
TSI Power Corporation April, 2021 SG03501
ATS-500 Series Rev. 3
Page 4 of 5
Power-Up Procedure
1. Perform a visual inspection of the ATS-500 unit and verify that it is not physically damaged. Verify that the
equipment label states correct voltage, frequency and amperage of the input & output AC power sources.
Also, verify that the stated output voltage, frequency and amperage are compliant with the input power
requirement of the load equipment to be powered by ATS-500.
CAUTION: Turn both switches marked as “Primary Input Breaker” and “Backup Input breaker” to
OFF position.
WARNING: Make sure that both Primary and Backup AC input wires are de-energized.
2. Connect (or plug in) both the Primary and Backup AC input connections. For 15, 20 and 30 Amp hardwire
units recommended tightening torque is 0.79Nm (7 in.-lbs), for 40 Amp hardwire units recommended
tightening torque is 2.26Nm (20 in.-lbs).
CAUTION: Make sure that both Primary and Backup AC input voltages and requencies match
those speci ied on the product label a ixed to the ATS unit. The ATS will only operate when the input
voltage is within speci ication and when the input requency is within ± 5 % o that speci ied. Both
primary and backup must be the same nominal requency.
3. Turn on the Backup AC circuit breaker in the rear of the ATS unit. ake sure that the audible alarm switch
(in front of the ATS unit) is in the "ENABLE" position.
4. The yellow LED should turn on and the alarm sound must turn ON (red alarm LED must turn ON; green
LED must be OFF).
5. Turn on the Primary AC circuit breaker in the rear of the ATS unit.
6. The green LED must turn on after several seconds. Yellow LED must turn OFF. The audible alarm (sound)
and red alarm LED must turn OFF.
7. Turn off the Primary AC circuit breaker. The green LED must turn off. The yellow Backup LED must turn ON.
Red alarm LED and alarm (sound) must turn ON.
8. Turn on the Primary AC circuit breaker. After several seconds, ATS must return to normal operating
condition as in step 6.
9. Turn off the Backup AC circuit breaker. The green LED must remain ON and the red alarm LED and alarm
sound must turn on.
10. Turn on the Backup AC circuit breaker. After several seconds, ATS must return to normal operating
condition as in step 6.
TESTING WITH ACTUAL LOAD EQUIPMENT (SUCH AS COMPUTERS, PLC, TELECOM EQUIPMENT, ETC.)
CAUTION: To avoid electric shock or accidents, ensure that both Primary & Backup AC sources are
de-energized be ore making the wire connection to the AC sources.
11. If the above test steps (1) through (10) are performed and the ATS is functioning properly, then actual load
equipment can be connected (or plugged into) the output terminal block (or output socket) of the ATS. For
15, 20 and 30 Amp hardwire units recommended tightening torque is 0.79Nm (7 in.-lbs), for 40 Amp
hardwire units recommended tightening torque is 2.26Nm (20 in.-lbs).
12. Perform steps 3 through 10 assuring that the load is operating properly.
13. End