Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of
Recommended Practices, Liabilities and Warranties.
IM6-08

Part II - Adjustments
Tools Needed
Models 126, 134, S126B, S134B:
Models 136-160, S136B-S164B, 680:
Models 258-274, 354-364:
Models 218-230:
Models 610-614:
Pressure Models
Vacuum Models
.
Figure 1: Models 136-160, S136B-S164B, 258-274,
and 354-364
Figure 2: Models 126, 134, S126B, S134B, 218-230,
610-614, 680
Types with Adjustable Deadband Switch (Option 1520)
Types with Manual Reset Switch (Option 1530)
“A”
ADJUSTMENT:
R.H. THREAD - TURN RIGHT
(COUNTER-CLOCKWISE) FOR HIGHER
PRESSURE SETTING
2 MT'G. HOLES.
(107.2mm)
(47.6mm)
CLEAR FOR 1/4 SCREW
8
7
1
C
16
(7.9mm)
5
4
NC
7
32
39
16
(90.5mm)
1/4 N.P.T.
PRESSURE CONNECTION
3/4 HEX
ADJUSTMENT: HOLD PLUNGER
ACROSS FLATS WITH WRENCH
TURN ADJ. SC. OUT FOR DEEPER
VACUUM SETTING.
WHEEL SPRING
COVER REMOVED IN FRONT VIEW
OPTIONAL SWITCH ADJUSTMENT:
R.H. THREAD - TURN RIGHT
(COUNTER-CLOCKWISE) FOR CLOSER
SWITCH DIFFERENTIAL
IM6-08

Dimensions
Dimensional drawings for all models may be found at www.ueonline.com.
IM6-08
Dimension A

Pressure Connections
1/2 NPT 1/4 NPT
1/4 NPT
1/4 NPT
1/4 NPT
Models S1261B-S164B Models 126-160 Models 218-230
Models 258-274 Models 354-364, 680 Models 610-614
UNITED ELECTRIC
CONTROLS
IM6-08
RECOMMENDED PRACTICES AND WARNINGS
United Electric Controls Company recommends careful consideration of the
following factors when specifying and installing UE pressure and temperature
units. Before installing a unit, the Installation and Maintenance instructions
provided with unit must be read and understood.
• To avoid damaging unit, proof pressure and maximum temperature limits
stated in literature and on nameplates must never be exceeded, even by
surges in the system. Operation of the unit up to maximum pressure or
temperature is acceptable on a limited basis (e.g., start-up, testing) but
continuous operation must be restricted to the designated adjustable range.
Excessive cycling at maximum pressure or temperature limits could reduce
sensor life.
• A back-up unit is necessary for applications where damage to a primary
unit could endanger life, limb or property. A high or low limit switch is nec-
essary for applications where a dangerous runaway condition could result.
• The adjustable range must be selected so that incorrect, inadvertent or
malicious setting at any range point cannot result in an unsafe system
condition.
• Install unit where shock, vibration and ambient temperature fluctuations will
not damage unit or affect operation. When applicable, orient unit so that
moisture does not enter the enclosure via the electrical connection. When
appropriate, this entry point should be sealed to prevent moisture entry.
• Unit must not be altered or modified after shipment. Consult UE if modifi-
cation is necessary.
• Monitor operation to observe warning signs of possible damage to unit,
such as drift in set point or faulty display. Check unit immediately.
• Preventative maintenance and periodic testing is necessary for critical ap-
plications where damage could endanger property or personnel.
• Electrical ratings stated in literature and on nameplate must not be ex-
ceeded. Overload on a switch can cause damage, even on the first cycle.
Wire unit according to local and national electrical codes, using wire size
recommended in installation sheet.
• Do not mount unit in ambient temp. exceeding published limits.
LIMITED WARRANTY
Seller warrants that the product hereby purchased is, upon delivery, free from de-
fects in material and workmanship and that any such product which is found to be
defective in such workmanship or material will be repaired or replaced by Seller (Ex-
works, Factory, Watertown, Massachusetts. INCOTERMS); provided, however, that this
warranty applies only to equipment found to be so defective within a period of 24
months from the date of manufacture by the Seller. Seller shall not be obligated under
this warranty for alleged defects which examination discloses are due to tampering,
misuse, neglect, improper storage, and in any case where products are disassembled
by anyone other than authorized Seller’s representatives. EXCEPT FOR THE LIMITED
WARRANTY OF REPAIR AND REPLACEMENT STATED ABOVE, SELLER DISCLAIMS
ALL WARRANTIES WHATSOEVER WITH RESPECT TO THE PRODUCT, INCLUDING ALL
IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR
PURPOSE.
LIMITATION OF SELLER’S LIAbILITY
SELLER’S LIABILITY TO BUYER FOR ANY LOSS OR CLAIM, INCLUDING LIABILITY
INCURRED IN CONNECTION WITH (I) BREACH OF ANY WARRANTY WHATSOEVER,
EXPRESSED OR IMPLIED, (II) A BREACH OF CONTRACT, (III) A NEGLIGENT ACT OR
ACTS (OR NEGLIGENT FAILURE TO ACT) COMMITTED BY SELLER, OR (IV) AN ACT FOR
WHICH STRICT LIABILITY WILL BE INPUTTED TO SELLER, IS LIMITED TO THE “LIMITED
WARRANTY” OF REPAIR AND/OR REPLACEMENT AS SO STATED IN OUR WARRANTY
OF PRODUCT. IN NO EVENT SHALL THE SELLER BE LIABLE FOR ANY SPECIAL, IN-
DIRECT, CONSEQUENTIAL OR OTHER DAMAGES OF A LIKE GENERAL NATURE,
INCLUDING, WITHOUT LIMITATION, LOSS OF PROFITS OR PRODUCTION, OR LOSS OR
EXPENSES OF ANY NATURE INCURRED BY THE BUYER OR ANY THIRD PARTY.
UE specifications subject to change without notice.
This manual suits for next models
10
Table of contents
Other UE Switch manuals

UE
UE ONE Series User manual

UE
UE B117 Technical specifications

UE
UE J21K User manual

UE
UE 120 Series User manual

UE
UE 100 Serie User manual

UE
UE Field Safety System One Series User manual

UE
UE ONE Series User manual

UE
UE 117 Series User manual

UE
UE ONE Series Installation and operating instructions

UE
UE 12 Series User manual