Trox BE-LCD User manual

Application
CONTROL PANEL TYPE
BE-LCD CONTROL PANEL
TEXT DISPLAY DISPLAY, FUNCTION
BUTTONS WITH STATUS
DISPLAY
BE-LCD
FOR EASYLAB FUME CUPBOARD CONTROLLERS OR
ROOM CONTROLLERS, WITH TEXT DISPLAY
Control panels to be used with fume cupboard controllers or room controllers, for
displaying operating values, activating functions and signalling operating states
Signalling of safety-related functions for fume cupboards according to
EN 14175 or of operating states for rooms
Display of actual values, setpoint values and status messages
Wireless communication with Bluetooth module
40-character text display
Push buttons for the operating mode default setting and for specific
functions
Project-specific range of functions with configurable push buttons
Integral service socket for configuration and diagnosis
Casing suitable for flush mounting to fume cupboard side frame, or for
surface mounting on a wall
Page d'accueil
>Produits >Unités de régulation >Débit variable >TROX UNIVERSAL >BE-LCD

Application
Control panels Type BE-LCD for displaying and operating the aerodynamic functions of fume cupboards or rooms
Display of actual values, setpoint values, and operating states either as text or on the status display
Optical and acoustic alarms
Operating mode default setting
Operation of lighting, automatic sash device or blinds without additional installation or wiring
Control panel for fume cupboard control
Status display to EN 14175
Connection to fume cupboard controller EASYLAB TCU3
Room control panel
Status display for the volume flow rate or differential pressure control of a room
Connection to room controller EASYLAB TCU3 or TAM with active room management function
Special characteristics
Large three-colour status display
Push buttons and functions can be configured individually
Easy to use – available function buttons are visible, unavailable function buttons are not visible
Excellent operating reliability as a result of continuous self monitoring of the communication between controller and control panel
Pluggable adapter which can provide four different viewing angles
Mounting on side frame or wall
Description
Parts and characteristics
40-character display, backlit (blue)
Three-colour status display (green, yellow, red) with text HIGH and LOW
Sash monitoring warning display
8 function button fields, can be individually activated
Alarm sounder
Connection socket for EASYLAB controller
Integral service socket for configuration and diagnosis of the controller
Wireless communication with Bluetooth module BlueCon
5 m connecting cable
Rectangular casing suitable for flush mounting or surface mounting
Useful additions
EasyConnect: Configuration software for the commissioning and diagnosis of EASYLAB components
Construction features
Casing with base plate and pluggable adapter to facilitate mounting
Adapter allows for mounting even on small side frames of fume cupboards
Pluggable adapter which can provide four different viewing angles: from the right, from the left, from top, from bottom
Pluggable connections
Materials and surfaces
Casing in ABS plastic
Casing: pearl light grey (RAL 9022)
Front plastic: anthracite grey (RAL 7016)
INFORMATION TECHNIQUE

Function, Technical data, Specification text, Order code, Related products
The BE-LCD control panel is used to display and control the most critical aerodynamic and safety-related functions of a fume cupboard or a room. Users
obtain information regarding the condition of the fume cupboard or room and can select among various operating modes. The individual display elements
and controls are as follows:
Three-colour status display
Warning display
40-character display
Alarm sounder
8 function button fields: 1 acoustic alarm acknowledgement, 3 operating mode buttons, 2 buttons for the automatic sash device, 1 button for the fume
cupboard lighting, 1 button for manual control
Service socket
The range of functions of the control panel can be adapted to project-specific requirements using the EasyConnect configuration software. The range of
functions may vary for different fume cupboards or rooms.
The function button fields are used for display and for operation. The available functions are highlighted in blue.
A required function can be selected by pressing the corresponding button.
Selecting an operating mode
Automatic sash device
Fume cupboard lighting on/off
The 40-character display shows system messages or, if enabled, actual values.
EASYLAB control panel BE-LCD
① 40-character display
② Alarm sounder

③ Sash monitoring warning display
④ Status display (green, yellow, red) with text HIGH and LOW
⑤ Connection socket for service and commissioning
⑥ Acoustic alarm acknowledgement
⑦ Manual control
⑧ Selection of operating mode
⑨ Lighting or other equipment (RMF)
⑩ Automatic sash device (FH), sun protection, e.g. blinds (RMF)
Base plate
Connection socket for EASYLAB controller
Supply voltage 24 V DC from the controller TCU3 or adapter module TAM
Connecting cable Approx. 5 m standard network patch cable, SF-UTP, extendable to 40 m
Operating temperature 10 – 50 °C
IEC protection class III (protective extra-low voltage)
Protection level IP 20
EC conformity EMC according to 2004/108/EC
Dimensions 145 × 111 × 23 mm
Weight 0.280 kg
Control panels with adjustable status display for the EASYLAB system, used to display and control the most critical aerodynamic and safety-related functions of a
fume cupboard or a room. The control panel includes a backlit 40-character display, function buttons, a three-colour status display, an alarm sounder, and a service
socket.
Mounting on side frame or wall
Functions
Configurable, optical and acoustic signalling of the safety-related functions
Text displays in several languages
Large three-colour status display; green, yellow or red with text LOW or HIGH (red: either blinking or permanent)
Continuous self monitoring of the communication between controller and control panel
Integral service socket for configuration and diagnosis
Wireless communication with Bluetooth module BlueCON
Two control panels can be connected simultaneously to a controller
Configurable functions
Available (configured) function buttons are visible
Unavailable function buttons are not visible
Control panel for fume cupboard controller
Function buttons that can be activated
Warning display that the 'maximum operational sash opening' has been exceeded
Increased volume flow
Reduced volume flow
Shut-off mode
Automatic sash device
Fume cupboard lighting
Manual mode (override operating mode default setting)
Text display

Service is due (option)
Power supply failure (EASYLAB controller with expansion module EM-TRF-USV)
Smoke extract is active
Extract air scrubber is active
Device faults (various codes)
Display of face velocity actual value at fume cupboards (option for fume cupboards with face velocity transducer)
Control panel for room controllers
Functions
Configurable, optical and acoustic signalling of the safety-related functions of a room with up to 24 EASYLAB controllers
Room pressure monitoring
Monitoring of the total room extract air (excess will be signalled)
Monitoring of the minimum room extract air (shortfall will be signalled)
Consolidated alarm for the room
Function buttons that can be activated
Increased volume flow
Reduced volume flow
Shut-off mode
Manual mode (override room operating mode default setting)
Control input signal for an individually usable relay changeover contact, e.g. for lighting
Control input signal for sun protection/blinds (to be provided by others)
The operating mode default setting applies to all controllers in a room.
Text display
Room operating mode
Total room extract air setpoint value and actual value (option)
Room pressure setpoint value and actual value (option)
System and device faults
Power supply failure (EASYLAB controller with expansion module EM-TRF-USV)
Special characteristics
Large three-colour status display
Push buttons and functions can be configured individually
Easy to use – available function buttons are visible, unavailable function buttons are not visible
Excellent operating reliability as a result of continuous self monitoring of the communication between controller and control panel
Pluggable adapter which can provide four different viewing angles
Mounting on side frame or wall
Materials and surfaces
Casing in ABS plastic
Casing: pearl light grey (RAL 9022)
Front plastic: anthracite grey (RAL 7016)
Technical data
Supply voltage: 24 V DC from the controller TCU3 or adapter module TAM
Plug-in connection cable, 5 m long, extendable to 40 m (standard network patch cable SF-UTP)
Protection level: IP 20

Fume cupboard control, Room control
Type
BE-LCD Control panel with 40-character display
Application
Displaying and operating the aerodynamic functions of fume cupboards
Status display to EN 14175
Connection to fume cupboard controller EASYLAB TCU3
Two control panels can be used for each fume cupboard controller, e.g. for fume cupboards with sash windows on two sides
Functions
Signalling of safety-related functions for fume cupboards according to EN 14175
Sash distance monitoring
Text displays
Volume flow rate actual value and setpoint value
Face velocity actual value (fume cupboards with face velocity transducer, equipment function FH-VS)
Divesity threshold has been exceeded
Service is due
Power supply failure (EASYLAB controller with expansion module EM-TRF-USV)
Smoke extract
Extract air scrubber is active
Configurable functions
Operating modes
Lighting
Automatic sash device
Operating modes
Increased volume flow (emergency operation)
Reduced volume flow (night-time operation)
Shut-off (night-time operation, system shutdown)

Manual mode (permanent override of central settings)
Increased volume flow and manual mode can be set for a limited period
The fume cupboard controller monitors the required volume flow rate and, depending on configuration, the face velocity. A relevant deviation is indicated
on the three-colour status display, together with the text LOW or HIGH. If the volume flow rate is too low, an acoustic alarm is sounded.
Status display
Green: Normal operation
Red with text LOW: Alarm, volume flow rate too low
Yellow with text HIGH: Warning, volume flow rate too high
The red signal can be configured either as a permanent light or blinking, as recommended by EN 14175
40-character display
Text display of operating values, system states and faults in various languages
Information about the safety of the user's workplace
Controls
Function buttons to switch operating modes, automatic sash device or fume cupboard lighting
BE-LCD as control panel for fume cupboards, typical configuration and display example

Installation details, Commissioning
Application
Displaying and operating the aerodynamic functions for rooms with up to 24 EASYLAB controllers TCU3
Connection to room controller EASYLAB TCU3 or TAM with active room management function
The room control panel is the main unit for the room operating mode concept within the EASYLAB system
Two room control panels can be used for each room controller, e.g. on the two doors to a large laboratory
Functions
State signalling for the configured room functions
Monitoring
Minimum total room extract air (shortfall will be signalled)
Total room extract air (excess will be signalled)
Room or duct pressure control
Configurable consolidated alarm (volume flow rate deviations, device faults) for all controllers in a room
Text displays
Room operating mode
Total room extract air setpoint value and actual value (can be configured)
Room pressure setpoint value and actual value (can be configured)
System and device faults
Power supply failure (EASYLAB controller with expansion module EM-TRF-USV)
Divesity threshold has been exceeded or diversity control is active (option)
Configurable functions
Selection of operating mode for all controllers in a room, without additional wiring
Increased volume flow (emergency operation)
Reduced volume flow (night-time operation)
Shut-off (night-time operation, system shutdown)
Manual mode (permanent override of central settings)
Control input signal for an individually usable relay changeover contact, e.g. for lighting
Control input signal for sun protection/blinds (to be provided by others)
Increased volume flow and manual mode can be set for a limited period
Depending on the control strategy and configuration, the control panel monitors and signals for example the total volume flow rates or pressure conditions
for a room that is equipped with up to 24 EASYLAB controllers. Relevant deviations are indicated on the three-colour status display. As an option, acoustic
alarms can be configured. Controller faults are signalled to the room control panel as an configurable consolidated alarm. The necessary data is
exchanged between the controllers via the EASYLAB communication cable.
BE-LCD as room control panel, typical configuration and display example

Installation and commissioning
Mounting on the fume cupboard, using the adapter: right-hand side frame, left-hand side frame, above the sash, or below the sash
Mounting on walls or furniture, also directly on junction boxes
Connect the control panel to the EASYLAB controller TCU3 or to TAM
Controller recognises the control panel
If necessary, make project-specific adjustments using the EasyConnect configuration software
On the left-hand side frame
On the right-hand side frame

Above the sash

Below the sash

BE-LCD, mounted on a fume cupboard
① Pluggable adapter that provides four different viewing angles
Fixing the base plate to a junction box

① Base plate
② Junction box, 60 mm minimum depth
Fixing the base plate to the wall
BE-LCD, wall mounting without adapter
Table of contents
Other Trox Control Panel manuals
Popular Control Panel manuals by other brands

PS Engineering
PS Engineering PMA8000BT System installation and operation manual

Alfaled
Alfaled AFT-20 quick start guide

Trane
Trane XR401 Comfort Control Installer's guide

Riello
Riello 20147241 Instruction booklet

Slant/Fin
Slant/Fin VICTORY II VHS Series manual

PEDROLLO
PEDROLLO E1 MONO Original instructions for use