Tyco Fire Protection Products CC2 User manual

Model CC2 — 4.2 and 5.6 K-factor
Combustible Concealed Space Sprinklers™
Specific Application, Upright
Worldwide
Contacts
www.tyco-fire.com
Page 1 of 8 APRIL 2014 TFP632
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cau-
tions with respect to handling
and installation of sprinkler sys-
tems and components. Improp-
er handling and installation can
permanently damage a sprin-
kler system or its components
and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
General
Description
The TYCO®Model CC2 Combusti-
ble Concealed Sprinklers are fast re-
sponse, upright, specific application
sprinklers designed to provide pro-
tection of specific light hazard com-
bustible, as well as non-combustible,
concealed spaces requiring sprinkler
protection. The CC2 Sprinklers com-
ply with the criterion for the protection
of combustible concealed spaces as
described in NFPA 13.
The Model CC2 Sprinklers are de-
signed for installation on BlazeMas-
ter®CPVC wet pipe systems and steel
wet pipe or dry pipe sprinkler systems
(refer to the respective Design Criteria
sections). They provide the following
features as compared to the 2.8K-fac-
tor Model CC1 Sprinklers described
on Technical Data Sheet TFP630:
•
Can be used on steel dry pipe
sprinklersystems.
•
Increasedspacingfrom10ft.(3,1
m)to12ft.(3,7m).
•
Increasedcoverageareafrom100
ft2(9,3m2)to144ft2(13,4m2).
The effectiveness of the Model CC2
Sprinklers in combustible concealed
spaces was clearly evident during the
full scale fire testing for this product.
Concealed spaces between floors, as
well as low pitch attics (slope of 2:12
or less) are inherently shallow. Stan-
dard spray sprinklers, by design, have
an umbrella like spray pattern that
poses a difficult challenge when trying
to achieve effective coverage within a
shallow space. The Model CC2 Com-
bustible Concealed Space Sprinklers
have addressed the difficult “above
ceiling” fire challenge for both wet
pipe and dry pipe sprinkler systems.
NOTICE
The Model CC2 Combustible Con-
cealed Sprinklers described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation, in addition to the standards of
any other authorities having jurisdic-
tion. Failure to do so may impair the
performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
Contact the installing contractor or
manufacturer with any questions.
Sprinkler
Identification
Number
TY2189 – Upright, 4.2K
TY3189 – Upright, 5.6K
Technical
Data
Approvals
UL Listed.
(Listings and approvals only apply to
the service conditions indicated in the
Design Criteria sections.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
1/2 inch NPT or ISO 7-R3/4
Discharge Coefficient
K = 4.2 gpm/psi1/2 (60,5 lpm/bar1/2)
K = 5.6 gpm/psi1/2 (80,6 lpm/bar1/2)
Temperature Rating
175° F (79° C)
Finish
Natural Brass
Physical Characteristics
Frame .............................Brass
Button............................Bronze
Sealing Assembly ......... Stainless Steel w/
TEFLON
Bulb .....................Glass (3 mm dia.)
Compression Screw . . . . . . . . . . . . . . . . . Brass
Deflector..........................Bronze
Operation
The glass bulb contains a fluid that ex-
pands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter
the glass bulb allowing the sprinkler to
activate and flow water.

TFP632
Page 2 of 8
Design Criteria
Design criteria is provided as follows:
•
175° F (79° C),ModelCC2Combus-
tible Concealed Sprinklers with
CPVC Pipe and horizontal slope
abovesprinklersnotexceeding2:12
(RefertoPage2).
•
175° F (79° C),ModelCC2Combus-
tible Concealed Sprinklers with
Steel Pipe and horizontal slope
abovesprinklersnotexceeding2:12
(RefertoPage3).
CPVC Pipe
CC2 Temperature Rating (CPVC
Pipe)
175° F (79° C)
Area Of Use (CPVC Pipe)
Horizontal (slope not exceeding 2:12)
combustible concealed spaces of:
•
Unobstructedwoodtrussconstruc-
tion or unobstructed bar joist
construction(Fig.2).
•
Non-combustible, insulation-lled
solidwoodorcompositewoodjoist
construction(Fig.3).
NOTE: In order to be considered
“non-combustible insulation-filled sol-
id wood or composite wood joist con-
struction,” the insulation (including in-
sulation provided with a combustible
vapor barrier), must completely fill the
pockets between the joists to the bot-
tom of the joists, and the insulation
must be secured in place with metal
wire netting. The metal wire netting is
intended to hold the insulation in place
should the insulation become wetted
by the operation of the CC2 Sprinklers
in the event of a fire.
Concealed Space Area (CPVC Pipe)
The area of the concealed space is
not limited; however, for both Fig. 2
and Fig. 3, where CPVC pipe is be-
ing utilized, draft-curtains or full height
walls must be provided at 1000 ft2(93
m2) areas. This draft curtain shall be
at least 1/3 the depth of the concealed
space or 8 inches (200 mm), whichev-
er is greater, and be constructed us-
ing a material that will not allow heat
to escape through or above the draft
curtain.
Concealed Space Size (CPVC Pipe)
The depth of the concealed space is
36 inches (915 mm) maximum to 12
inches (305 mm) minimum.
System Type (CPVC Pipe)
Light hazard, wet pipe system
Minimum Distance Between CC2
Sprinklers (CPVC Pipe)
The minimum distance between sprin-
klers is 7 Ft. (2,1 m).
NOTE: Minimum spacing does not
apply to any additional sprinklers
required for protection of Blaze-
Master CPVC that is offset over an
obstruction.
Maximum Distance Between CC2
Sprinklers (CPVC Pipe)
12 feet (3,7 m)
Maximum Coverage Area (CPVC
Pipe)
144 ft2(13,4 m2)
Deflector Position (CPVC Pipe)
•
1-1/2 to 4 inches (40 to 100 mm)
belowupperdeckforwoodtruss
constructionorbarjoistconstruc-
tion(Fig.2)
•
1-1/2 to 4 inches (40 to 100 mm)
below solid wood or composite
woodjoists(Fig.3)
Minimum Distance Away From
Trusses (CPVC Pipe)
4-1/2 inches (114 mm)
Remote Area (CPVC Pipe)
The remote area is 1000 ft2(93 m2)
NOTE: The remote area does not in-
clude any additional sprinklers re-
quired for protection of BlazeMas-
ter CPVC that is offset over an
obstruction.
Required Density (CPVC Pipe)
0.10 gp m /f t 2(4,1 m m/min)
Minimum Operating Pressure
(CPVC Pipe)
7 psi (0,48 bar)
NOTE: The minimum resulting flow for
the 4.2K is 11.1 gpm, and the minimum
resulting flow for the 5.6K is 14.8 gpm.
Therefore, for coverage areas less
than the maximum permitted cover-
age area of 144 ft2, the 4.2K may pro-
vide a hydraulic advantage. The use of
the CC1 sprinkler having a K-factor of
2.8, minimum operating pressure of
10 psi, and resulting minimum flow of
9.5 gpm may provide a further hydrau-
lic advantage for yet smaller coverage
areas. The CC1 is described in Tech-
nical Data Sheet TFP630.
Obstructions (CPVC Pipe)
See Figure 8 in this data sheet for ob-
structions rules.
Use Of UL Listed BlazeMaster
CPVC Piping With Model CC2
Sprinklers
Only BlazeMaster CPVC product may
be used in concealed spaces requir-
ing automatic sprinklers, when used
in conjunction with Model CC2 Sprin-
klers. In order to use the BlazeMaster
CPVC product for wood truss or bar
joist construction, the horizontal run of
pipe must be a maximum of 6 Inches
(150 mm) above the ceiling or noncom-
bustible ceiling insulation, or 1/3 the
depth of concealed space (as mea-
sured from the top surface of the ceil-
ing to the bottom of the deck above),
whichever is smaller (Fig. 2). For insu-
lation filled solid wood or composite
wood joist construction, the horizon-
tal run of pipe must be a maximum
of 6 Inches (150 mm) above ceiling or
non-combustible ceiling insulation,
or 1/3 the depth of concealed space
(as measured from the top surface of
the ceiling to the bottom surface of
the joist insulation above), whichever
is smaller (Fig. 3). The CPVC piping
can then be used to supply the Model
CC2 Sprinklers, as well as the sprin-
klers below the ceiling. Unless modi-
fied by this Technical Data Sheet, all
other guidelines of the “BlazeMaster
— Installation Instructions & Techni-
-
-
-
-
-
-
-
2
7
4
6
5
3
1
CROSS SECTION ELEVATION
Frame
Button
Sealing
Assembly
Deector
Bulb
Compression
Screw
2
1
3
4
Components:
5
6
WRENCH
FLATS
7/16" (11,1 mm)
NOMINAL MAKE-IN
SPRINKLER
FRAME
ARMS
1-11/16"
(42,9 mm)
2-1/4"
(57,2 mm)
1/2" NPT
7
Ejection
Spring
FIGURE 1
MODEL CC2 SPRINKLER

TFP632
Page 3 of 8
cal Manual” must be met. When using
1 inch (DN25) or larger pipe, a hanger
must be located at the truss nearest a
sprig for purposes of restraint. If using
3/4 inch (DN19) piping, all sprigs over
12 inches (305 mm) must be laterally
braced using methods described in
the NFPA standards.
Where the CPVC must be offset up
and over an obstruction and the pipe
exceeds the allowed horizontal posi-
tioning requirements specified above
as well as shown in Figure 2 and 3, ad-
ditional Model CC2 Sprinklers are to
be installed as shown in Figure 2 and
3 to protect the BlazeMaster CPVC
product.
A minimum lateral distance of 18
inches (460 mm) must be maintained
between the CPVC pipe and heat
pumps, fan motors, and heat lamps.
Steel Pipe
CC2 Temperature Rating (Steel
Pipe)
175° F (79° C)
Area Of Use (Steel Pipe)
Horizontal (slope not exceeding 2:12)
combustible concealed spaces of
•
Unobstructedwoodtrussconstruc-
tion or unobstructed bar joist
construction(Fig.4)
•
Solidwoodjoistconstruction(Fig.
5)wheretheupperdeckandceiling
joistsmayhaveamaximumdepth
of12inches(300mm)andtypical
oncenterjoistspacingofminimum
16inches(400mm)
•
Non-combustible insulation lled
solidwoodjoistorwoodcomposite
joistconstruction(Fig.6)
•
Obstructedwoodtruss construc-
tion(Fig.7)
NOTE: In order to be considered
“non-combustible insulation filled sol-
id wood joist or composite wood joist
construction”, the insulation (including
insulation provided with a combusti-
ble vapor barrier),must completely fill
the pockets between the joists to the
bottom of the joists, and the insulation
must be secured in place with metal
wire netting. The metal wire netting is
intended to hold the insulation in place
should the insulation become wetted
by the operation of the CC2 Sprinklers
in the event of a fire.
Concealed Space Area (Steel Pipe)
The area of the concealed space is
not limited; however,
•
for unobstructed wood truss
constructionorconcealedspaces
ofnon-combustible,unobstructed
bar joist construction (Fig. 4)
draft-curtains or full height walls
must be provided at 1000 ft2 (93
m2)areas.Thisdraft curtainshall
be at least 1/3 the depth of the
concealedspaceor8inches(200
mm), whichever is greater, and
be constructed using a material
that will not allowheat toescape
throughorabovethedraftcurtain.
•
for solid wood joist construction
(Fig.5)andobstructedwoodtruss
construction(Fig.7),blockingmust
beprovidedineachupperdeckand
ceilingjoistchannelatamaximum
32 feet (9,75 m) intervals. This
blockingshallbeinstalledtothefull
depthofthejoistsandbeinstalled
soastonotallowheattoescape
through or above the blocking.
Theblockingmustbeconstructed
usinganon-combustiblematerial
or the joist construction material.
Draftcurtainsmustprotrudebelow
thejoistaminimumof6inches(150
mm) or 1/3 the space, whichever
is greatest, and run parallel with
thejoistspacedat31feet(9,4m)
widthmaximumtolimittheareato
amaximumof1000ft2(93m2).The
draft curtain may be constructed
of 1/4 inch (6,4 mm) plywood to
preventheatfromescapingbeyond
thearea.
•
For non-combustible, insulation-
lledsolidwoodjoistorcomposite
woodjoistconstruction(Fig.6),the
requirement for draft curtains or
blockingdoesnotapply.
Concealed Space Size (Steel Pipe)
The minimum and maximum con-
cealed space depth is as follows:
For unobstructed wood truss con-
struction or concealed spaces of un-
obstructed bar joist construction (Fig.
4) the depth of the concealed space
is 36 inches (915 mm) maximum to 12
inches (305 mm) minimum.
For solid wood joist construction (Fig.
5), solid wood or composite wood joist
construction filled with non-combus-
tible insulation (Fig. 6), or obstruct-
ed wood truss construction (Fig. 7),
the maximum depth of the concealed
space is 54 inches from bottom of up-
per deck to top of ceiling, and the min-
imum depth is 6 inches from the bot-
tom of the upper deck joists to the top
of the ceiling joists.
System Type (Steel Pipe)
Light hazard, wet or dry pipe system
using steel pipe.
NOTES:
Use of the 4.2K sprinklers in
dry pipe systems is permitted by section
8.3.4.3 of NFPA 13 (2007 edition) where
piping is corrosion resistant or internally
galvanized.
Minimum Distance Between CC2
Sprinklers (Steel Pipe)
7 feet (2,1 m)
Maximum Distance Between CC2
Sprinklers (Steel Pipe)
12 feet (3,7 m)
Maximum Coverage Area (Steel
Pipe)
144 ft2(13,4 m2)
Deflector Position (Steel Pipe)
1-1/2 to 4 inches (40 to 100 mm) be-
low upper deck for wood truss con-
struction or concealed spaces of non-
combustible bar joist construction
(Fig. 4)
1-1/2 to 2 inches (40-50 mm) below
solid wood joist (Fig. 5) or top chord of
a wood truss that has a depth greater
than 4 inches
1-1/2 to 4 inches (40 to 100 mm) below
non-combustible insulation filled solid
wood joists or composite wood joists
(Fig. 6)
Remote Area (Steel Pipe)
The remote area for wood truss con-
struction or bar joist construction (Fig.
4) or solid wood joist construction
(Fig. 5) is 1000 ft2(93 m2) for wet pipe
systems or 1300 ft2(121 m2) for dry
pipe systems.
The remote area for non-combusti-
ble insulation filled solid wood joist
or wood composite joist construction
(Fig. 6) is to be calculated per the re-
quirements of NFPA 13.
Required Density (Steel Pipe)
0.10 gp m /f t 2(4,1 mm/min)
Minimum Operating Pressure (Steel
Pipe)
7 psi (0,48 bar)
Note: The minimum resulting flow for
the 4.2K is 11.1 gpm, and the mini-
mum resulting flow for the 5.6K is
14.8 gpm. Therefore, for coverage ar-
eas less than the maximum permitted
coverage area of 144 ft2, the 4.2K may
provide a hydraulic advantage. The
use of the CC1 sprinkler having a K
factor of 2.8, minimum operating pres-
sure of 10 psi, and resulting minimum
flow of 9.5 gpm may provide a further
hydraulic advantage for yet smaller
coverage areas when designing wet
pipe systems. The CC1 is described in
Technical Data Sheet TFP630.
Obstructions (Steel Pipe)
See Figure 8 in this data sheet for ob-
structions rules.

TFP632
Page 4 of 8
CC2
SPRINKLER
12" (305 mm)
MINIMUM
36" (915 mm)
MAXIMUM
1-1/2" (40 mm)
MINIMUM
4" (100 mm)
MAXIMUM
6" (150 mm)
MAXIMUM FOR
CPVC PIPE
FRAME ARMS OF
SPRINKLER MUST
BE INSTALLED
IN-LINE WITH
PIPE RUN
WHEN OFFSETTING CPVC PIPE OVER
AN OBSTRUCTION, A CC2 SPRINKLER
MUST BE INSTALLED DIRECTLY ON THE
CPVC PIPE OVER THE OBSTRUCTION
BOTTOM
OF PIPE
CEILING
UPPER DECK
OBSTRUCTION
4-1/2" (114 mm) MINIMUM
FROM FACE OF WOOD TRUSS
OR TOP CHORD OF BAR JOIST
TOP CHORD
4" (100 mm)
OR LESS
6" (150 mm) MAXIMUM ABOVE CEILING OR
NON-COMBUSTIBLE CEILING INSULATION,
OR 1/3 THE DEPTH OF CONCEALED SPACE
(AS MEASURED FROM TOP SURFACE OF
CEILING TO BOTTOM OF DECK ABOVE),
WHICHEVER IS SMALLER
CC2
SPRINKLER
UPPER
DECK
NON-COMBUSTIBLE
INSULATION
OBSTRUCTION
12" (305 mm)
MINIMUM
36" (915 mm)
MAXIMUM
1-1/2" (40 mm)
MINIMUM
4" (100 mm)
MAXIMUM
6" (150 mm)
MAXIMUM FOR
CPVC PIPE
COMPOSITE
WOOD JOISTS
SOLID WOOD
JOISTS
CEILING
FRAME ARMS OF
SPRINKLER MUST
BE INSTALLED
IN-LINE WITH
PIPE RUN
WHEN OFFSETTING CPVC PIPE OVER
AN OBSTRUCTION, A CC2 SPRINKLER
MUST BE INSTALLED DIRECTLY ON THE
CPVC PIPE OVER THE OBSTRUCTION
6" (150 mm) MAXIMUM ABOVE CEILING OR
NON-COMBUSTIBLE CEILING INSULATION,
OR 1/3 THE DEPTH OF CONCEALED SPACE
(AS MEASURED FROM TOP SURFACE
OF CEILING TO BOTTOM SURFACE
OF JOIST INSULATION ABOVE),
WHICHEVER IS SMALLER
BOTTOM
OF PIPE
FIGURE 2
UNOBSTRUCTED WOOD TRUSS CONSTRUCTION OR COMBUSTIBLE BAR JOIST CONSTRUCTION
CROSS SECTION ELEVATION VIEW
CPVC PIPE
FIGURE 3
NON-COMBUSTIBLE INSULATION-FILLED UPPER DECK
SOLID WOOD OR COMPOSITE WOOD JOIST CONSTRUCTION
CROSS SECTION ELEVATION VIEW
CPVC PIPE

TFP632
Page 5 of 8
CC2
SPRINKLER
12" (305 mm)
MINIMUM
36" (915 mm)
MAXIMUM
1-1/2" (40 mm)
MINIMUM
4" (100 mm)
MAXIMUM
FRAME ARMS OF
SPRINKLER MUST
BE INSTALLED
IN-LINE WITH
PIPE RUN
4-1/2" (114 mm) MINIMUM
FROM FACE OF WOOD TRUSS
OR TOP CHORD OF BAR JOIST
TOP CHORD
4" (100 mm)
OR LESS
CEILING
UPPER DECK
FRAME ARMS OF SPRINKLER
MUST BE INSTALLED
IN-LINE WITH PIPE RUN
UPPER
DECK
CC2 SPRINKLER
CEILINGCEILING
FRAMING
54" (1372 mm)
MAXIMUM
6" (152 mm)
TO
36" (914 mm)
2x FLOOR SOLID
WOOD JOISTS
2" (51 mm) MAXIMUM
1-1/2" (38 mm) MINIMUM
FIGURE 4
UNOBSTRUCTED WOOD TRUSS CONSTRUCTION
OR UNOBSTRUCTED BAR JOIST CONSTRUCTION
CROSS SECTION ELEVATION VIEW
STEEL PIPE
FIGURE 5
SOLID WOOD JOIST CONSTRUCTION
CROSS SECTION ELEVATION VIEW
STEEL PIPE

TFP632
Page 6 of 8
FRAME ARMS OF SPRINKLER
MUST BE INSTALLED
IN-LINE WITH PIPE RUN
UPPER
DECK
CC2
SPRINKLER
CEILING
FRAMING
54" (1372 mm)
MAXIMUM
6" (152 mm)
TO
36" (914 mm)
2x FLOOR SOLID
WOOD JOISTS
CEILING
NON-COMBUSTIBLE
INSULATION
4" (102 mm) MAXIMUM
1-1/2" (38 mm) MINIMUM
COMPOSITE
WOOD JOISTS
UPPER
DECK
CC2
SPRINKLER
CEILING
FRAMING
54" (1372 mm)
MAXIMUM
6" (152 mm)
TO
36" (914 mm)
2" (51 mm) MAXIMUM
1-1/2" (38 mm) MINIMUM
CEILING
TOP CHORD GREATER
THAN 4" (100 mm) IN DEPTH
FIGURE 6
NON-COMBUSTIBLE INSULATION-FILLED UPPER DECK
SOLID WOOD OR COMPOSITE WOOD JOIST CONSTRUCTION
CROSS SECTION ELEVATION VIEW
STEEL PIPE
FIGURE 7
OBSTRUCTED WOOD TRUSS CONSTRUCTION
CROSS SECTION ELEVATION VIEW
STEEL PIPE

TFP632
Page 7 of 8
Installation
The Model CC2 Sprinklers must be
installed in accordance with this
section.
General instructions
The CC2 Sprinklers are to be installed
upright and with their frame arms in-line
with the pipe run (reference Figures 1 - 9,
as applicable).
Do not install any bulb type sprinkler if the
bulb is cracked or there is a loss of liquid
from the bulb. With the sprinkler held
horizontally, a small air bubble should be
present. The diameter of the air bubble is
approximately 1/16 inch (1,6 mm) for the
175° F (79° C) temperature rating.
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7 to
14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque may distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
The Model CC2 Sprinklers must only
be installed in the upright position
with the deflector parallel to the up-
per deck. With pipe thread sealant ap-
plied to the pipe threads, use only the
W-Type 6 (End A) Sprinkler Wrench
(Fig. 9) for installation of the Mod-
el CC2 Sprinklers by applying the
wrench to the sprinkler wrench flats
only.
Care and
Maintenance
The Model CC2 Sprinklers must be
maintained and serviced in accor-
dance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, permission to shut-
down the affected fire protection sys-
tems must be obtained from the prop-
er authorities and all personnel who
may be affected by this action must
be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section).
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and devic-
es in compliance with this document,
as well as with the applicable stan-
dards of the National Fire Protection
Association (e.g., NFPA 25), in addition
to the standards of any other authori-
ties having jurisdiction. Contact the in-
stalling contractor or sprinkler manu-
facturer with any questions.
It is recommended that automatic
sprinkler systems be inspected , test-
ed, and maintained by a qualified In-
spection Service in accordance with
local requirements and/or national
codes.
WRENCH RECESS
(USE END "A"
ONLY)
0"
2-1/2"
(63,5 mm)
3-1/2"
(88,9 mm)
5-1/2"
(139,7 mm)
7-1/2"
(190,5 mm)
9-1/2"
(241,3 mm)
12"
(304,8 mm)
14"
(355,6 mm)
16-1/2"
(419,1 mm)
(0 mm)
Maximum Allowable
Distance of Deector
Above Bottom of
Obstruction
(B)
Distance from
Centerline of
Sprinkler to Side
of Obstruction
(A)
A≥3C or 3D
A≤24" (609,6 mm)
(Use dimension C or D, whichever is greater)
<12"
<(304,8 mm)
12" to <18"
(304,8 mm to <457,2 mm)
18" to <24"
(457,2 mm to <609,6 mm)
24" to <30"
(609,6 mm to <762,0 mm)
30" to <36"
(762,0 mm to <914,4 mm)
36" to <42"
(914,4 mm to <1066,8 mm)
42" to <48"
(1066,8 mm to <1219,2 mm)
48" to <54"
(1219,2 mm to <1371,6 mm)
54" to <60"
(1371,6 mm to <1524,0 mm)
NOTE:
WEB MEMBERS AND GUSSETS
SHALL NOT BE CONSIDERED
OBSTRUCTIONS PROVIDED THE
MINIMUM 4-1/2 INCH LATERAL
DISTANCE (FIG. 2) REQUIRED
BY THE SPECIFIC APPLICATION
LISTING IS MAINTAINED.
OBSTRUCTION
CC2
SPRINKLER
C
D
A
OBSTRUCTION
UPPER
DECK
LOWER
DECK
A
CC2
SPRINKLER
CC2
SPRINKLER
A
UPPER DECK
OR BOTTOM OF
NON-COMUSTIBLE
INSULATION
B
ELEVATION VIEW PLAN VIEW
C
D
OBSTRUCTION
FIGURE 9
W-TYPE 6 SPRINKLER
WRENCH
FIGURE 8
NFPA 13 OBSTRUCTION TO WATER DISTRIBUTION CRITERIA
(REFERENCE)

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
TFP632
Page 8 of 8
Copyright © 2014 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of The DuPont Corporation.
Limited
Warranty
For warranty terms and conditions,
visit www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indi-
cate the full product name and Part
Number (P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: SIN (specify), K-factor (spec-
ify), Model CC2, 175° F (79° C), Up-
right, Specific Application, Combus-
tible Concealed Space Sprinkler, P/N
(specify)
TY2189,4.2K.................. 51-311-1-175
TY3189,5.6K..................51-301-1-175
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
This manual suits for next models
2
Table of contents
Other Tyco Fire Protection Products Irrigation System manuals