larms
The unit runs a nu ber of checks during the start-up cycle and during nor al
operation. The possible alar s and respective solutions are shown in the following
table.
larm
No. Description ction
E01 F05 set to 24 Vdc
Vac ju per detected
- For 24 Vdc, switch the device off and
ove the AC/DC ju pers to DC.
- For 24 Vac, press OK, then press
SET, set the function F05 using “+”
and “-”, select A24 and press OK to
confir .
E02 F05 set to 24 Vac
Vdc ju per detected
- For 24 Vac, switch the device off and
ove the AC/DC ju pers to AC.
- For 24 Vdc, press OK, then press
SET, set the function F05 using “+”
and “-”, select d24 and press OK to
confir .
E03 F05 set to 24 Vac or Vdc.
Voltage out of range detected
- To use 24V valves, switch the device
off and ove the output voltage
selection ju per to 24V.
- If the ju per is in the correct
position, press OK, then SET, select
the F05 function with “+” and “-”, set
115 or 230 (as ju per) and press OK.
E04 F05 set to 115 Vac.
Voltage out of range detected
- To use 115V valves, switch the
device off and ove the output voltage
selection ju per to 115V.
- If the ju per is in the correct
position, press OK, then SET, select
the F05 function with “+” and “-”, set
115 or 230 (as ju per) and press OK.
E05 F05 set to 230 Vac.
Voltage out of range detected
- To use 230V valves, switch the
device off and ove the output voltage
selection ju per to 230V.
- If the ju per is in the correct
position, press OK, then SET, select
the F05 function with “+” and “-”, set
a24, d24 or 115 (as ju per) and press
OK.
E06
Solenoid valve current lower than
ini u threshold or disconnected
solenoid valve
Check correct connection of the
solenoid valve and respective data.
The alar is self-reset.
E07 Solenoid valve current higher than
axi u threshold
Check correct connection of the
solenoid valve and respective data.
The alar is self-reset.
E08
Output short circuit. Alar
The signaling of the code E08 alternates
with the indication of the interested
output is shown as Uxx where xx is the
nu ber of the output.
Switch the device off and back on after
having checked the solenoid valve
syste .
E11 Maintenance deadline reached Carry out aintenance.