Signal processor
MC96 for flow sensors
MC96-12EX0-R/24VDC
Edition • 2011-09-17T06:58:24+02:00
1 / 2
Hans Turck GmbH & Co.KG
ñ D-45472 Mülheim an der Ruhr
ñ Witzlebenstraße 7
ñ T
el. 0208 4952-0
ñ Fax 0208 4952-264
ñ [email protected] ñ www
.turck.com
Type MC96-12EX0-R/24VDC
Ident-No. 9078511
Ambient temperature -20…40 °C
Operating voltage 19.2…28.8 VDC
No-load current I0ð 80 mA
Output function Relay output, changover contact
Device designation É II (1) G [EEx ia] IIC
Protection type [Ex ia] IIC
Ex approval acc. to conformity certificate TÜV 97 ATEX 1183X
Protection class IP20
Protection class (terminals/housing) IP20 / IP40
Design Eurocard
Dimensions 175.5 x 20.3 x 128.5 mm
Housing material Metal/plastic
Connection connector
Indication: Drop below setpoint LED red
Indication: Setpoint reached LED yellow
Indication: Setpoint exceeded 4 x LEDs green
■ATEX category II (1) G, Ex Zone 0
■Single-channel intrinsically safe signal
processor
■type MC96 „multicart“
■Adjustment via potentiometer
■Intrinsically safe control circuit, [EExia]
IIC
■2 relay outputs: 1 changerover switch
each for flow and temperature monitor-
ing
■Flow status indication via 6 LEDs
■Wire-break monitoring
■Temperature monitoring, adjustable
range -20…+100°C
■Programmable switch-on/off delay, ad-
justable range of 0…25 s
Wiring diagram
Functional principle
Signal processors not only supply insertion
and inline sensors with voltage, they also pro-
cess and display the measured signals. De-
vices with MK96…, MS96… and MC96…
housing styles are available. The individual
housing styles are designed for different oper-
ating voltages and feature various output and
supplementary functions. For intrinsically safe
flow sensors it is required to use signal pro-
cessors with intrinsically safe control circuits
of the series MS96…Ex… and MC96…Ex… .