Instinct_UK version_222171_A01.indd 2 18/07/2019 18:38

3
CHAPTER 1
CHAPTER 1 - OPERATING INFORMATION
The Main Menu (EZSetup, no code required) can be ac-
cessed from the Home Screen by touching the center
soft key . More information can be found in the In-
stallation manual of the INSTINCT units.
To shut down the unit, touch the soft key.
When touching the soft key, the unit shuts
down but is not isolated from power supply.
Therefore, live current is still present in the
unit. For your safety, disconnect electrical
power supply to the unit before servicing or
making any electrical connections to avoid
possible electric shock hazard. Failure to do
so can cause serious injury, or death.
• When shutting down using the soft key,
the appliance will not react to any heat de-
mand. However, the basic appliance protec-
tion functions (such as frost protection, etc.)
remain active.
• In addition, the arrow soft keys are no lon-
ger illuminated, and the soft key light-
ing is dimmed.
1.1.4 Main settings of INSTINCT CTRLMax Dis-
play
The Home Screen presents status information in a very
user friendly way so that the current state of the boiler
can be quickly accessed.
• Screen backlight - it will illuminate when any soft
key is touched, and remain illuminated for ve min-
utes.
• Screen brightness - it can be adjusted at the
Home screen by touching and holding simultane-
ously the and soft keys for 2 seconds. Touch
the and soft key to increase or decrease the
contrast. Touch to end the process.
DANGER
NOTICE
1.1.5 Main Icons of CTRLMax display
Central Heating - indicates information related
to the CH circuit.
DHW - indicates information related to the Do-
mestic Hot Water circuit.
Home - to go back to the main menu screen.
Back - to go back to the previous screen.
Pump - indicates a pump is operating.
Warm weather shutdown - displays on the home
screen when the outdoor temperature reaches the
Warm Weather Shutdown preset temperature.
1.2. Installer Access Code
By pushing the installer button (PRESTIGE/HEATMAS
TER TC), or touching simultaneously the and
soft keys for 3 seconds (INSTINCT), the access code
window opens, where the installer can enter the spe-
cic code “054”. Subsequently, the installer can access
various setup screens and menus, allowing to dene a
large set of parameters and adapt the operation of the
CTRLMax to the system conguration.
To navigate on the screen, use the UP, DOWN, LEFT
and RIGHT keys, then the OK key to validate a selection.
To increase/decrease values, use the UP and DOWN or
LEFT and RIGHT keys, according to the situation and
validate with OK.
Entering the installer access code allows the in-
staller to make adjustments for 30 minutes. Af-
ter 30 minutes, the access code will need to be
entered again to make any adjustments.
If the end user misuses the installer code to ac-
cess installer-specific parameters and makes
changes that cause a system failure, any war-
ranty claim will be void.
NOTICE
CTRLMax_w Instinct_UK version_222171_A01.indd 3 18/07/2019 18:38

4
CHAPTER 1
CHAPTER 1 - OPERATING INFORMATION
1.3. CTRLMax Installer Menu Structure
The Installer Menu is divided into four sections
CH & DHW Settings – Allows the installer to adjust
the appliances central/space heating and domestic hot
water settings for the application.
Boiler Protection
P3
DHW
P4
183°F
141°F
1
2
CH
Target = 188°F
Prestige Solo ENTER ACCESS CODE
05[4]
CH Settings
CH & DHW Settings
Reset All Settings
Press OK to restore factory settings,
any other button to keep current
settings.
Cascade Info.
?
Manual Operation
FAN
CH1
CH2
DHW
Released
O
O
O
Select a position using the
LEFT and RIGHT keys, and
increase or decrease the
digit value using the UP
and DOWN keys. Then the
OK key to validate.
CH & DHW Settings
Reset All Settings Cascade
Manual Operation
PRESTIGE / HEATMASTER
1x
J
INSTINCT
J
J
3 Sec.
OR
Manual Operation – The burner and circulators can
be manually enabled for testing.
Cascade – Allows the installer to setup, adjust and
monitor the Cascade System.
Reset All Settings – Resets all CH, DHW, and Cas-
cade Settings back to the default settings
CTRLMax_w Instinct_UK version_222171_A01.indd 4 18/07/2019 18:38

5
CHAPTER 2
CHAPTER 2 - CH SETTINGS
CH Settings
Heating Settings
Heating Operation Enabled
Demand Thermostat & Outd. Curve
CH maximum capacity 100%
CH minimum capacity 0%
Abs. Max. CH Setpoint 186°F
CH1 Max. Setpoint 180°F
Heating Operation
Disabled
Enabled
Heating Settings
Heating Operation Enabled
Demand Thermostat & Outd. Curve
CH maximum capacity 100%
CH minimum capacity 0%
Abs. Max. CH Setpoint 186°F
CH1 Max. Setpoint 180°F
Demand Type
Thermostat & Outd. Curve
Thermostat & Setpoint
Constant & Outdoor Curve
Constant & Setpoint
0-10 V Modulation Signal
Navigate on the screen using the UP, DOWN, LEFT and RIGHT keys, then
the validate a selection with the OK key. To increase/decrease values, use
the UP and DOWN or LEFT and RIGHT keys, according to the situation and
validate with OK.
NOTICE
CH & DHW Settings
Installer Code
Heating Operation allows the central heating function to be
enabled and disabled.
Select Enabled or Disabled using the UP or DOWN keys, then
store the setting with the OK key.
Enabled - The Appliance will respond to a central heating call.
Disabled - The Appliance will not respond to a central heating call.
The heating operation disabled icon ( ) is displayed
on the home screen when central heating operation
has been disabled.
When heating is disabled the frost protection will
still be active.
Default: Enabled
NOTICE
Demand Type allows the installer to select how a CH Demand
is generated.
Select the CH Demand Type using the UP or DOWN keys, then
store the setting with the OK key.
Default: Thermostat and Outd. Curve
See detail of menu on next page.
CTRLMax_w Instinct_UK version_222171_A01.indd 5 18/07/2019 18:38

6
CHAPTER 2
CHAPTER 2 - CH SETTINGS
Demand Type screen menu
Thermostat & Outdoor Curve – A central heating call from a dry contact
switch will enable the appliance and the setpoint will vary with the outdoor
temperature for central heating calls.
Thermostat & Setpoint - A central heating call from a dry contact switch will
enable the appliance and the setpoint will be xed for central heating calls.
Constant & Outd. Curve - The appliance will maintain setpoint and the central
heating circulators will be constantly enabled without an external call from a
dry contact switch. The central heating circulators will be disabled when the
outdoor temperature exceeds the Warm Weather Shutdown Temperature set-
ting. The setpoint will vary with the outdoor temperature for central heating
calls.
Constant & Setpoint - The appliance will maintain setpoint and the central
heating circulators will be constantly enabled without an external call from a
dry contact switch. The central heating circulators will be disabled when the
outdoor temperature exceeds the Warm Weather Shutdown Temperature set-
ting. The setpoint will be xed for central heating calls.
0 - 10V Modulation Signal - This option allows the appliance ring rate to be
controlled by an external control system with a 0-10 VDC signal. Based on the
control input voltage, the appliance will start to operate for heat demand. The
CH temperature is limited by the Absolute maximum temperature.
• 0 – 2V appliance is o.
• 2 – 10 V linear power increase from minimum to maximum output.
• 10 – 2 V linear power decrease from maximum to minimum output.
• 2 – 1 V appliance on minimum capacity.
• 1 - 0 V appliance o.
CH Settings
Heating Settings
Heating Operation Enabled
Demand Thermostat & Outd. Curve
CH maximum capacity 100%
CH minimum capacity 0%
Abs. Max. CH Setpoint 186°F
CH1 Max. Setpoint 180°F
Demand Type
Thermostat & Outd. Curve
Thermostat & Setpoint
Constant & Outdoor Curve
Constant & Setpoint
0-10 V Modulation Signal
CH Settings
Heating Settings
Heating Operation Enabled
Demand Thermostat & Outd. Curve
CH maximum capacity 100%
CH minimum capacity 0%
Abs. Max. CH Setpoint 186°F
CH1 Max. Setpoint 180°F
CH Maximum Capacity
100%
0% 100%
CH Maximum Capacity limits the maximum CH capacity.
The appliance capacity can be dened by adjusting this value,
100% means Maximum CH output, 0% means minimum CH
output. It is therefore possible to adjust the CH capacity to the
installation needs.
Example: when set to 60%, the real appliance capacity is the
appliance minimum capacity plus 60% of the dierence be-
tween the maximum and minimum capacity.
Adjust the CH Maximum Capacity value using the LEFT or
RIGHT keys to then store the setting with the OK key.
Default: 100%
CTRLMax_w Instinct_UK version_222171_A01.indd 6 18/07/2019 18:38

7
CHAPTER 2
CHAPTER 2 - CH SETTINGS
CH Settings
Heating Settings
Heating Operation Enabled
Demand Thermostat & Outd. Curve
CH maximum capacity 100%
CH minimum capacity 0%
Abs. Max. CH Setpoint 186°F
CH1 Max. Setpoint 180°F
CH Minimum Capacity
0%
0% 100%
Heating Settings
Heating Operation Enabled
Demand Thermostat & Outd. Curve
CH Maximum Capacity 100%
CH Minimum Capacity 0%
Abs. Max CH Setpoint 186°F
CH1 Max. Setpoint 180°F
Abs. Max
CH Setpoint
186°F
68°F 188°F
Heating Settings
Demand Thermostat & Outd. Curve
CH Maximum Capacity 100%
CH Minimum Capacity 0%
Abs. Max CH Setpoint 188°F
CH1 Max. Setpoint 180°F
CH1 Min. Setpoint 80°F
CH1 Max.
Setpoint
180°F
68°F 188°F
Heating Settings
Demand Thermostat & Outd. Curve
CH Maximum Capacity 100%
CH Minimum Capacity 0%
Abs. Max CH Setpoint 186°F
CH1 Max. Setpoint 180°F
CH1 Min. Setpoint 80°F
CH1 Min.
Setpoint
80°F
60°F 188°F
CH Minimum Capacity sets the lowest limit of the CH capac-
ity. The appliance capacity can be dened by adjusting this
value and the CH Maximum capacity. It is therefore possible to
adjust the CH capacity to the installation needs.
Example: when the CH minimum capacity is set to 20%, the
real appliance capacity is the appliance minimum capacity
plus 20% of the dierence between the maximum and mini-
mum capacity.
Adjust the CH Minimum Capacity using the LEFT or RIGHT
keys, then store the setting with the OK key.
Default: 0%
Absolute Max CH Setpoint limits the setpoint during a cen-
tral heating call.This setting can be used to prevent a user from
adjusting the central heating setpoint or outdoor curve above
a safe operating temperature in the EZ Setup Menu. A warn-
ing screen will be displayed in EZ Setup if the user attempts to
raise the setpoint above the Absolute Max CH Setpoint. The
Absolute Max CH Setpoint will be displayed on the outdoor
curve in EZ Setup if the user selects an outdoor curve which
goes above the Absolute Max CH Setpoint.
Adjust the Absolute Max CH Setpoint using the LEFT or RIGHT
keys to then store the setting with the OK key.
Default: 186°F
CH1 Max. Setpoint is the maximum setpoint for a CH1
heating call when an Outdoor Curve option is chosen in
Demand Type. CH1 Maximum Setpoint is the xed setpoint
for a CH1 heating call when a Setpoint option is chosen in
Demand Type.
Adjust the CH1 Maximum Setpoint value using the LEFT or
RIGHT keys, then store the setting with the OK key.
Default: 180°F
CH1 Min. Setpoint is the minimum setpoint for a CH1
heating call when an Outdoor Curve option is chosen in
Demand Type. This setting is not applicable when a Set-
point option is chosen in Demand Type.
CH1 Min. Setpoint must be set equal or below the CH1
max. setpoint.
Adjust the CH1 Minimum Setpoint value using the LEFT or
RIGHT keys, then store the setting with the OK key.
Default: 80°F
CTRLMax_w Instinct_UK version_222171_A01.indd 7 18/07/2019 18:38

8
CHAPTER 2
CHAPTER 2 - CH SETTINGS
CH Settings
Heating Settings
CH Maximum Capacity 100%
CH Minimum Capacity 0%
Abs. Max CH Setpoint 186°F
CH1 Max. Setpoint 180°F
CH1 Min. Setpoint 80°F
Outdoor Curve Coldest Day 10°F
Outdoor Curve
Coldest Day
10°F
-30°F 50°F
Heating Settings
CH Minimum Capacity 0%
Abs. Max. CH Setpoint 186°F
CH1 Max. Setpoint 180°F
CH1 Min. Setpoint 80°F
Outdoor Curve Coldest Day 10°F
Outdoor Curve Warmest Day 64°F
Outdoor Curve
Warmest Day
64°F
60°F 78°F
Heating Settings
Abs. Max CH Setpoint 186°F
CH1 Max. Setpoint 180°F
CH1 Min. Setpoint 80°F
Outdoor Curve Coldest Day 10°F
Outdoor Curve Warmest Day 64°F
CH2 Circuit Enabled
CH2 Circuit
Disabled
Enabled
Heating Settings
CH1 Max. Setpoint 180°F
CH1 Min. Setpoint 80°F
Outdoor Curve Coldest Day 10°F
Outdoor Curve Warmest Day 64°F
CH2 Circuit Enabled
CH2 Max. Setpoint 140°F
CH2 Max.
Setpoint
140°F
68°F 188°F
Outdoor Curve Coldest Day is the coldest outdoor design
temperature of the heating system when an Outdoor Curve
option is chosen in Demand Type. This setting is not applicable
when a Setpoint option is chosen in Demand Type.
Adjust the Outdoor Curve Coldest Day value using the LEFT
or RIGHT keys, then store the setting with the OK key.
Default: 10°F
Outdoor CurveWarmest Day is the warmest outdoor design
temperature of the heating system when an Outdoor Curve
option is chosen in Demand Type. This setting is not applicable
when a Setpoint option is chosen in Demand Type.
Adjust the Outdoor Curve Warmest Day value using the
LEFT or RIGHT keys, then store the setting with the OK key.
Default: 64°F
CH2 Circuit allows the CH2 Max and Min setpoints to be
enabled and disabled. When disabled, the boiler will not
respond to a CH2 heating call.
Select Enabled or Disabled using the UP or DOWN keys,
then store the setting with the OK key.
Enabled – The appliance will respond to a CH2 heating call
using CH2 max and min setpoints.
Disabled – The appliance will not respond to a CH2 heat-
ing call using CH2 max and min setpoints.
Default: Enabled
CH2 Maximum Setpoint is the maximum setpoint for a
CH2 heating call when an Outdoor Curve option is chosen
in Demand Type. CH2 Maximum Setpoint is the xed set-
point for a CH2 heating call when a Setpoint option is cho-
sen in Demand Type.
Adjust the CH2 Maximum Setpoint value using the LEFT or
RIGHT keys, then store the setting with the OK key.
Default: 140°F
The temperatures of Outdoor Curve Coldest
Day and Outdoor Curve Warmest Day are iden-
tical to those of CH1 and CH2.
NOTICE
CTRLMax_w Instinct_UK version_222171_A01.indd 8 18/07/2019 18:38

9
CHAPTER 2
CHAPTER 2 - CH SETTINGS
CH Settings
Heating Settings
CH1 Min. Setpoint 80°F
Outdoor Curve Coldest Day 10°F
Outdoor Curve Warmest Day 64°F
CH2 Circuit Enabled
CH2 Max. Setpoint 140°F
CH2 Min. Setpoint 80°F
CH2 Min.
Setpoint
80°F
60°F 190°F
Heating Settings
Outdoor Curve Coldest Day 10°F
Outdoor Curve Warmest Day 64°F
CH2 Circuit Enabled
CH2 Max. Setpoint 140°F
CH2 Min. Setpoint 80°F
Warm Weather Shutdown
O
Warm Weather Shutdown
O
O 78°F
Heating Settings
Outdoor Curve Warmest Day 64°F
CH2 Circuit Enabled
CH2 Max. Setpoint 140°F
CH2 Min. Setpoint 80°F
Warm Weather Shutdown
O
Circulation Pump Perman. Disabled
Circulation Pump
Permanent
Disabled
Enabled
Heating Settings
CH2 Circuit Enabled
CH2 Max. Setpoint 140°F
CH2 Min. Setpoint 80°F
Warm Weather Shutdown
O
Circulation Pump Perman. Disabled
CH Post Pump Time 5 min
CH Post
Pump Time
5 min
O 20 min
CH2 Minimum Setpoint is the minimum setpoint for a
CH2 heating call when an Outdoor Curve option is chosen
in Demand Type. This setting is not applicable when a Set-
point option is chosen in Demand Type.
Adjust the CH2 Minimum Setpoint value using the LEFT or
RIGHT keys, then store the setting with the OK key.
Default: 80°F
CH Post Pump Time sets how long the central heating
circulators will continue to operate at the completion of a
heating call. Any call during the CH Post Pump Time will be
ignored until the post pump has completed. The CH Post
Pump Time feature allows the heat remaining in the appli-
ance at the completion of a call to be sent to the heating
system, which will improve the overall eciency of the sys-
tem.
Adjust the CH Post Pump Time value using the LEFT or
RIGHT keys, then store the setting with the OK key.
Default: 5 min
Warm Weather Shutdown allows to enter an optional outdoor
temperature at which to disable the central heating function. The
Appliance will continue to respond to a domestic hot water call
or a 0- 10V Modulation Signal when the outdoor temperature ex-
ceeds the Warm Weather Shutdown Temperature setting.
Adjust the Warm Weather Shutdown Temperature value us-
ing the LEFT or RIGHT keys, then store the setting with the
OK key.
The Warm Weather Shutdown icon ( ) is displayed on the
home screen when the outdoor temperature reaches the
Warm Weather Shutdown Temperature.
Default: OFF.
Circulation Pump Permanent allows the central heating
circulators to be constantly enabled even without a central
heating call. A domestic hot water call will cause the circula-
tors to be disabled during the domestic call as long as DHW
Priority is enabled.
Select Enabled or Disabled using the UP or DOWN keys,
then store the setting with the OK key.
• Enabled – The central heating circulators will be enabled
for constant circulation without a central heating call.
• Disabled – The central heating circulators will only be
enabled during a central heating call.
Default: Disabled
CTRLMax_w Instinct_UK version_222171_A01.indd 9 18/07/2019 18:38

10
CHAPTER 2
CHAPTER 2 - CH SETTINGS
CH Settings
Heating Settings
CH2 Max. Setpoint 140°F
CH2 Min. Setpoint 80°F
Warm Weather Shutdown
O
Circulation Pump Perman. Disabled
CH Post Pump Time 5 min
Freeze Protection Enabled
Freeze Protection
Enabled
Disabled
Heating Settings
CH2 Min. Setpoint 80°F
Warm Weather Shutdown
O
Circulation Pump Perman. Disabled
CH Post Pump Time 5 min
Freeze Protection Enabled
Frost Protection Setpoint -22°F
Frost Protection
Setpoint
-22°F
-22°F 50°F
The Freeze Protection menu allows the feature to be enabled
and disabled. The built-in frost protection mechanism activates
the system pumps as soon as the ow temperature [NTC1
probe] drops below 46°F. As soon as the ow temperature is at
42°F, the burner starts up until the ow temperature rises above
60°F. The pumps continue to run for around 10 minutes.
Select Enabled or Disabled using the UP or DOWN keys,
then store the setting with the OK key.
• Enabled –The Freeze Protection feature protects the in-
stallation from freezing at a predetermined system ow
temperature.
• Disabled – The Freeze Protection feature is disabled.
Only the pumps operate.
Default: Enabled
Frost Protection Setpoint allows to dene the outside air
temperature at which the anti-freeze function is activated
(only available if an outdoor temperature sensor is connected).
The pumps are activated when the outside temperature drops
below the threshold dened in this menu.
Adjust the Frost Protection Setpoint using the LEFT or
RIGHT keys, then store the setting with the OK key.
In order to enable the protection of the whole
system against freezing, all the valves of the
radiators and the convectors should be com-
pletely open.
Default: -22°F
CAUTION
The appliance should NEVER be installed in
a location where freezing could occur. Sub-
jecting the appliance to freezing conditions
could lead to freezing of the condensate pos-
sibly causing serious injury or death.
Freeze Protection should only be disabled
when the system contains antifreeze to pre-
vent the system from freezing. Serious damage
could occur to the appliance as well as the en-
tire heating system if Freeze Protection is dis-
abled without antifreeze in the system.
WARNING
CAUTION
CTRLMax_w Instinct_UK version_222171_A01.indd 10 18/07/2019 18:38

11
CHAPTER 2
CH Settings
CHAPTER 2 - CH SETTINGS
Heating Settings
Warm Weather Shutdown
O
Circulation Pump Perman. Disabled
CH Post Pump Time 5 min
Freeze Protection Enabled
Frost Protection Setpoint -22°F
Parallel Shift 0°F
Parallel Shift Value
0°F
0°F 144°F
Heating Settings
Circulation Pump Perman. Disabled
CH Post Pump Time 5 min
Freeze Protection Enabled
Frost Protection Setpoint -22°F
Parallel Shift 0°F
CH Call Blocking 2 min
Heating Settings
CH Post Pump Time 5 min
Freeze Protection Enabled
Frost Protection Setpoint -22°F
Parallel Shift 0°F
CH Call Blocking 2 min
Appliance min CH setpoint 60°F
CH Call Blocking
2 min.
0 min. 30 min.
Appliance min. CH
Setpoint
60°F
60°F 188°F
Parallel Shift allows the CH setpoint to be externally adjusted
when a Constant option is chosen in Demand Type. When a
Constant option is chosen in Demand Type, continuous CH1
and CH2 heating calls are generated. Simultaneous CH1 and
CH2 calls will result in the Appliance operating at the highest
CH1 or CH2 setpoint. The CH1 or CH2 Thermostat terminals
with the highest setpoint will be used to adjust the setpoint. If
the Thermostat terminals with the highest setpoint are open,
the CH setpoint will decrease by the Parallel Shift Value. If the
Thermostat terminals with the highest setpoint are closed, the
CH setpoint will return to the highest CH1 or CH2 setpoint
Adjust the Parallel Shift Value using the LEFT or RIGHT keys,
then store the setting with the OK key.
Default: 0°F
CH Call Blocking sets the minimum time between burner
rings for central heating calls. At the completion of a burn-
er ring, the CH Call Blocking time will begin. The burner
will not re again until after the CH Call Blocking time has
elapsed. The CH Call Blocking time only prevents the burn-
er from ring, the central heating circulators will respond
to a central heating call. This blocking time has no aect
on domestic hot water calls. The CH Call Blocking feature
prevents short cycling of the burner and extends the life of
the burner components.
Adjust the CH Call Blocking value using the LEFT or RIGHT
keys, then store the setting with the OK key.
Default: 2 min.
Appliance min CH Setpoint - The minimum setpoint can
be reduced when the heating system is needing it to de-
frost installations.
Adjust the Appliance min. CH Setpoint using the LEFT or
RIGHT keys, then store the setting with the OK key.
Default: 60°F.
CTRLMax_w Instinct_UK version_222171_A01.indd 11 18/07/2019 18:38

INTENTIONALLY LEFT BLANK
CTRLMax_w Instinct_UK version_222171_A01.indd 12 18/07/2019 18:38
This manual suits for next models
18
Table of contents
Other TriangleTube Controllers manuals
Popular Controllers manuals by other brands

Sundaya
Sundaya Apple user manual

Bosch
Bosch Rexroth VT-VPCD Series operating instructions

Inovance
Inovance H0U Series user manual

Altronix
Altronix ACM4 Series installation guide

Galcon
Galcon AC 4 Installation and operating instructions

Morningstar
Morningstar EcoBoost MPPT EB-MPPT-20 Installation, operation and maintenance manual

WiXHC
WiXHC MACH4 MK-M4 Series manual

HEIDENHAIN
HEIDENHAIN ND 287 - GUIDE Quick reference guide

Weathermatic
Weathermatic smartline SL800 owner's manual

Zander Aachen
Zander Aachen ZX09 Series operating manual

Dresser
Dresser Surepowr Sure 150 installation manual

Spirax Sarco
Spirax Sarco MPC2 Installation and maintenance instructions