UE Field Safety System One Series User manual

IM_ONE_Safety-07
www.ueonline.com 1
GENERAL
MISUSE OF THIS PRODUCT MAY CAUSE EXPLOSION AND PERSONAL INJURY. THESE INSTRUCTIONS MUST BE THOROUGHLY READ AND UNDERSTOOD
BEFORE UNIT IS INSTALLED. SEE THE PRODUCT NAMEPLATE INFORMATION FOR SPECIFIC AGENCY CERTIFICATIONS APPLICABLE TO YOUR PRODUCT.
SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN HAZARDOUS LOCATIONS.
FOR ZONE HAZARDOUS LOCATIONS, ALL CABLE ENTRY DEVICES SHALL BE CERTIFIED IN TYPE OF EXPLOSION PROTECTION FLAMEPROOF ENCLOSURE “d”
WITH AN IP66 RATING, SUITABLE FOR THE CONDITIONS OF USE AND CORRECTLY INSTALLED. IF CABLES AND CABLE GLANDS ARE NOT USED, A STOPPING
BOX SHALL BE PROVIDED WITHIN 2” (5CM) OF THE ENCLOSURE. FLAMEPROOF JOINT AND GAP DETAILS ARE PROVIDED ON PAGE 2.
INSTALL UNITS WHERE SHOCK, VIBRATION AND TEMPERATURE FLUCTUATIONS ARE MINIMAL. ORIENT UNIT TO PREVENT MOISTURE FROM ENTERING
ENCLOSURE. USE PROPERLY RATED SEALING FITTINGS FOR ELECTRICAL WIRE ENTRY. DO NOT MOUNT UNIT IN AMBIENT TEMPERATURES EXCEEDING
PUBLISHED LIMITS. THIS IS ESPECIALLY CRITICAL FOR LOCAL MOUNT TEMPERATURE UNITS. USE OF A SHROUD IS RECOMMENDED WHERE DIRECT SUNLIGHT
AND RAIN MAY COME IN CONTACT WITH THE ENCLOSURE.
IN ORDER TO MEET THE ELECTROMAGNETIC COMPATIBILITY REQUIREMENTS SPECIFIED IN EN61000-6-2: IMMUNITY FOR INDUSTRIAL ENVIRONMENTS,
EXTERNAL WIRING MUST BE RUN USING CABLE WITH A GROUNDED SHIELD OR CABLE RUN INSIDE OF A GROUNDED METAL CONDUIT
INTERFERENCE FROM IMPROPERLY SHIELDED VFD’S (VARIABLE FREQUENCY DRIVES) AND MOTOR CONTROLLERS MAY CAUSE NUISANCE TRIPS.
DURING INSTALLATION, MARK THE BOX NEXT TO EACH PROTECTION METHOD ON THE NAMEPLATE THAT APPLIES TO YOUR APPLICATION.
THIS EQUIPMENT IS CERTIFIED IN ACCORDANCE WITH THE REQUIREMENTS OF THE FOLLOWING APPLICABLE STANDARDS (SEE TABLE 1) AND
IS SUITABLE FOR USE IN NON-HAZARDOUS AND THE FOLLOWING HAZARDOUS LOCATIONS, AND IS ATEX AND IECEX CERTIFIED SUITABLE FOR
APPROPRIATE USE IN GAS AND DUST ZONE 1 APPLICATIONS.
Model 2SLP N. America Europe International
Flameproof
Cert Number: UL File E226592 DEMKO 09 ATEX 0813748X IECEx UL 08.0017X
Applicable
Standards
UL 50, UL 50E, UL 61010-1, UL 1203, CSA C22.2 No.
25-1966, CSA C22.2 No. 30-M1986, CSA C22.2 No.
94.01-07, CSA C22.2 No. 94.02-07, CSA C22.2 No.
61010-1, UL 60079-0, UL 60079-1, CSA 22.2 No.
60079-0:11, CSA 22.2 No. 60079-1:11
EN 60079-0: 2012 + A11:2013
EN 60079-1:2014
EN 60079-31:2014
IEC 60079-0, Ed.6 (2011-06)
+ Corr.1 (2012-01) + Corr.2
(2013-12)
IEC 60079-1:Ed.7
IEC 60079-31:Ed.2
Suitable for
appropriate use in:
Class I, Div. 1, Groups A, B, C & D
Class II, Div. 1 Groups E, F & G
Class III
Class I, Zone 1 AEx db IIC T3/T5*
Ex d IIC T3/T5*
II 2 G Ex db IIC T3/T5* Gb
II 2 D Ex tb IIIC T90°C Db
IP66
-40°C ≤ TAMB ≤ +70°C
Ex db IIC T3/T5* Gb
Ex tb IIIC T90°C Db
IP66
-40°C ≤ TAMB ≤ +70°C
*Straight pressure sensor models P06-P16 have a temperature class of T3, all others T5
FLAMEPROOF AND DUST-IGNITION PROOF - SPECIAL CONDITIONS FOR SAFE USE
• Field wiring must be rated 105°C minimum. For ambient temperatures below -10°C, use suitable field wiring.
• Blanking elements from factory have been tested for flameproof “d” and dust “tb” with the enclosure as an assembly and carry no markings.
• A suitable thermowell made from corrosion-resistant material and engaging 5 threads minimum (with thread sealant) is required for the local
spring loaded temperature sensor to maintain IP66
One Series Field Safety System™
Electronic Pressure, Differential Pressure,
and Temperature Transmitter Switch
Model: 2SLP
UNITED ELECTRIC
CONTROLS
Installation and Maintenance
Instructions
IM_ONE_Safety-07
Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of Recommended
Practices, Liabilities and Warranties. All Warnings are translated to French and can be found of pages 22 and 23.
Table 1

IM_ONE_Safety-07
www.ueonline.com
2
Flameproof joint and gap details
– Enclosure to cover threaded joint: 4”-16 UN-2, 7 threads engaged minimum
– Glass to cover cemented joint: 0.753” (19.1 mm) rabbet/spigot minimum length
– Breather element threaded joint: M8-1.25 (6g/6H medium fit class), 11 threads engaged minimum
– Electrical conduit threaded joint: 3/4”-14 NPT, 5 threads engaged minimum
– Enclosure to sensor threaded joint:
• Pressure models: 1”-20 UNEF-2, 10 threads engaged minimum
• Temperature models: 1/2”-14 NPT, 5 threads engaged minimum
• Remote and local spring loaded temperature sensor gap joints: 0.0045” (0.114 mm) maximum annular gap by
1.25” (31.8 mm) minimum length
• The device must be cleaned with a damp cloth to avoid static discharge.
Dual Seal Adaptor (Option M041)
• Threaded Dual Seal Adaptor Option Enclosure to One Series Field Safety System™ Enclosure: 1”-20 UNEF-2, 10 threads engaged
minimum
• Breather element threaded joint: 1/4”-20 UNC-2, 10 threads engaged minimum
• Secondary Seal Housing to union housing joint: 0 .580” (14.73 mm) rabbet/spigot minimum length, maximum annular gap 0.003“
(0.08 mm)
• Sensor to union housing joint: 0 .580” (14.73 mm) rabbet/spigot minimum length, maximum gap 0.003” (0.08 mm)
• Threaded Dual Seal Adaptor option to Sensor: 1”-20 UNEF-2, 10 threads engaged minimum or 1/2”-14 NPT 5 threads engaged
minimum.
CONTINUOUS OPERATION SHOULD NOT EXCEED THE DESIGNATED OVER RANGE PRESSURE OR MAXIMUM WORKING PRESSURE
STATED WITHIN THE LITERATURE AND ON DEVICE NAMEPLATE.
Over Range Pressure: The maximum pressure to which a pressure sensor may be continuously subjected without cause damage and
maintaining set point repeatability.
Max Working Pressure: The maximum that can be applied to both process ports simultaneously without affecting sensor performance.
The One Series transmitter-switch product line is based on an all-solid-state electronic module that incorporates a microprocessor.
The One Series Field Safety System™ is a loop-powered, all-in-one device connected directly to the final element and replacing a
transmitter, safety relay, trip amplifier, and logic solver. It has an embedded high capacity, programmable safety relay that provides
extremely fast response time in the event an emergency shutdown of a final control element is triggered. The One Series Field
Safety System™ incorporates UE’s patented IAW™ self-diagnostics, redundant and diverse signal processing, and software algo-
rithms to detect abnormalities in the process, and internal faults within. The device meets the latest IEC 61508 standard for SIL 2
SIS and the requirements of SIL 2 for random integrity at HFT = 0, SIL 3 for random integrity at HFT = 1, and SIL 3 for systematic
capability.
Not all abnormal conditions require emergency shutdown, so the One Series Field Safety System™ provides additional logic
outputs for use in voting logic schemes that could report warnings prior to a shutdown. This feature provides the ability to balance
safe working environments with process throughput when conditions permit it.
The One Series Field Safety System™ provides an explosion-proof type 4X/IP66, weather-tight enclosure suitable for harsh envi-
ronments and hazardous (Class I, Division 1, Zone 1) locations. Repeatability rivals that of a process transmitter, with a 0.1% of
full range while the switch set point and deadband (hysteresis) of the Safety Relay Output are fully programmable over the entire
range of the sensor. Reaction time for the One Series Field Safety System™ to a process change is less than 100 milliseconds.
When filter settings are set to “OFF,” switch status and Safety Relay Output are moved to the safe state (open position) in less than
100 milliseconds, and the 4-20 mA output stabilizes to 90% of a step response within 250 milliseconds.

IM_ONE_Safety-07
www.ueonline.com 3
I Am Working (IAW™)
The One Series Field Safety System™ also contains UE’s patented IAW™ self-diagnostic software. On a continuous basis, the IAW™ algorithm
checks for proper operation, and locally reports the status using messages or revolving arrows on the display. For remote reporting, a discrete
IAW™ output signal can be monitored by logic solver and used to detect normal, tripped, and fault conditions. A discrete outputs truth table is
provided on page 18. IAW™ self-monitors, searching for possible faults, both within the instrument and in the overall system (a list of the various
fault codes is outlined in table 5, page 17). In the event of a fault condition, the One Series Field Safety System™ will attempt to display the problem and
provide remote indication signals using the IAW Status and NAMUR NE43 standard 4-20 mA outputs. In the case of certain micro-controller faults, the revolving
arrows may freeze or go out, indicating that a failure exists. If loop power is interrupted to the One Series Field Safety System™, the display will go blank
and all discrete outputs will open.
DISPLAY FEATURES AND DIAGNOSTICS
The One Series Field Safety System™ features a large, easy to read LCD display (See Figure 1). It is used for three main purposes: process
indication, programming and switch status/troubleshooting.
In the Process Display mode, the display may be indicating the following:
• Current process value and units of measure: A value will be displayed as long as the reading is within 103% of the full
scale range noted on the nameplate. For valves beyond 103% of range, the PV is replaced with a scrolling message OVER RANGE.
• I Am Working (IAW™) status: When the unit is working properly, a circular 4-segment arrow will be revolving around the letters “IAW™” in
the top center of the display.
• Offset/Span Adjustment: The word “offset” will appear above the process value, indicating that the factory offset and/or span
calibration has been modified by the user.
In addition, the user can easily access information such as the set point, deadband and minimum/maximum process readings:
By pushing the right gbutton once, the display will scroll as follows:
SP1 XX.XX DB1 XX.XX SP2 XX.XX DB2 XX.XX
By pushing the left 2button once, the display will scroll the min/max process values recorded in memory:
MAX XX.XX MIN XX.XX
The display will automatically revert back to the Process Display mode after scrolling.
ALARM CONDITION
When the process goes beyond the set point, the display will begin to flash, alternating between the process value and “SW1”. This indicates that
set point has been reached, causing the Safety Relay Output (SRO) and Status Switches to open. The display will continue to flash until the process
has returned to a value beyond the deadband, at which point the display will revert to normal operation and process value display. If the unit was
programmed to have a latching output, a small “Latch” icon will light in the display when the set point is reached, indicating that the output is
latched and needs to be manually reset.
FAULT CONDITIONS
In the case of a fault condition, the display may indicate the following:
• If the IAW software detects a fault it will display an error code and force the SRO, SRO Status and IAW Outputs to open state and the 4-20 mA output to the
fault current.
• If the power supply or the wiring fails, the display will go blank. All switch outputs will open (fail safe open) and the 4-20 mA signal will go to zero.
(See the Fault Codes and the Discrete Output Truth Table on pages 17 and 18 for a complete description of fault diagnostics and the response by the One Series
Safety Transmitter.)
Please refer to the product technical brochure for product specifications. Product technical brochure may be found at www.ueonline.com.
UE declarations and third party issued certifications are available for download at www.ueonline.com/support/certifications/.
Date code format on nameplate is “YYWW” for year and week (see Figure 19, Page 18)
PART I - MOUNTING
Tools Required: Screwdriver for mounting bolts; 4 mounting bolts (1/4”Max.)
NOTE: For optional surface and pipe mounting kit, order part no. 6361-704. See page 20.
BEFORE INSTALLING, CHECK THE SENSOR MODEL SELECTED FOR COMPATIBILITY TO THE PROCESS MEDIA IN CONTACT WITH THE SENSOR
AND WETTED PARTS.
IN ALL APPLICATIONS, SECURE THE ENCLOSURE AS DETAILED BELOW. DO NOT MOUNT VIA THE PROCESS CONNECTION ONLY.
Figure 1

IM_ONE_Safety-07
www.ueonline.com
4
Mount the device using the four (4) 1/4” clearance holes in the enclosure base. Plumb sensor to the process port. See page 20-21 for dimensions.
The device may be mounted in any position except with the sensor connection facing up. Ensure the process connection is sealed to the process
port to prevent leakage. Care should be taken to minimize effects of shock and vibration. The One Series should be protected from direct sunlight
and rain in outdoor installations using a shroud (user supplied). NOTE: the optimal display viewing position is 6:00.
FOR PRESSURE AND LOCAL TEMPERATURE MODELS ALWAYS HOLD A WRENCH ON THE SENSOR HOUSING HEX WHEN MOUNTING DEVICE. DO
NOT TIGHTEN BY TURNING ENCLOSURE, THIS WILL DAMAGE THE CONNECTION BETWEEN THE SENSOR AND HOUSING.
FOR DIFFERENTIAL PRESSURE MODELS (ESPECIALLY LOW RANGE MODELS), MOUNT THE SENSOR LEVEL TO MINIMIZE ANY PRESSURE
READING OFFSETS. THE OFFSET COMMAND MAY BE USED TO ZERO THE DISPLAY, (SEE PAGE 13 FOR ADDITIONAL INFORMATION).
PROCESS CONNECTIONS AND SENSOR INSTALLATION
NEVER INSERT ANY OBJECT INTO THE PRESSURE SENSOR OPENING. DAMAGE TO THE SENSOR WILL RESULT, AFFECTING ACCURACY.
Pressure and Differential Pressure Models
To pipe mount: Thread the pressure connection onto the pressure port, with thread sealant, making sure that the mating threads are clean and
free of debris. Use a wrench on the pressure connection hex to tighten. Test for leaks. On Differential Pressure models, the Low (L) side pressure
must NOT exceed the high (H) side pressure. Damage to the sensor may result.
Local and Remote Temperature Models
For Local Ambient Sensing (model L): Mount using the mounting holes on the electronics housing. Mount the device to ensure that the sensor
housing will not be damaged and where the measured temperature is representative of the surrounding environment.
For Local Spring-Loaded (model T): A suitable thermowell, made from corrosion-resistant material, 5 threads engaged minimum, with thread
sealant, is required to maintain enclosure type 4X/IP66.
For Remote Sensing: Route the extension wire to avoid contact with live components or close proximity to electrical noise sources. Avoid kinks, or
excessive flexing. Tighten the ferrule fitting, if applicable.
For Surface Sensing: Secure the sensor housing to the pipe or vessel using an adhesive or strapping method suitable for the application.
For Immersion Sensing (models C, H, R & L): Use of a thermowell is highly recommended to aid in maintenance, testing and preservation of the
system integrity. For existing thermowells with 0.375” bore, an insert is available from UE as part number 62169-44 (see Figure 2). The adapter provides a
faster heat transfer by adapting the 0.250” diameter temperature sensor housing to a larger bore 0.375” thermowell. Heat transfer compound is recommended
in the bottom of the well and inside the adapter opening.
Insert the sensor housing (0.25”diameter) into the well ensuring that the sensor’s sheath bottoms out and the well is completely immersed in
the media (2.5”min.) Screw the sensor’s nipple into the thermowell, with thread sealant, by placing a wrench on the union nut. Tighten the union
connector.
For best temperature measurements, the sensor housing must be in full contact with the surface or media being measured. Heat transfer compound
may be used to aid in fully transferring the media temperature to the sensor housing. Locate where the temperature is most representative of the
system. Minimum insertion depth is 2-1/2”. Sensor dimensional drawings are shown on page 21.
0.375 REF
0.250
REF
2.50
REF
SENSOR
THERMOWELL ADAPTER
[6.35] mm
[63.5] mm
[9.53] mm
Figure 2

IM_ONE_Safety-07
www.ueonline.com 5
PART II - WIRING
Removing the One Series Field Safety System™ Enclosure Cover and Display Module
TO PREVENT ELECTROSTATIC DISCHARGE WIPE DOWN COVER AND ENCLOSURE OF ANY DUST BUILD-UP BEFORE REMOVING COVER.
DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING DEVICE. WIRE DEVICE IN ACCORDANCE WITH LOCAL AND
NATIONAL ELECTRICAL CODES. MAXIMUM RECOMMENDED WIRE SIZE AND RECOMMENDED TIGHTENING
TORQUE FOR FIELD WIRING TERMINAL BLOCKS ARE SHOWN WITHIN TABLE 2 (PAGE 5).
TO PREVENT SEIZURE OF ENCLOSURE COVER, DO NOT REMOVE LUBRICANT. THREADS SHOULD ALSO BE FREE OF DIRT
AND OTHER CONTAMINANTS.
Remove the enclosure cover by turning it counter-clockwise for 8 revolutions (Figure 3). Carefully remove the display
module by grasping the outer edge and pulling it away from the base enclosure (Figure 4), being careful not to
strain any of the wired connections. Allow the display module to hang from the wired connections to access the base
enclosure and terminal blocks for wiring. Do not remove the display module wire assemblies. Insert the field wiring
through the conduit opening(s) of the base enclosure. Make the connections as shown within the wiring diagrams
(Figure 5-6, page 6). The primary chassis and equipment grounding terminal is provided inside the
base enclosure.
Cleaning the display and keypad surface should be performed with a damp cloth only. Do not attempt to wash down
the One Series with the cover removed.
Tools Required: Small flat-head screwdriver; wire strippers
TO PREVENT IGNITION, DISCONNECT POWER BEFORE REMOVING ENCLOSURE COVER. KEEP COVER TIGHT WHILE IN OPERATION. DO NOT
DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
DO NOT REPLACE COMPONENTS UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
THE DEVICES SHALL BE PROPERLY GROUNDED IN THE END USE APPLICATION USING THE GROUND SCREWS PROVIDED WITH THE
ENCLOSURE.
FIELD WIRING MUST BE RATED 105°C MINIMUM. FOR AMBIENT TEMPERATURES BELOW -10°C, USE SUITABLE FIELD WIRING.
MODEL 2SLP IS LOOP-POWERED AND OBTAINS OPERATING POWER FROM THE 4-20 mA LOOP. THE POWER SUPPLY PROVIDING POWER TO THE LOOP
MUST BE CLASS 2 OR SELV AND CURRENT LIMITED. THE MAXIMUM LOAD RATING FOR THE SAFETY RELAY OUTPUT (SRO) IS SHOWN IN TABLE 3 ON PAGE
6. OVERLOADING THE SAFETY RELAY OUTPUT (SRO) MAY CAUSE FAILURE. THE SRO MUST NOT BE CONNECTED DIRECTLY TO A POWER SUPPLY WITHOUT
A SUITABLE SERIES LOAD.
Terminal Block and Torque Details
Description Max. Wire Gauge Min. Wire Gauge Recommended Tightening Torque
TB1 3-Position 14 AWG 22 AWG 3.50 in-lbs. or 0.4 Nm
TB2 4-Position 14 AWG 26 AWG 3.50 in-lbs. or .4 Nm
TB3 2-Position 16 AWG 26 AWG 2.2 in-lbs. or .25 Nm
TB4 2-Position 16 AWG 26 AWG 2.2 in-lbs. or .25 Nm
NOTE: The sensor’s 4-conductor ribbon cable assembly must remain connected to the display module with the red wire oriented to the arrow on
the label at the rear of the module. Reversing this connector will result in measurement errors or failure. Please refer to the wiring diagrams
beginning on page 6.
Figure 3
Figure 4
Table 2

IM_ONE_Safety-07
www.ueonline.com
6
The One Series Field Safety System™ enclosure includes two conduit openings,
one intended for the high-power SAFETY RELAY OUTPUT (SRO) wiring and the
other intended for low-level signal and analog 4-20 mA wiring. 4-20 mA signals
shall be wired using a shielded/twisted pair to minimize the effects of electrical
interference. Please follow local electrical code requirements for explosion/flame
proof instrumentation.
The diagrams in Figures 5 and 6 provide a rear view of the display module after
it has been removed from the base enclosure and an inside view of the base
enclosure circuit boards. Terminal Block 1 (TB1) is located on the display module.
All other terminal blocks (TB2 - TB4) are located inside the base enclosure.
Model 2SLP is loop-powered and is connected directly to an analog input of a PLC
or DCS via TB1 providing a 4-20 mA analog signal (see Table 3). (Polarity must
be observed). The loop connection powers the entire One Series Field Safety
System™, including the Safety Relay Output switch actuation. The auxiliary SAFETY
RELAY OUTPUT is connected via TB2 and is intended to switch an external load.
Refer to Table 3 for the SAFETY RELAY OUTPUT switch ratings.
Figure 6 shows the switch wiring connections located at TB2, TB3 and TB4 inside
the base enclosure. TB2 A and B terminals are provided for the external power
supply inputs to be switched by the Safety Relay Output. The SRO at TB2 C and D
terminals provide connections to the Safety Relay Output switch. Polarity must be
observed on all VDC switches. Please refer to the wiring diagrams shown on page
7.
The SRO Monitor function, if used, requires a connection to VDC (+) or VDC (-)
depending on whether the SRO circuit arrangement is sinking or sourcing (either
Neutral1 or Neutral2 for model 2SLP47). This connection allows the SRO current
to be measured that is sent out to an external load (final element), allowing the
IAWTM diagnostics to determine the integrity of the SRO wiring and if the SRO is
functioning properly.
NOTE: As an alternative to loop power, model 2SLP may be wired directly to a
24 VDC power supply (+) and minus (-) terminals. In this wiring configuration,
power is provided for all switching and diagnostic functions but a 4-20 mA output
is not possible. This alternative method of powering the One Series Field Safety
System™ may be used when loop power is not available and a 4-20 mA output is
not desired.
Two additional discrete outputs are available at TB3 and TB4 - SRO STATUS and
IAW OUTPUT. These are intended for use in Safety Instrumented Systems (SIS)
applications and for monitoring certain One Series Safety Transmitter functions.
These discrete signals are useful for voting logic schemes where the safety PLC can
decide to initiate an emergency shutdown (ESD) or an alarm depending on their
state. These outputs may also be used to distinguish between a process upset
(set point reached) or the IAW™ self-diagnostics detecting a fault with the One
Series Field Safety System™. Please refer to table 4 on page 15 for additional
information.
NOTE: Do not exceed the maximum switch ratings of the SAFETY RELAY OUTPUT,
IAW™ OUTPUT and SRO STATUS signals or permanent damage to the One Series
Field Safety System™ may result. Please refer to Table 3.
WIRING DIAGRAMS - MODEL 2SLP
+
+
TB 2
+
-
RED
TB1
+
+
TB4
TB3
TB 2
TB2
TB 2
TB4
TB3
TB 2
SRO/SWITCH STATUS
TB2
IAW OUTPUT
SAFETY
RELAY
OUTPUT
+TB4-2
-TB4-1
+TB3-2
-TB3-1
NEUTRAL 1
NEUTRAL 2
LINE
SRO
Table 3 – Voltage and Current Maximum Ratings
Signal Name Location 2SLP47 2SLP48 2SLP49
Power Supply TB1: + & - 2-wire 20-40 VDC @ 4-20 mA (Loop or Fixed Current)
Safety Relay Output TB2: C & D 12-250 VAC @ 5 mA-5 A10-30 VDC @ 6 A1, 1.8 A1Pilot Duty 0-130 VDC @ 2.5 A1, Q1501,2 Pilot Duty
With Relay Monitor Enabled 12-250 VAC @ 5 mA-5 A110-30 VDC @ 5 mA-6 A110-130 VDC @ 5 mA-2.5 A1
Temperature Derating 11% per ˚C above 25˚C
SRO Status TB3: 1 & 2 30 VDC @ 20 mA
IAW Output TB4: 1 & 2 30 VDC @ 20 mA
2Q150 Pilot Duty: 2.5 A (Continuous Current), 0.55 A (Make or Break), 69 VA
Figure 5 - Rear View Display Module
Figure 6 - Inside View Base Enclosure

IM_ONE_Safety-07
www.ueonline.com 7
+
-
RED
TB1
Logic Solver
Analog Inputs
Ain1+
24 VDC Loop
Power
+
-
RED
TB1
Power Supply
24 VDC
+
Power Options
Loop Powered by the 4-20 mA signal. Use this configuration for 2-wire
transmitter only function (Figure 7). NOTE: If IAW is not monitored,
the SFF of the device is reduced. Reference the product FMEDA report.
www.ueonline.com/techinfo/one_series_st_fmeda_report.pdf
DC power supply – The device is powered using the 4-20 mA signal
connections. All other outputs Safety Relay Output, SRO Status and IAW
Output function as normal. NOTE: The 4-20 mA analog signal is not
possible in this wiring configuration.
In this configuration the 4-20 mA output and IAW Output are monitored by the
safety system logic solver. The final element is controlled by the logic solver. Total
wire connections = 4. The 4-20mA signal is used by the logic solver to initiate
the safety function. IAW provides a separate indication of device health. NOTE:
If IAW is not monitored, the SFF of the device is reduced. Reference the product
FMEDA report.
www.ueonline.com/techinfo/one_series_st_fmeda_report.pdf
+
TB 2
+
-
RED
TB1
Logic Solver
Analog Inputs
Ain1+
24 VDC
24 VDC Loop
Power
Logic Solver
Discrete Inputs
Din1+
Din2+
DC Com
Wiring Diagrams
Figure 7
Figure 8
Figure 9
Figure 10

IM_ONE_Safety-07
www.ueonline.com
8
TB 2
Logic Solver
Discrete Inputs
Din1+
Din2+
DC Com
TB 2
Logic Solver
Discrete Inputs
Din1+
Din2+
DC Com
TB 2
Logic Solver
Discrete Inputs
Din1+
Din2+
DC Com
Internal
Jumper
SRO
SRO
SRO
VDC
VDC
+
-
+
-
+
-
+
-
Final
Element
Final
Element
+ VDC - VDC
Final
Element
+ VDC - VDC
TB4
TB4
TB3
TB3
2SLP47 Wiring Options
2SLP48 and 2SLP49 Wiring Options
Current Sourcing SRO
Current Sinking SRO
OR
L1 (H) L2 (N)
Optional
Connections
Optional
Connections
Optional
Connections
TB4
TB3
The following wiring diagrams show the One Series Field Safety System™ fully configured where the health status (IAW) and SRO switch status signals are
being monitored by a logic solver (PLC or DCS). These connections are not required; however, UE recommends monitoring the IAW signal to maximize the safe
failure fraction in an SIS application. Additionally, wiring the SRO to an external load (final element) is not required.
For direct control of a final element from the One Series Field Safety System™, Figures 11-13 show the recommended SRO wiring methods. The wiring con-
nection shown at TB2 – A+B is required for proper operation of the SRO Monitor diagnostics only if this feature is turned ON in the menu. The default factory
setting for SRO Monitor is OFF.
Figure 11
Figure 12
Figure 13

IM_ONE_Safety-07
www.ueonline.com 9
0
200
400
600
800
1000
1200
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
R
series
V
supply
Power Supply and Load Limits
Rmin
Rmax
Vin Rmin Rmax
20 0.0 181.8
21 0.0 227.3
22 0.0 272.7
23 0.0 318.2
24 0.0 363.6
25 47.6 409.1
26 95.2 454.5
27 142.9 500.0
28 190.5 545.5
29 238.1 590.9
30 285.7 636.4
ONE SERIES 4-20mA POWER SUPPLY AND LOAD LIMITS
Vin Rmin Rmax
31 333.3 681.8
32 381.0 727.3
33 428.6 772.7
34 476.2 818.2
35 523.8 863.6
36 571.4 909.1
37 619.0 945.5
38 666.7 1000.0
39 714.3 1045.5
40 761.9 1090.9
No Fault Displayed
4-20 mA Normal Operating range Unused
Fault < 3.6
3.8 mA Normal
Under-range
420
20.5 mA Normal
Over-range
21.0 mA*
*21.0 mA only when the temperature
sensor is subject to 103.25% to 110%
of range or when the pressure sensor
is subject to 103.25% to 150% of
range.
Fault
0
FAULT CURRENT
In addition to the discrete IAW™ and Safety Relay Output status signals, the One Series Field Safety System™ includes a 4-20 mA output that
adheres to the NAMUR NE 43 current level standard. Figure 14 deatails these current levels and what they indicate.
A diagnostic fault will force the IAW™ Safety Relay Output and Status to the fail safe state and the (≤ 3.6 mA) fault condition.
Table 4
Graph 1
Figure 14

IM_ONE_Safety-07
www.ueonline.com
10
PART III - PROGRAMMING
Basic Programming
Tools Required: Programming Flowchart (see Flowchart 1, page 19)
Programming of the One Series Field Safety System™ is accomplished using the two buttons on the faceplate (labeled 2and g
see Figure 15). Stepping down through the main menu using the left 2button, you can access the various commands of the software
menu. The right button is then used to move into the command submenu for setting up or modifying the parameters.
NOTE: The flowchart on page 19 shows the enitre programming commands menu structure. Before removing the enclosure cover,
please read the instructions on page 5. The programming menu is a single direction lop, with submenus embedded within, so there is
no way to back up in the program. If you need to make a correction to a prior Main Menu step, you will need to continue forward, exit,
then re-enter the program to step through to the appropriate feature. If you are in a Submenu, you will need to continue to the begin-
ning of the menu item and re-enter the Submenu to make the correction.
Entering the Programming Mode
NOTE: While in the Programming Mode, the One Series Field Safety System™ will remove itself from service (go offline). All out-
puts are set to the fail safe state and the Field Safety System™ ignores process variable input from the process sensor. The Safety
Relay Output and Status, and the IAW™ Output signal will open. The control system will interpret these signals as a detected fault and
a process upset (set point reached) simultaneously. It is essential to alert the control system operators before entering the
Programming Mode.
Use the Flowchart on page 19 as a guide through the various commands in the Programming Mode.
• Press and release both buttons 2g simultaneously and then press the right button gto enter the password.
• Enter the 4-digit password. The factory defualt password is “0000”.
• The left 2button increments the blinking digit.
• The right gbutton sets the digit and moves to the next.
• Once a valid password is entered, “OK” will appear on the display.
• Press and release the right gbutton.
• CLR MAX/MIN (or MAN RSET if Latch is set) will appear on the display.
This is the first command prompt in the Programming Mode.
NOTE: The Field Safety System™ will automatically exit the Programming Mode and resume monitoring the process (go back online)
if two minutes elapse without a button being pressed. The One Series recalls all previously saved parameters from memory and any
program changes that were made will be discarded. This two-minute timeout feature prevents the One Series from being left offline
accidentally.
Exiting the Programming Mode
When any of the programming commands are displayed, it is possible to escape and exit the Programming Mode by pressing the left
2and right gbutton simultaneously. Doing this redirects the program to the Save Changes menu location, which is only possible at
menu actions indicated by an asterisk (*) on the Programming Flowchart, found on page 19.
NOTE: It is also possible to exit the Programming Mode by repeatedly pressing the left 2button from any programming command until
the Save Changes menu location is reached.
Saving Programming Changes
When changes have been made to the programming settings, a choice is provided to Save or Discard the changes. At any prompt:
• Press both left 2and right gbuttons to display SAVE CHNG menu.
To Save changes, press the right gbutton. NO (the default) will be displayed.
• Press the left 2button to toggle and display YES.
• Then press both left 2and right gbuttons to confirm, save the changes and return to the Process Display mode.
The One Series will resume process monitoring (go back online) using the new programming parameters.
To Discard changes, press the right gbutton. NO will be displayed.
• Press both left 2and right gbuttons to confirm, discard changes and return to the Process Display mode.
The One Series will resume monitoring the process (go back online) recalling all previously saved parameters from memory.
Figure 15

IM_ONE_Safety-07
www.ueonline.com 11
BASIC FEATURES
Setting the Units of Measure
The One Series Field Safety System™ allows the units of measure to be set in the field. The default units are pounds per square inch
(PSI) for pressure models and degrees Fahrenheit (˚F) for temperature models.
• To change the units of measure, enter the programming mode. Press the left 2button. The display will scroll SET UNITS.
• Press the right gbutton and the display will read the default units psi or˚F.
• Repeatedly press and release the left 2button to select from the available choices. Stop at the desired choice.
• Press the right gbutton to make the selection. The display will return to “Set Units.”
• Press the left 2button to continue on in the menu or press both left 2and right gbuttons to exit the Programming Mode and
save changes.
NOTE: MAX/MIN memory is reset (changed to zero) whenever the units of measure have been changed. Set Point, Deadband, Offset,
Span, Plug Port, and 4 mA and 20 mA values are recalculated for the newly selected units of measure.
Setting the Safety Relay Output Mode, Set Point and Deadband
Please refer to the Programming Flowchart, page 19.
NOTE: The One Series Field Safety System™ is intended for use in functional safety applications. As a result, the Safety Relay Output
(SRO) was designed to fail safe (open) if power is lost to the One Series Field Safety System™ or if a fault is detected by the IAW
self-diagnostics.
• Enter the programming mode (see page 10).
• Press and release the left 2 button until SW1 appears on the display.
• Press the right g button. The previously selected mode will appear. OPEN RISE is the factory default.
NOTE: The One Series Field Safety System™ has three operating modes:
OPEN RISE - The Safety Relay Output opens on rising process values that reach the set point.
OPEN FALL - The Safety Relay Output opens on falling process values that reach the set point
OPEN WINDOW - The Safety Relay Output opens when process values are within a specified range set by two points, set point high and
set point low.
Please use the Safety Relay Output Decision Logic (Figure 13, page 12) for help with setting the appropriate Safety Relay Output mode.
• Press and release the left 2button until the desired mode appears.
• Press the right gbutton to select the mode and move on to the set point. SP will appear.
NOTE: The set point is the process value at which the One Series Field Safety System™ opens the Safety Relay Output. The Set Point
is fully programmable throughout the operating range of the sensor as noted on the device nameplate.
• Press the right gbutton to select a positive or negative set point. POS is the default. Use the left 2button to change to NEG.
• Press the right gbutton to view and change the set point. Press the left 2button to increment the blinking digit. Press the right
gbutton to enter and move to the next digit.
• Press the right gbutton to enter a new Deadband. DB will show on the display.
NOTE: The Deadband is the amount above or below the set point at which the One Series Field Safety System™ resets the Safety
Relay Output, returning it to the normally closed state. Deadband is represented as a value which is added or subtracted from set point,
depending on the control mode.
• Example 1: If the Control Mode is OPEN RISE and the set point is 100 and the deadband is 10, the Safety Relay Output will open as
pressure rises to 100 and close (reset) as the pressure falls to 90.
• Example 2: If the Control Mode is OPEN FALL and the set point is 100 psi and the deadband is 10, the Safety Relay Output will open
as pressure falls to 100 psi and close (reset) as pressure rises to 110 psi.
NOTE: Deadband should be set wide enough so that frequent or rapid Safety Relay Output cycling (chatter) does not occur but narrow
enough to satisfy the process conditions. A Deadband value of zero is undefined and, therefore, not permitted.

IM_ONE_Safety-07
www.ueonline.com
12
• Press the right gbutton to view and change deadband. Press the left 2button to increment the blinking digit. Press the right g
button to enter and move to the next digit.
• Press the right gbutton to enter a new Deadband. SW1 will show on the display.
NOTE: The Set Point and Deadband settings are subject to the accuracy of the instrument. Actual switch points may vary up to +0.5%
of the sensor’s maximum range at room temperature. Example: The P15 sensor has a range of 0 to 300 psi. When setting a Set Point
of 150, the actual switch point may occur between 148.5 and 151.5 due to the accuracy error of +1.5 (300 x 0.5%).
Figure 16
Resetting the Maximum & Minimum Values
The One Series Field Safety System™ continuously records the readings from the sensor and stores the minimum and maximum (MAX/MIN,
peak hold) values in non-volatile memory. The max/min values may be viewed at any time by removing the enclosure cover (page 5) and pushing
the left 2button. The display will scroll the MAX/MIN values and then return to the Process Display mode.
To reset the values, enter the Programming Mode (see page 10). Repeatedly press the left 2button to get to the CLR MAX/MIN command and then
press the right gbutton two times. After exiting the Programming Mode and saving the changes (see page 10), the values will be reset to the
current reading and begin recording again.
Open
Closed Closed
Open
Closed Closed
SP
DB
SP
DB
Open Open
Closed Closed Closed
DBH
DBL
SPH
SPL
Open on Rise
Open on Fall
Window

IM_ONE_Safety-07
www.ueonline.com 13
ADVANCED FEATURES
NOTE: No initial configuration of these features is required. The default for these advanced commands is zero or off.
Adjusting Display Offset
The One Series Field Safety System™ is factory calibrated to 0.25% of the sensor’s maximum range at room temperature. In some
installations, it may be necessary to adjust the display’s offset due to the range and position of the sensor. Chemical seals with long
capillaries combined with low maximum range sensors are a common cause of offset error. The OFFSET command allows the user
to enter a positive (“POS”) or negative (“NEG”) offset to the display readings. An offset adjustment of up to +10% of the sensor’s
maximum range is allowed. If adjusting OFFSET, it may be necessary to adjust SPAN (see below).
Example: When the sensor has a zero pressure applied, but the display reads a value other than zero, entering the additive inverse
(reversing the sign) of the displayed value for OFFSET will force the display to read zero.
NOTE: Any numerical value entered other than 0.00 will cause the display to indicate “Offset” just above the process reading in the
process display.
USE OF THIS OPTION MAY CREATE A CONDITION WHERE THE DISPLAY MAY INDICATE “0.00” WHEN SIGNIFICANT PRESSURE OR
TEMPERATURE (UP TO 10% OF MAXIMUM RANGE) EXISTS IN THE SYSTEM. INDEPENDENT VERIFICATION OF THE PROCESS VARI-
ABLE SHOULD BE DONE PRIOR TO MAINTENANCE ON THE SYSTEM WHEN “OFFSET” APPEARS ON THE DISPLAY.
Refer to the Programming Flowchart on page 19.
• Enter the Programming Mode and use the left 2button to move to the OFST command.
• Press the right gbutton to select a positive or negative offset. POS is default. Use the left 2button to change to NEG.
• Press the right gbutton to view and change the offset. Zero is the factory setting. Press the left 2button to increment the blink-
ing digit. Press the right gbutton to enter and move to the next digit.
• Press the right gbutton to enter the new offset and return to the main menu.
Adjusting Span
SPAN provides an adjustment to shift the slope of the sensor’s response curve to accommodate an offset value other than zero. To
adjust SPAN, calculate and enter a new SPAN value.
To calculate the SPAN value, apply a reference source below maximum scale to the sensor. Record the value that shows on the One
Series Field Safety System™ display and the reference source value. Divide the reference source value by the display value and then
multiply the result by the sensor’s upper range.
FORMULA: SPAN = reference source / display value x upper range value
• Pressure example: For a sensor range of 0 - 100 psi, choose a reference source (90) below the upper range limit (100) to
prevent an over range condition. Divide the reference source value from the resulting display value (88). Multiply the result by the
upper range limit. Span = 90 / 88 x 100 = 102 (rounded)
• Temperature example: For a sensor range of -40 to 450ºF, choose a reference source (400) below the upper range limit (450) to
prevent an over range condition. Divide the reference source value from the resulting display value (404). Multiply the result by
the upper range limit. Span = 400 / 404 x 450 = 446 (rounded)
Refer to the Programming Flowchart on page 19.
• Enter the Programming Mode (see page 10) and use the left 2button to move to the SPAN command.
• Press the right gbutton to select a positive or negative span. POS is the default. Use the left 2button to change to NEG.
• Press the right gbutton to view and change the span. Zero is the factory setting. Press the left 2button to increment the blink-
ing digit. Press the right gbutton to enter and move to the next digit.
• Press the right gbutton to enter the new span and return to the main menu.

IM_ONE_Safety-07
www.ueonline.com
14
NOTE: To return to factory calibration settings, enter all zeros for both SPAN and OFST.
Setting the Latch Mode (Manual Reset)
The Safety Relay Output can be configured to latch open when the set point is reached. Refer to the Programming Flowchart on page
19.
• LCH1: In the Programming Mode, press the right gbutton.
• If OFF is displayed, press the left 2button to set LCH1 to ON.
• Press the right gbutton to set the latch. When latch mode is on (set), the Safety Relay Output changes state from closed to open
when the set point is crossed and remains latched until the Safety Relay Output is manually reset by the user or the One Series
Field Safety System™ is power cycled.
When latched, the display will read MAN RSET.
To Reset the Latch
• Enter the Programming Mode (see page 10). If the Latch is set, the display will read MAN RSET. To return to the Process Display
without resetting the latch, press the right gbutton.
• To continue programming without resetting the latch, press the left 2button.
• Press both 2g buttons to reset the latch. The display now reads RSET DONE.
• Press the right gbutton to return to the Process Display.
• Press the left 2button to continue Programming.
Setting the Plugged Port Feature
The One Series Field Safety System™ IAW™self-diagnostics have the ability to detect that the process port may be plugged. It does
this by monitoring the sensor for changes over time. The amount of change and the time period are programmable. If the process
variable does not change by the amount and selected time period, the display will indicate PLUG and the IAW™Output will open, indicat-
ing a fault. Refer to the Programming Flowchart on page 19.
• Enter the Programming Mode and press the left 2button until PLUG PORT is scrolling on display. Press the right gbutton.
• There are four possible selections -
• OFF - This disables the plugged port function and is the default setting. This should be done where sensor plugging is
not a concern or where the system pressures may not change over time (example: a storage tank).
• 1 minute
• 1 Hour Maximum time with no process variation before fault indication
• 24 Hours
• Using the left 2button, select a time.
• If OFF is selected, press the right gbutton to return to the PLUG PORT command and leave Plug Port deactivated.
• Press the right gbutton to enter a process value < 10% of the sensor’s maximum range. This number represents the minimum
variation expected in the process value over the time period entered above under normal operating conditions. Each time the
process value reaches this value, the Plug Port timer is reset.
NOTE: This value can be accurately determined by subtracting the minimum from the maximum process value as recorded by the MAX/
MIN feature. See RESETTING MAXIMUM AND MINIMUM VALUES on page 12 for additional information.
}

IM_ONE_Safety-07
www.ueonline.com 15
SETTING THE SRO FAULT MONITOR
The SRO fault monitor senses the output of the relay and verifies that it is in the correct state. If the relay is closed when it should be open or open
when it should be closed this feature will turn off IAW, set the output current to < 3.6 mA attempt to turn off the SRO and SRO Status outputs. A
relay fault message will be displayed. This feature requires a connection to +VDC, -VDC or neutral (L2) from the load’s power supply. See wiring
connections for TB2 on page 8.
NOTE: The SRO fault monitor default is set to “OFF” from the factory and must be enabled by the user. Refer to the Programming Flowchart on page 19.
• Enter the Programming Mode and move through the program until SRO FAULT MON is scrolling on the display. Press the right gbutton.
• If OFF is displayed, press the left 2button to set fault monitoring to ON
• Press the right gbutton to activate SRO fault monitoring.
Setting the Filter
In some applications, it is desirable to “dampen” the Safety Relay Output response and prevent intermittent false trips due to pressure
spikes or other transient/isolated events. The Filter feature provides a software digital filter with a configuration time constant for sup-
pressing certain transient short-duration events.
Refer to the Programming Flowchart on page 19.
• Enter the Programming Mode (see page 10) and move through the commands until FILTER is scrolling on the display. Press the
right gbutton.
• The available selections are as follows
Pressure Models: OFF (Default) Temperature Models: 1/2 second
1/4 second 1 second
1/2 second 2 seconds
1 second
2 seconds
• Using the left 2button, select a time constant.
• Press the right gbutton to enter the time constant and return to main menu.
NOTE: The One Series typically responds to a process value change in less that 100 milliseconds when the Filter is set to off. Using this
feature can lengthen the overall response time of the One Series for certain types of process value changes (pressure spikes).
• A shorter delay setting provides a faster response but is less stable.
• A longer delay setting provides a slower response and is more stable.

IM_ONE_Safety-07
www.ueonline.com
16
NOTE: Do not replace the One Series display module or pres-
sure sensor. Swapping these amongst devices will cause a
mis-match between the stored sensor calibration data and the
pressure sensor. For proper operation, the display module
serial number must always match the serial number inside the
enclosure (see Figure 18).
These serial numbers must match for proper operation.
DISPLAY MODULE CALIBRATION
SETTING THE SCALE
The 4-20 mA output is field scalable. The default setting is 100% of the sensor’s maximum range, where 4 mA represents minimum and 20 mA
is maximum range. If desired, both the 4 mA and 20 mA levels may be set independently to shrink or stretch the portion of the sensor’s range
represented by the 4-20 mA output.
• Setting the 4 mA portion of the scale (see Figure 17):
• Enter the Programming Mode (see page 10) and use the left 2button to move to the 4MA SET command.
• Press the right gbutton to select a positive or negative scale. POS is the default. Use the left 2button to change to NEG.
• Press the right gbutton to view and change the scale. Press the left 2button to increment the blinking digit. Press the right g
button to enter and move to the next digit. This process value must be between -3% and 25% of the sensor’s maximum range.
• Press the right gbutton to enter the new scale and return to the main menu.
• Setting the 20 mA portion of the scale (see Figure 17):
• Enter the Programming Mode (see page 10) and use the left 2button to move the 20MA SET command.
• Press the right gbutton to select a positive or negative scale. POS is the default. Use the left 2button to change to NEG.
• Press the right gbutton to view and change the scale. Press the left 2button to increment the blinking digit. Press the right g
button to enter and move to the next digit. This process value must be between 50% and 110% of the sensor’s maximum range.
• Press the right gbutton to enter the new scale and return to the main menu.
NOTE: Scaling the 4-20 mA output over a smaller portion of the sensor’s range does not the increase the accuracy of the proportional output. A
2:1 turndown is possible using these commands.
Sensor Range
-3 to 25% 50 to 110%
4MA 20MA
0% 100%
Figure 17
Figure 18

IM_ONE_Safety-07
www.ueonline.com 17
The One Series Field Safety System™ IAW™ diagnostics are capable of detecting many possible fault conditions. Some fault conditions will
clear automatically when the parameter returns to normal; others require the device to be powered down and restarted; and some may require
repair or replacement. A list of fault conditions are shown below in table 5.
If a fault message appears on the One Series display, a fault code can be obtained by pressing both keypad buttons 2g simultaneously.
Please provide this code if calling UE Inside Sales for assistance.
ONE SERIES FAULT CODES
Code Probable Cause Reason Action
E- 04 Loop Current Fault The current measured in the 4-20mA loop, by the fault monitoring
circuitry, is incorrect.
Verify that the power supply voltage
and load resistance on the 4-20mA
loop are within allowable limits.
E- 15 Diagnostic Fault Sensor OPEN An open circuit has been detected on the sensor drive pins 2 & 3. Diagnostic Fault Sensor open, check
all sensor connections.
E- 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 & 3. Diagnostic Fault Sensor Short, check
all sensor connections.
E- 18 Diagnostic Fault Relay Monitor The relay output fault monitor circuit has detected that the output
state of the solid state relay is incorrect. This feature must be
enabled in the menu.
Check the wiring connections or dis-
able feature if not being used.
E- 65 Error -- switch output The switch output fault monitor circuit has detected that the switch
output state is incorrect.
Internal Hardware Fault, contact
factory
E- 88 Error -- Process Variable Extreme
Overrange
Extreme overrange, a pressure input has exceeded 150% of the op-
erating range or a temperature input has exceeded 110% of range.
Warning: This fault may indicate
damage to the sensor. Check that
the process is within the operating
limits of the device. Verify all sensor
connections.
NOTE: Power cycling the One Series will reset some faults. If the fault remains after power cycling, please contact UE Inside Sales at
[email protected] or call +1 (617)-923-6977. Some fault codes not noted above indicate microprocessor faults.
Table 5

IM_ONE_Safety-07
www.ueonline.com
18
LOST PASSWORDS
Contact UE Inside Sales at +1-617-923-6977 or go online at www.UEonline.com/UUC to obtain a unique unlock code. The Kanban number from
the product nameplate is required (see Figure 19).
Table 6
THIS DOCUMENT IS PROPRIETARY
PROPERTY OF UNITED ELECTRIC CONTROLS.
UNAUTHORIZED USE IS STRICTLY PROHIBITED.
TOLERANCES ON FRACTIONS
±1/64
±1/2°
±0.010 ±0.005
2 PLACE DEC 3 PLACE DEC ANGLES
Page 1 of 1
WARNING: AGENCY CRITICAL DOCUMENT.
NO REVISIONS WITHOUT CERTIFICATION
ENGINEER APPROVAL
NOTES:
LASER MARKED ON BLANK NAMEPLATE P/N 6211-751. 1.
NAMEPLATE DIMENSIONS ARE 3.943" REF X 1.35" REF
FORMAT SHOWS FIXED TEXT AND GRAPHICS ONLY.
2.
ANY VARIABLE TEXT SHOWN IS BETWEEN * MARKS.
C
E5537
ADDED PROTECTION METHOD CHECK BOXES.
6-12-15
SR
EM
B
E5530
UPDATED PER AGENCY REQUIREMENTS
6/9/15
SR
EM
A
E5453
FIRST ISSUE
5/14/15
SR
EM
EM
2.25:1
DWG NO
UNITED ELECTRIC
CONTROLS COMPANY
WATERTOWN * MASSACHUSETTS
SCALE
TITLE
ORIGINAL DATE
DRWN
CHKD
APPD
DO NOT SCALE THIS DRAWING
DOC #: DE733010102 Rev B
EM
ONE SERIES
1X
NAMEPLATE
A-6211-847
SR
5/14/15
6211-847
DESCRIPTION
DATE
DRWN
APPD
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
REV.
ECN#
Figure 19
Kanban number and Date Code
Set Point Reached IAW Fault SRO Status IAW Output Safety Relay Output
No No Closed Closed Closed
No Yes Open Open Open
Yes No Open Closed Open
Yes Yes Open Open Open
DISCRETE OUTPUTS TRUTH TABLE
TROUBLESHOOTING
The Safety Relay Output contained in the One Series Field Safety System™ is electronic, and the signal is produced by a transistor or a
solid-state relay. The Safety Relay Output cannot be properly tested with an ohmmeter. Instead, measure the voltage drop across the SRO
connected to the intended load to determine if it is open or closed. A properly functioning One Series Field Safety System™ will exhibit the
following voltage levels:
Troubleshooting Voltage Levels
Output Location Voltage Open Voltage Closed
IAW OUTPUT TB4 pins 1,2 24 VDC (Loop Voltage) 0 VDC
SRO STATUS TB3 pins 1,2 24 VDC (Loop Voltage) 0 VDC
SRO TB2 pins C,D Load Power Supply Voltage 0 VAC
Table 7

IM_ONE_Safety-07
www.ueonline.com 19
Flowchart 1
Process Display
1234
MAN
RSET
Display to Scroll :
SP1 xxxx, DB1 xxxx, SP2 xxxx, DB2
xxxx
Display to Scroll :
MAX xxxx, MIN xxxx
RSET
DONE
BOTH
PASS
WORD
8888
Set Blinking Digit
Increments Blinking Digit
Sets Digit and moves to next
ENTER
NEW
PWORD
PWORD
Valid
8888
Set Blinking Digit
Increments Blinking Digit
Sets Digit and moves to next
CONF PASSWORD
8888
BOTH
ABORT
CHANGE
BOTH
If Latch
Set
No Latch Set
CLR
MAX/MIN
CLR?
NO
YES
SET
UNITS
PSI
BAR/mBAR °F
KPa/MPa °C
Kg/cm2
“wc
SW1
SP
8888
Set Blinking Digit
Increments Blinking Digit
Sets Digit and moves to next
POS
NEG
Skip if range only POS
Set Point Outside Sensor
Range
flash “Err”
DB
8888
Set Blinking Digit
Increments Blinking Digit
Sets Digit and moves to next
Dead Band out of Range
flash “Err”
Shortcut to
Save
Changes
BOTH
OPEN
RISE
OPEN
FALL
WINDOW
SPH
DBH
SPL
DBL
Note: Enter Set Point High, Dead Band High, Set Point Low and Dead Band Low.
Details of entry are similar to above.
Note: Bar/mBAR or KPa/MPa will depend on sensor
range.
Invalid
PWORD
BOTH
Abort
NO
RESET
OK
Flash Err
Abort
BDOOR PWORD
Valid
SAVING
*
*
*
SAVING
One Series
Field Safety
System
LCH1
ON
O
FF
OFST
POS
NEG
8888
Set Blinking Digit
Increments Blinking Digit
Sets Digit and moves to next
SPAN
POS
NEG
8888
Set Blinking Digit
Increments Blinking Digit
Sets Digit and moves to next
Offset out of Range
flash “Err”
SPAN out of Range
flash “Err”
PLUG
PORT
FILTER
Un-shaded = Display Toggles
Shaded = Display Scrolls
THIS DOCUMENT IS PROPRIETARY PROPERTY OF
UNITED ELECTRIC CONTROLS
UNAUTHORIZED USE IS STRICTLY PROHIBITED
PLUG
PORT
OFF
1MIN
1HR
24HR
If OFF is selected,
pressing will
return to menu
8888
Set Blinking Digit
Increments Blinking Digit
Sets Digit and moves to next
Set Window
Setting > 10% of Range
flash “Err”
SRO FAULT
MONITOR
ON
OFF
*
*
*
*
*
* Denotes shortcut to Save Changes
when both buttons are pressed.
*
*
*
SAVE
CHNG
NO
YES
Both saves
changes
FILTER
4 MA
SET
POS
NEG
8888
Set Blinking Digit
Increments Blinking Digit
Sets Digit and moves to next
20MA
SET
POS
NEG
8888
Set Blinking Digit
Increments Blinking Digit
Sets Digit and moves to next
Out of Range
flash “Err”
Out of Range
flash “Err”
Both
Discards
changes
SAVING
CHANGES
CHANGES
DISCARDED
OFF
1/4S
1/2S
1Sec
2Sec

IM_ONE_Safety-07
www.ueonline.com
20
5.3”
5.7”
5.4”
6.1”
5.3 5.4
10.4”
8.0”
5.4”
5.3”
5.1”
5.4”
3.00”
3.63”
CLEARANCE
HOLE FOR 1/4" BOLT
4 PLCS
5.3”
5.1”
5.4”
3/4” - 14 NPT
CONDUIT PORTS
1/2” - 14 NPT
SENSOR PORT
3/4” - 14 NPT
CONDUIT PORTS
3/4” - 14 NPT
CONDUIT PORTS
3/4” - 14 NPT
CONDUIT PORTS
3/4” - 14 NPT
CONDUIT PORTS
1/2” - 14 NPT
SENSOR PORT 1/2” - 14 NPT
SENSOR PORT
1”-20 NPT
SENSOR PORT
1”-20 NPT
SENSOR PORT
[111.92]
mm
[76.2]
mm
[133.35]
mm
[12.7]
mm
SURFACE MOUNTING KIT
6361-704
[144.78]
mm
[134.62]
mm
[137.16]
mm
[154.94]
mm
[134.62]
mm
[137.16]
mm
[264.16]
mm
[203.2]
mm
[137.16]
mm
[129.54]
mm
[134.62]
mm
[137.16]
mm
[76.2]
mm
[92.20]
mm
[129.54]
mm
[134.62]
mm
[137.16]
mm
[107.95]
mm
[61.91]
mm
[158.75]
mm
[7.11]
mm
[107.95]
mm
[76.2]
mm
[6.35]
mm [8.73]
mm
DIMENSIONAL DRAWINGS
GAGE PRESSURE
LOCAL TEMPERATURE
(SPRING LOADED)
DIFFERENTIAL PRESSURE
LOCAL TEMPERATURE
(WELDED)
MOUNT BOLT PATTERN
This manual suits for next models
1
Table of contents
Other UE Switch manuals
Popular Switch manuals by other brands

ICS Schneider Messtechnik
ICS Schneider Messtechnik PSA-31 operating instructions

call4tel
call4tel NXGW-XET1 user manual

Indu-Sol
Indu-Sol PROmesh U16 Quick start user guide

Vigitron
Vigitron MaxiiNet Vi3003W user manual

Kindermann
Kindermann Multimatrix 8 operating instructions

GRASS VALLEY
GRASS VALLEY TRITON TTN-BVS-1602 installation manual