Turbo E8T Operation instructions

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channels
I nMn E E 8 T
e n R ev . 0 0
T UR B O Sr l
D u s t F i l t e r C o m p o n en t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
1
Economizer E8T 16 Output Channels
U s e a n d M a i n t e n a n c e I n s t r u c t i o n s

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
2 T UR B O Sr l
D u s t F i l t e r C o m p o n en t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
I n Mn E E 8 T
R e v . 0 0 e n
Description ____________________________________________________________________ 3
Technical Specifications ________________________________________________________ 4
Dimensions And Measurements ________________________________________________ 6
Warning Symbols Used n This Manual _________________________________________ 7
nstallation Regulations and Warnings__________________________________________ 7
Electrical Connections __________________________________________________________ 9
Jumper Configuration Power nput ____________________________________________ 10
Jumper Configuration Output Voltage _________________________________________ 10
Keyboard And Monitor _________________________________________________________ 11
Menu Layout __________________________________________________________________ 12
Basic Settings _______________________________________________________________________ 12
Advanced Settings __________________________________________________________________ 13
Alarms ______________________________________________________________________________ 14
Calibration / Test ___________________________________________________________________ 15
Counters ____________________________________________________________________________ 16
Tribo Electric Probe ____________________________________________________________17
Operation Description_________________________________________________________ 18
Manual Operating Mode ____________________________________________________________ 18
Automatic Operating Mode _________________________________________________________ 18
Proportional Operating Mode _______________________________________________________ 18
Special Manual Operating Mode ____________________________________________________ 19
Other Function Descriptions___________________________________________________ 19
Alarms ______________________________________________________________________________ 19
Cleaning Function With Fan Off Post-Cleaning ______________________________________ 20
Selecting The Number Of Outputs __________________________________________________ 20
Pre-Coating Function _______________________________________________________________ 20
Cleaning Function From Remote Control ____________________________________________ 20
4-20mA Out Function _______________________________________________________________ 21
4-20mA N Function _________________________________________________________________ 21
Trouble Shooting
FAQ
________________________________________________________ 22
Default Settings _______________________________________________________________ 23
Maintenance __________________________________________________________________ 23
Scrapping _____________________________________________________________________ 23
Warranty ______________________________________________________________________ 24
Warranty Exclusions ___________________________________________________________ 24
Declaration Of Conformity Of The Manufacturer ______________________________ 25

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
I n Mn E E8 T
e n R ev . 0 0
T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
Description
Economizer for the control of industrial dust collector system pneumatic cleaning.
Differential pressure digital control through internal transducer, which allows the
accurate analysis of the cleaning filter clogging status.
Voltage free contact digital inputs, input and output relay contacts.
LCD backlit monochromatic graphic monitor where the following can be read at any
time:
dP filter clog status
running solenoid valves
time remaining for next air jet start
emission value
Interface menu available in five languages.

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
4 T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
I n Mn E E 8 T
R e v . 0 0 e n
Technical Specifications
Power Voltage
115 Vac 50-60 Hz ± 10 %
2 0 Vac 50-60 Hz ± 10 %
Alternative Power Voltage
Upon Request
24 Vac ± 10 %
24 Vdc ± 10 %
Output Voltage For Solenoid 115 Vac 50-60 Hz ± 10 %
2 0 Vac 50-60 Hz ± 10 %
24 Vac ± 10 %
24 Vdc ± 10 %
Inputs from 4 to 20mA x 1
Outputs Proportionate To Dp Value
For Remote Pressure Reading from 4 to 20mA x 1
Power Consumption 28 Watts Maximum Load
Alarm Relays Normally Closed
Display Graphic LCD Backlit Monochromatic
B/W 128 x 64 Pixel
Glass Fuse 5 x 20 mm 115 or 2 0 Vac 1 x 1 A
24 Vac or 24 Vdc 1 x A
Operating Temperature -10 °C - 55 °C
Storage Temperature -20 °C - 60 °C
Environmental Humidity 0 ÷ 95% Relative
Non Condensing
Valve Opening Impulse Time 50 m.sec. - 10 s
Interval Pause Time Between
Valve Opening 1 sec. – 7200 sec.
Measurable Pressure 0 - 10 kPa
Maximum Pressure Applicable
To The Gauge
50 kPa – 0.5 bar
Higher pressures will
damage the device
Casing ABS Base
Polycarbonate Cover
Protection Degree From Water And Dust
IP65 DIN EN 60529
Shock Resistance IK07 2 Joule (EN62262).

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
I n Mn E E8 T
e n R ev . 0 0
T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
5
Operating modes
manual, automatic, proportional, special manual.
Selectable pressure unit of measure
kPa, millibar, mmH2O, Inch w.c.
Manual solenoid valve activation.
Operating time expressed in seconds and minutes with selectable values for any
application.
Cleaning function with fan off (post-cleaning) by "dP fan" threshold in automatic
/ proportional mode and by contact in manual / special manual modes, with
selectable number of cycles up to 100.
With the automatic operation, is activated upon reaching the dP Start Cleaning
value, turns off when the low threshold is reached dP End Cleaning.
Hour counter and impulse counter.
Minimum dP alarm "broken sleeve" (with the possibility of inclusion / exclusion).
Maximum dP alarm (clogged filter).
Faulty solenoid valve alarm.
Filter element maintenance alarm (with the possibility of inclusion / exclusion).
Cleaning start from external contact.
Compressed air consent input.
Pre-coating function.

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
6 T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
I n Mn E E 8 T
R e v . 0 0 e n
Dimensions And Measurements
Fastening
Weight 2.1 Kg
To open the transparent cover, press on the right side
and lift.

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
I n Mn E E8 T
e n R ev . 0 0
T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
7
Warning Symbols Used In This Manual
The safety-related indications are highlighted using the symbols:
Attention - Danger
Warning - Generic
Risk – Danger Electric Current
Dispose of in compliance with the electrical and
electronic equipment Standard WEEE
Installation Regulations and Warnings
Protect the equipment from direct exposure to sunlight.
Do not position the equipment near or directly in contact with sources of
heat or electromagnetic fields.
Fix the equipment at a height of at least 60 cm from the ground.
In a clearly visible place that is easily accessible.
Connect the equipment to power lines other than those used for operating motors
or other high power devices, which could generate network interference or
instability.
The unit electric power supply must be protected by a 2 0Vac~ 0mA Residual
Current Device RCD and a bipolar 2 0Vac~ 10A magnet circuit breaker, positioned
in a place that is easily accessible.
Before intervening on the equipment to perform any operation, deactivate
the magnet circuit breaker switch.
For electric operations, always remove voltage, wait 0 seconds for the
internal capacitors to discharge before opening. At the end of the
operations, close the equipment before powering up.
Before intervening on the equipment to perform any operation, check the
conditions of the atmosphere are safe.
For connection of the supply voltage, use flame-retardant wires with a minimum
section of 0.75mm² certified and conform to the IEC 60227 or IEC 60245
standard.
Use flame-retardant cables with a minimum cross-section area of 0.75 mm² for all
control signals.
Use flame-retardant cables with a minimum cross-section area of 0.75 mm² to
connect to the indicating relays.
The earth wire must be yellow/green.
The earth wire must be connected first.
The yellow/green wire must only be used for the earth connection.

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
8 T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
I n Mn E E 8 T
R e v . 0 0 e n
The cable glands must be chosen according to the diameter of the cable to be
used.
Sealing of the cable glands is guaranteed by the compression of the rubber gasket
that tightens on the outer diameter of the cable.
The size of cable and cable gland must ensure that power cord traction is not
acting on the terminals.
The terminal block must not be the mechanical anchorage point of the wires.
The cable gland PG9 supplied on request, has minimum cable diameter of 4 mm
and maximum of 8 mm, with 19 mm clamping nut.
Any use not described in this user instruction manual or incorrect use of the
device may cause damage to the device or to the equipment connected to it.
Furthermore, incorrect use or tampering with the equipment may cause injury.
The impermeability of the casing is guaranteed when the door is closed.
Make sure that rigid or flexible ducts used for wiring, do not fill up with water or
other liquids.
Do not make unprotected holes in the container or holes that are protected by
accessories with protection rating lower than that of the control unit.
Cut off power supply immediately if water is found in the casing.
If the control unit is used in ways not specified by the manufacturer, the
protection provided by the device may be impaired.
The E9T Control Unit does not release potentially toxic or harmful substances to
the health and the environment.
No part with dangerous voltage is normally accessible.
Do not use the control unit if you have not read or do not understand this manual.

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
I n Mn E E8 T
e n R ev . 0 0
T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
9
Electrical onnections
To connect the wires to the E8T control unit, remove
the cover panel to access the terminal board,
unscrewing the two screws.

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
1 0 T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
I n Mn E E 8 T
R e v . 0 0 e n
Jumper onfiguration Power Input
115 VAC ~
230 VAC ~
In the 24Vac and 24Vdc versions J and J4 jumper are not used.
Jumper onfiguration Output Voltage
24 VAC ~
115 VAC ~
230 VAC ~
24 VDC
In versions powered at 24VAC and 24VDC the output voltages can not be 115Vac
or 2 0Vac.

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
I n Mn E E8 T
e n R ev . 0 0
T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
1 1
Keyboard And Monitor
There are 5 round keys on the front panel to control the instrument and select
functions.
When turned on, the screen displays the firmware version
during initialisation
The next screen is always displayed during normal
operations:
Menu
provides access to settings
it is used as RESET in the event of alarms
Keys
Increase and decrease the values, manually start
valves in Test mode, used to scroll any alarms.
The
S
key starts/stops solenoid valves in
manual/special manual mode. It is not enabled in
automatic/proportional mode.
Use the L key to select one of the 5 available
languages: Italian, English, French, German,
Spanish.
On the main screen, when an alarm is active, the letter
L
changes state becomes
A
,
pressing scrolls through the alarms, pressing
A
returns to the screen with
dP reading.
With the probe installed, the and-keys change the screen to display the
emission reading values with that of the DP values.
Without the probe installed, only the screen with dP values is available.

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
1 2 T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
I n Mn E E 8 T
R e v . 0 0 e n
Menu Layout
Basic Settings
Press the
Menu
key in the main screen.
Use the arrows to select Main Set Up
Press
OK
key.
Use the arrows to select the item to be set.
Use keys to increase or decrease the value and change the item
conditions. Press
exit
to save and exit.
Set Operation Selectable arameters
Operative Mode Manual
Automatic
Proportional
Special
Pulse Time Opening Valve 50 mSeconds ÷ 10 Seconds
Cycle Time Interval Openings 1 Second ÷ 7200 Seconds
Number of Valves 1 ÷ 16
Unit Measure dP mmH2O – Mbar - Kpa - Inch WC
dP Start Cleaning Enter the start cleaning dP value
for Automatic or Proportional operating mode
dP Stop Cleaning Enter the end cleaning dP value
for Automatic or Proportional operating mode

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
I n Mn E E8 T
e n R ev . 0 0
T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
1
Advanced Settings
Press the
Menu
key in the home page.
Use the arrows to select Advanced Set Up.
Press
OK
key.
Use the arrows to select the item to be set.
Use keys to increase or decrease the value and change the item
conditions. Press
exit
to save and exit.
Set Operation Selectable arameters
dP Fan On / Off dP threshold tied to fan on / off for which
the tool recognizes that suction is on over
the set threshold while cleaning cycles are
started with the fan off under it
Post-Cleaning
Cleaning Fan off Number of complete cleans with fan off for
the number of connected solenoid valves.
Pulse Time Valve opening time in cycles with fan off
50 mSeconds ÷ 10 Seconds
Cycle Time Interval between valve opening in cycles
with fan off
1 Second ÷ 7200 Seconds
Precoating Enables the Precoating function.
For applying the layer of powder protective
on the filter media
dP Precoating Enter the dP value where the pre-coating
function is kept enabled. When exceeded
the instrument returns to the originally set
operating mode
Cycles Man. Special If Special operating mode was selected in
basic set up, enter the number of complete
cycles for the number of connected solenoid
valves to be completed
Pause Cycles Man. Special If Special operating mode was selected in
basic set up, enter the pause between the
number of cycles

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
1 4 T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
I n Mn E E 8 T
R e v . 0 0 e n
Alarms
Press the
Menu
key in the home page.
Use the arrows to select Advanced Set Up.
Press
OK
key.
Use the arrows to select the item to be set.
Use keys to increase or decrease the value and change the item
conditions. Press
exit
to save and exit.
Set Operation Selectable arameters
dP Dirty Filter Enter the dP threshold to trigger the
clogged filter alarm.
Enabling Minimum dP Minimum dP alarm enabling (broken
sleeve).
Low Alarm Thresh. dP Enter the dP threshold to trigger the
Minimum dP alarm.
Hour Meter Fan Enabling the fan hour meter.
Connect the fan filter remote switch to
terminals 18_19 connector P9, to count
actual suction working hours
Replace Filters Enter the number of working hours desired
to trigger the filtering element replacement
alarm (sleeves/cartridges), the alarm is
only generated if the fan hour meter is
enabled and the fan remote switch
connected to terminals 18_19 on conn
ector
P9 on the electronic board.

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
I n Mn E E8 T
e n R ev . 0 0
T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
1 5
alibration / Test
Press the
Menu
key in the home page.
Use the arrows to select Calibration / Test.
Press
OK
key.
Use the arrows to select the item to be set.
Use keys to increase or decrease the value and change the item
conditions. Press
exit
to save and exit.
Set Operation Selectable arameters
No. Valve (+/- = ON) Activation Press the keys to manually start
the solenoid valves connected to the
electronic board in sequence.
Calibration Zero dP = Press the keys to calibrate
zero dP.
Run this operations with the filter fan off.
4 mA Output Press the keys to calibrate the
4mA output which corresponds to zero dP
20 mA Output Press the keys to calibrate the
20mA output which corresponds
to dP full scale

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
1 6 T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
I n Mn E E 8 T
R e v . 0 0 e n
ounters
Press the
Menu
key in the home page.
Use the arrows to select Counters.
Press
OK
key.
Use the arrows to select the item to be set.
Use keys to increase or decrease the value and change the item
conditions. Press
exit
to save and exit.
Set Operation Selectable arameters
Hours Power
Counting
the operating hours of the
electronic control unit.
Pulse count
Number of times the valves connected
to the electronic board were started.
Hours Fan
Hours the filter fan is on.
The counter is only on if the filter fan
remote switch is connected to
terminals
18_19 on connector P9
and the fan hour
counter function enabled in the Alarm
menu.

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
I n Mn E E8 T
e n R ev . 0 0
T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
1 7
Tribo Electric Probe
For the E8T versions were is provided.
Press the
Menu
key in the home page.
Use the arrows to select Counters.
Press
OK
key.
Use the arrows to select the item to be set.
Use keys to increase or decrease the value and change the item
conditions. Press
exit
to save and exit.
Tribo Electric robe
Alarms
arameters Factory Setting
Pre-Alarm Threshold 0.01 mg/m³ 800
Pre-Alarm Time
Recognition Multiple of 0.5 Sec. 00
Threshold Alarm 0.01 mg/m³ 1500
Time Alarm Recognition
Multiple of 0.5 Sec. 60
Threshold Peak 0.01 mg/m³ 000
Time Recognition Peak Multiple of 0.5 Sec. 10
Reference Emissions 0.01 mg/m³ 5000
Reference µ Ampere 0.001 mA 20000
The alarms generated by the electric Tribo probe activate the K relay at the 4_5
terminals of the P4 connector.
The relay is normally closed, opens in case of alarm, and opens to the control
unit off in the absence of power.
The Pre-Alarm and Alarm parameters are understood as:
Pre-Alarm Sets a value that indicates that the quantity of emissions tolerated
was exceeded.
Time of
Pre-Alarm
Sets the time interval duration in which emissions above the critical
threshold should remain before being reported.
Alarm
Setting an alarm value, a peak of moments is not reported as a
warning, but the warning only occurs if a value is high and
permanent over time.

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
1 8 T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
I n Mn E E 8 T
R e v . 0 0 e n
Operation Description
The displayed information are:
the operating mode
the internal dust filter pressure
active outputs and the time necessary to
activate the next output.
Manual Operating Mode
When manual operating mode is set, the economizer works as a programmable
cycle sequencer. The connected outputs will be activated at programmed time
intervals. Manual operating mode can be selected in the Main Set Up menu under
the first menu item.
Intervals are programmed in the same menu where activation time, pause time
and the number of solenoid valves connected to the device are set.
Automatic Operating Mode
When Automatic mode is selected from the basic set up menu, first menu item,
the economizer will work autonomously running pneumatic cleaning only when
necessary. If the device detects clogging over the dP Start Cleaning threshold,
cleaning is started.
If clogging drops under the dP Stop Cleaning threshold, cleaning is suspended
and turns off, until the pressure rises to a value over dP Start Cleaning.
When cleaning, the time in which the economizer cleans can be set in the basic
set up menu.
Proportional Operating Mode
By selecting the Proportional mode in the basic set up menu, the economizer
works autonomously initially setting the Start Cleaning threshold, pulse time and
pause time.
Automatically, when the Start Cleaning threshold is exceeded, the solenoid valves
are activated in sequence. If the dP threshold lowers 15% at the end of an entire
pulse cycle for the connected solenoid valves, cleaning is suspended until the
pressure rises over the dP Start Cleaning threshold.
If the dP value does not drop 15% under the Start Cleaning threshold, the pause
time frequency is automatically reduced proportionately at each complete cycle
of connected solenoid valve pulses, until a pause time between solenoid valves is
minimum 10 seconds. The minimum 10 second threshold was chosen to not
stress air distribution by the compressor connected to the filter.

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
I n Mn E E8 T
e n R ev . 0 0
T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
1 9
Special Manual Operating Mode
In the basic set up men, first menu item, select Special mode, enter the pulse
time and pause time. Open the advanced set up menu, second menu item, enter
the number of complete cycles and pause time between these cycles for the
connected solenoid valves.
With this mode, unlike manual mode, the device only runs the solenoid valves for
the set number of cycles and will remain in stand-by until an operator presses
S
(start / stop) in the main menu to repeat the cycles. This mode is especially
suited for small filters or filters where the dP has low values or the inverter
keeps pressure constant and it is hard to work with automatic and proportional
modes.
Other Function Descriptions
Alarms
This function allows an alarm device to be connected. The alarm device can be
connected to two alarm relays (see wiring diagram) which are opened when the
threshold set in the ALARMS menu is exceeded. For details, see the third menu
item and the description in the Accessing the Alarm menu section.
When an alarm is triggered, it is signaled on the display by a blinking row that is
normally occupied by the operating mode. The menu key is used for Reset and
keys can be used to scroll any alarm items that may have triggered for
relay no. 1: dP minimum (
if enabled in the menu
), dP Dirty Filter, Replace Filters
(if enabled in the menu) while failed valve activation is signaled with relay no. 2.
Relay 1
Terminals 8-9 Conn. 4
Relay 2
Terminals 6-7 Conn. 4
Relay 3
Terminals 4-5 Conn. 4
dP Minimum
if enabled in the menu Valve Activation Failed Triboelectric Probe
Pre - Alarm
dP Dirty Filter Triboelectric Probe
Alarm
Replace Filters
if enabled in the menu Triboelectric Probe
Peak

U s e A n d M a i n t e n a n c e I n s t r u c t i o n s
E conomizer E8T 16 Output Channel s
2 0 T UR B O S rl
D u s t F i l t e r C om p o n e n t s
V i a P o / 5 2 0 8 11 C e s an o M a d e r n o ( M B ) I t a l y T e l + + 9 0 6 2 57 4 0 2 4 F a x + + 9 0 6 2 5 7 4 0 92
I n Mn E E 8 T
R e v . 0 0 e n
leaning Function With Fan Off Post- leaning
This function allows a cleaning cycle to be run with the fan off.
Post-cleaning is automatically activated in Automatic and Proportional operating
modes and when differential pressure drops under a threshold that can be set in
the advanced set up menu, second menu item.
While in Manual and Special Manual modes, it occurs through a contact
connecting the fan to terminals 12_1 on connector P9, see wiring diagram.
In the advanced set up menu, the following post-cleaning settings can be set:
Start cleaning with fan off (Enable/Disable)
Activation pressure (dP fan ON/OFF threshold)
Number of cycles (cycles completed)
Pause time (pause duration between one solenoid valve start and the
next during post-cleaning).
Pulse time (cleaning pulse duration regardless of the fan on operating
time).
Selecting The Number Of Outputs
The number of outputs, solenoid valves on which the economizer runs the
cleaning cycle can be selected. Cleaning is run in order from the first solenoid
valve to the last. Valve regulation is possible in the basic set up menu.
Pre- oating Function
This function lets you run pre-coating. Pre-coating is a filter element treatment
run with a powder called pre-coating powder. During the pre-coating phase,
cleaning is suspended until the dP pre-coating threshold is reached.
In the advanced set up menu, the following pre-coating settings can be set:
Pre-coating start: Enable on / Disable off.
Disable pressure dP Pre-Coating.
leaning Function From Remote ontrol
This function lets you pneumatically clean only after an external consent is
received. The external consent can be connected to prevent cleaning without
pressure in the high pressure circuit or in the compressed air tank.
The external contact must be voltage free, normally open and connected to
terminals 14_15 connector P9.
Table of contents
Popular Control Panel manuals by other brands

GARDINER TECHNOLOGY
GARDINER TECHNOLOGY Gardtec 800 installation instructions

DMP Electronics
DMP Electronics XTLN-WiFi installation guide

Beijer Electronics
Beijer Electronics IFC MC manual

BFT
BFT LIBRA-C-LX installation manual

Channel Safety Systems
Channel Safety Systems FW1001 User manual & log book

NAPCO
NAPCO MFA6000 Operating and installation instructions