
Alarms
The unit runs a number of checks during the start-up cycle and during normal operation. The
possible alarms and respective solutions are shown in the following table.
Alarm
N mber Description Action
E01 F05 set to 24Vdc – AC jumper detected
For 24Vdc, switch the device off and move the
AC/DC jumpers to DC
- For 24Vac, press OK, then press SET, set the function
F05 using “+” and “-”, select A24 and press OK to
confirm.
E02 F05 set to 24Vac – DC jumper detected
For 24Vac, switch the device off and move the AC/DC
jumpers to AC.
- For 24Vdc, press OK, then press SET, set the function
F05 using “+” and “-”, select d24 and press OK to
confirm.
E03 F05 set to 24Vac or dc. Voltage out of range
detected
To use 24V valves, switch the device off and move
the output voltage selection jumper to 24V. - If the
jumper is in the correct position, press OK, then SET,
select the F05 function with “+” and “-”, set 115 or
230 (as jumper) and press OK.
E04 F05 set to 115V. Voltage out of range
detected
To use 115V valves, switch the device
the output voltage selection jumper to 115V.
- If the jumper is in the correct position, press OK,
then SET, select the F05 function with “+” and “-”, set
115 or 230 (as jumper) and press OK.
E05 F05 set to 230V. Voltage out of range
detected
To use 230V valves, switch the device off and move
the output voltage selection jumper to 230V.
- If the jumper is in the correct position, press OK,
then SET, select the F05 function with “+” and “-”, set
a24, d24 or 115 (as jumper) and press OK.
E06 Solenoid valve current lower than minimum
threshold or disconnected solenoid valve
Check correct connection of the solenoid valve and
respective data. The alarm is self-reset.
E07
Solenoid valve current higher than maximum
threshold
connection of the solenoid valve and
respective data. The alarm is self-reset.
E08
Output short circuit. Alarm
The signaling of the code E08 alternates with
the indication of the interested output is
shown as Uxx where xx is the number of the
output and the value of dP.
Switch the device off and back on after having
checked the solenoid valve system.
E11 Maintenance deadline reached
Carry out maintenance.
E14
Indicates that a valve in short circuit has
been excluded from the cycle.
The signaling of the code E14 alternates with
the indication of the interested output is
shown as Uxx where xx is the number of the
output and the value of dP.
An output is considered a short circuit if not
responding for 3 following activations.
An activation without error resets the
counting.
Switch the device off and back on after having
checked the solenoid valve system.