
Alarms
The unit runs a number of checks during the start-up c cle and during normal
operation. The possible alarms and respective solutions are shown in the
following table.
A. No.
Description Action
E01 F05 set to 24Vdc – AC jumper
detected
- For 24Vdc, switch the device off and
move the AC/DC jumpers to DC. Jumper
see table next pages.
- For 24Vac, press OK, then press SET,
set the function F05 using “+” and “-”,
select A24 and press OK to confirm.
E02 F05 set to 24Vac – DC jumper
detected
- For 24Vac, switch the device off and
move the AC/DC jumpers to AC. Jumper
see table next pages.
- For 24Vdc, press OK, then press SET,
set the function F05 using “+” and “-”,
select d24 and press OK to confirm.
E03 F05 set to 24Vac or dc. Voltage out
of range detected
- To use 24V valves, switch the device
off and move the output voltage
selection jumper to 24V. Jumper see
table next pages.
-
If the jumper is in the correct position,
press OK, then SET, select the F05
function with “+” and “-”
(as jumper) and press OK.
E04 F05 set to 115V. Voltage out of
range detected
- To use 115V valves, switch the device
off and move the output voltage
selection jumper to 115V. Jumper see
table next pages.
- If
the jumper is in the correct position,
press OK, then SET, select the F05
function with “+” and “-”
(as jumper) and press OK.
E05 F05 set to 230V. Voltage out of
range detected
- To use 230V valves, switch the device
off and move the output voltage
selection jumper to 230V.
-
If the jumper is in the correct position,
press OK, then SET, select the F05
function with “+” and “-”, set a24, d24
or 115 (as jumper) and press OK.
E06
Solenoid valve current lower than
minimum threshold or disconnected
solenoid valve
Check correct connection of the solenoid
valve and respective data. The alarm is
self-reset.
E07 Solenoid valve current higher than
maximum threshold
Check correct connec
valve and respective data. The alarm is
self-reset.