Unipulse DeviceNet F381A User manual

Ethernet I/F
01FEB2015REV.3.01
F381A/F388A
OPERATION MANUAL

Introduction
I
Introduction
The Ethernet I/F option is an interface to carry out communications with F381A/F388A(s) through an
Ethernet.
Supported functions are set value read/write, waveform read/write, hold result read, wave No. read/write,
etc.
WARNING
The F381A/F388A(s) is factory-set as follows:
・IP address (192.168.0.1)
・Subnet mask (255.255.255.0)
・Default gateway (unused)
If there is a need to change the settings of the IP address, subnet mask, and default
gateway, be sure to change the settings and then carry out wiring of Ethernet cable(s).

Contents
II
Contents
1. Part names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2. How to establish communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3. F381A/F388A setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
■Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
■Setting screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
■Ethernet I/F option self-check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4. Communication connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5. Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6. Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7. Cautions in creating client software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8. Communication commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
-List of items that can be communicated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
- Set value read command (First Setting) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
- Set value read command (Work Setting) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
- Set value write command (First Setting) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
- Set value write command (Work Setting) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
- Zero calibration command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
- Actual load calibration command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
- Hold result read command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
- Result read command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
- Waveform update check/equipment ID read command . . . . . . . . . . . . . . . . . . . 24
- Waveform read command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
- Waveform write command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
- Wave No. read command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
- Wave No. write command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
- Display read command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
- Time read command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
- Time write command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
- List of commands to read set values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
- List of commands to write set values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
- List of zero calibration commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
- List of actual load calibration commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
- Unit setting list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
■Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9. Error message. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
10.Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
■Hardware specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
■Software specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
11.Outside dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

1.Part names
1
1. Part names
Status LED
This indicates the LINK/ACT status.
(See "5.Status LED" on page10)
Communication connector
This connector connects an Ethernet cable.
(See "4.Communication connector" on page10)
2. How to establish communications
・Network check
Check the network environment in which the F381A/F388A(s) is to be connected.
Status LED
Communication
connector
LINK (Orange)
ACT (Green)
LAN
LAN1 LAN2
①The F381A/F388A and client are connected
in a one-to-one relationship.
②The F381A/F388As and client exist on the
same LAN.
③The F381A/F388As and client exist on different LANs.

2.How to establish communications
2
1. Set the IP address, subnet mask, and default gateway.
①When the F381A/F388A and client are connected in a one-to-one relationship
IP address: Set the same network address as that of the client, and set a unique
address avoiding overlap with the client.
Subnet mask: Set the same subnet mask as that of the client.
Default gateway: No particular setting is required.
②When the F381A/F388As and client exist in the same network
IP address: Set the same network address as that of the client, and set a unique
address avoiding overlap with other equipment in the network each
F381A/F388A belongs to.
Subnet mask: Set the same subnet mask as that of the client.
Default gateway: No particular setting is required.
③When the F381A/F388As and client exit in different networks
IP address: Set the same network address as that of the equipment in the
network each F381A/F388A belongs to, and set a unique address
avoiding overlap with other equipment.
Subnet mask: Set the same subnet mask as that of the equipment in the network
each F381A/F388A belongs to.
Default gateway: Set the IP address of the router.
F381A/F388A
IP address:
192.168.0.2
Subnet mask:
255.255.255.0
Default gateway:
---.---.---.---
Client
IP address:
192.168.0.5
Subnet mask:
255.255.255.0
LAN
Network address
192.168.0
F381A/F388A
IP address:
192.168.0.2
Subnet mask:
255.255.255.0
Default gateway:
---.---.---.---
F381A/F388A
IP address:
192.168.0.1
Subnet mask:
255.255.255.0
Default gateway:
---.---.---.---
Client
IP address:
192.168.0.5
Subnet mask:
255.255.255.0

2.How to establish communications
3
2. Connect LAN cable(s).
For use at 10Mbps, use STP (category, 3, 4, 5) cable(s). For use at 100Mbps, use STP
(category 5) cable(s).
* UTP cable(s) can also be used, but use of STP cable(s) is recommended.
①When the F381A/F388A and client are connected in a one-to-one relationship.
Use a cross cable.
F381A/F388A
IP address:
192.168.1.2
Subnet mask:
255.255.255.0
Default gateway:
192.168.1.3
F381A/F388A
IP address:
192.168.1.1
Subnet mask:
255.255.255.0
Default gateway:
192.168.1.3
Client
IP address:
192.168.2.5
Subnet mask:
255.255.255.0
Default gateway:
192.168.2.3
LAN1
Network address
192.168.1
LAN2
Network address
192.168.2
IP address
①
:
192.168.1.3
Subnet mask:
255.255.255.0
IP address
②
:
192.168.2.3
Subnet mask:
255.255.255.0
F381A/F388A PC etc.
Modular jack Modular jack
RJ-45 8pin RJ-45 8pin
1
2
3
4
5
6
7
8
TX+
TX-
RX+
RX-
1
2
3
4
5
6
7
8
TX+
TX-
RX+
RX-

2.How to establish communications
4
②When the F381A/F388As and client exist in the same network.
③When the F381A/F388As and client exist in different LANs.
Connect with the client through a hub, etc., by using straight cables.
3. Check that the LINK lamp is lit.
If the lamp is not lit, it is considered that the equipment (hub, host, etc.) connected with the
F381A/F388A(s) is not running normally, or the cable(s) is wired incorrectly or broken.
Check that the equipment (hub, host, etc.) connected with the F381A/F388A(s) is running
normally, and the cable(s) is wired correctly and is not broken.
4. Check the connection of the client and each F381A/F388A.
i) With the power of the F381A/F388A OFF, execute a PING command (see "・What is
PING?" on P.12.) from the client to the IP address of the turned-OFF F381A/F388A,
and check that no response is made. If a response is made, the specified IP address is in
use. Check that the IP address is not used in other equipment.
ii) Turn on the power of the F381A/F388A, and execute a PING command from the client
to the IP address of the turned-ON F381A/F388A, and check that a response is made.
If no response is made, connection between the client and F381A/F388A is not
established.
Check that the route between the equipment from which the PING command was sent
and F381A/F388A is established and that the network settings of the client and F381A/
PLC
1
2
3
4
5
6
7
8
TX+
TX-
RX+
RX-
F381A/F388A ハブ等
Modular jack Modular jack
RJ-45 8pin RJ-45 8pin
1
2
3
4
5
6
7
8
TX+
TX-
RX+
RX-

3.F381A/F388A setting
5
F388A are as intended.
* Check with your network administrator for the use environment.
5. Check the establishment of connection.
Start the client software, and connect with the F381A/F388A.
Upon establishment of connection, the IP address of the connection-established equipment
is displayed under "Connect IP" on the Ethernet setting item screen of the F381A/F388A.
(If the F381A/F388A is connected with the client through a router, the address of the router
close to the F381A/F388A is displayed.)
If connection is not established, the settings of the client software may be wrong. Check the
specifications of the IP address, port number (50381 (TCP/IP), etc., for errors.
* Check with your network administrator for the use environment.
3. F381A/F388A setting
■Operation
Operation
Main screen→Setting→First Setting→Option setting→Ethernet
■Setting screen
Ethernet setting item screen
MAC Address
Connect IP

3.F381A/F388A setting
6
Display
Numeric display: Displays the currently-set value and currently-input value.
MAC Address: Displays the MAC address of the an Ethernet I/F option.
Connect IP: Displays the IP address of the equipment the TCP connection of which is
currently established with the F381A/F388A.
If TCP connection is not established, "---.---.---.---" is displayed.
Keys
: Accepts the currently-input value.
: Cancels the currently-input value, and moves to the setting item screen.
: Octets to input move every time each key is pressed.
Numeric keypad: IP/Mask setting screen / default gateway setting screen
The number of the pressed key is input to the flashing place.
Equipment ID setting screen
The number of the pressed key is input.
: Selected octets are zeroed.
Selective item keys: Select the item of a set value.
Selection keys: Select settings to input.
Equipment ID (Initial value, 0): 0 to 999
IP (Initial value, 192.168.0.1): 1 to 223. 0 to 255. 0 to 255. 0 to 255
Mask (Initial value, 255.255.255.0): 255. 0 to 255. 0 to 255. 0 to 252
Default gateway (Initial value, Unused): 0 to 223. 0 to 255. 0 to 255. 0 to 255
Header (Initial value, None): None, STX
Header setting screen Equipment ID setting screen
Selective
items
IP/Mask setting screen Default gateway setting screen
Numeric
keypad
Selection
keys
Numeric
display

3.F381A/F388A setting
7
Explanation for setting
Equipment ID: Set the equipment ID.
When connecting two or more F381A/F388As to Ethernet, set each equipment ID
to identify them.
* This is the same as the equipment ID of the SD card slot option.
IP/Mask: Set the IP address and subnet mask.
- IP address
①: 1 to 223 (127 cannot be set.)
②: 0 to 255
③: 0 to 255
④: 0 to 255
* 0.0.0.0 cannot be set.
- Subnet mask
The subnet mask setting range varies according to the setting of the IP address.
When IP address ①is in the range of 1 - 126:
①:255
②: 0, 128, 192, 224, 240, 248, 252, 254, 255
③: When ②is 255: 0, 128, 192, 224, 240, 248, 252, 254, 255
When ②is other than 255: 0
④: When ③is 255: 0, 128, 192, 224, 240, 248, 252
When ③is other than 255: 0
When IP address ①is in the range of 128 - 191:
①:255
②:255
③: 0, 128, 192, 224, 240, 248, 252, 254, 255
④: When ③is 255: 0, 128, 192, 224, 240, 248, 252
When ③is other than 255: 0
When IP address ①is in the range of 192 - 223:
①:255
②:255
③:255
④: 0, 128, 192, 224, 240, 248, 252
192. 168. 0 . 1
①②③④
255. 255. 000. 000
①②③④

3.F381A/F388A setting
8
- About the combination of the IP address and subnet mask
Unsettable combination:
When the IP address and subnet mask are expressed in binary, IP addresses in which
all the bits 0-specified to the subnet mask become 0 or 1 cannot be set.
Example) Unsettable combination
Gateway: Set the default gateway.
- Default gateway
①: 0 to 223 (127 cannot be set.)
②: 0 to 255
③: 0 to 255
④: 0 to 255
* If 0.0.0.0 is set, the default gateway is unused.
In such a case, "---.---.---.---" is displayed.
* If "0" is set to ①, values other than 0 cannot be set to ②, ③, and ④.
- Conditions under which the default gateway cannot be set
When the IP address, subnet mask, and default gateway are expressed in binary, if the
bits 1-specified to the subnet mask do not correspond to the IP address, the specified
default gateway address cannot be set.
Also, default gateway addresses in which all the bits 0-specified to the subnet mask
become 0 or 1 cannot be set.
Decimal number Binary number
Subnet mask 255.255.000.000 11111111.11111111.00000000.00000000
IP address 192.168.000.000 11000000.10101000.00000000.00000000
192.168.255.255 11000000.10101000.11111111.11111111
Combination in which the default gateway is forcedly unused (000.000.000.000)
When the IP address, subnet mask, and default gateway are expressed in binary, if the bits
1-specified to the subnet mask do not correspond between the IP address and default
gateway, the IP address becomes effective and the default gateway is forcedly unused.
Example) Combination in which the default gateway is unused
Decimal number Binary number
Subnet mask 255.255.000.000 11111111.11111111.00000000.00000000
IP address 192.169.036.150 11000000.10101001.00100100.10010110
Default gateway 192.168.036.001 11000000.10101000.00100100.00000001
Point
192. 016. 036. 001
①② ③④

3.F381A/F388A setting
9
Example) Combinations in which the default gateway cannot be set
Header: Set the presence or absence of a header (STX).
■Ethernet I/F option self-check
1. Go to the ETN Check screen under Self-check.
Operation
Main screen→Setting→First Setting→System Setting→Self-Check→ETN Check
2. Press .
The SDRAM, DPRAM, and LAN controller are checked.
If there is no error, OK is displayed, and if there is any error, NG is displayed.
Also, the software version of the Ethernet I/F option is displayed.
* Communication status is not checked. The IC is simply checked.
Decimal number Binary number
Subnet mask 255.255.000.000 11111111.11111111.00000000.00000000
IP address 192.169.036.150 11000000.10101001.00100100.10010110
Default gateway 192.168.036.001 11000000.10101000.00100100.00000001
Decimal number Binary number
Subnet mask 255.255.000.000 11111111.11111111.00000000.00000000
Default gateway 192.169.000.000 11000000.10101001.00000000.00000000
192.169.255.255 11000000.10101001.11111111.11111111
Check that the same IP address as that of other equipment is not set.
Connect your PC to the network, and check that a response returns when a PING
command, such as a DOS prompt.
Point
At power-on, it takes about 15 seconds for the communications of the Ethernet I/
F option to become ready. During that time, connection and changes of the
settings of the Ethernet I/F option cannot be made.
Point

4.Communication connector
10
4. Communication connector
5. Status LED
ACT (Green): flashes during communications.
LINK (Orange): lights at 10BASE-T/100BASE-TX-link time.
6. Network
・What is a LAN?
For carrying out communications with multiple pieces of equipment, a group of a certain size is
normally formed for managing and geographical reasons.
This group is called a LAN (Local Area Network).
・How to form a LAN
The same network address needs to be set in one LAN.
When the IP address is expressed in binary, the IP address of the part 1-specified to the subnet mask
is the network address.
Example)
Decimal number Binary number
Subnet mask 255.255.255.000 11111111.11111111.11111111.00000000
IP address 192.168.000.001 11000000.10101000.00000000.00000001
Network address 192.168.000 11000000.10101000.00000000
8
1
Pin No. Signal
8
7
6-RX
5
4
3+RX
2-TX
1+TX
LAN
Network address
192.168.0
F381A/F388A
IP address:
192.168.0.2
Subnet mask:
255.255.255.0
Default gateway:
---.---.---.---
F381A/F388A
IP address:
192.168.0.1
Subnet mask:
255.255.255.0
Default gateway:
---.---.---.---
Client
IP address:
192.168.0.5
Subnet mask:
255.255.255.0

6.Network
11
・How to connect different LANs
For connecting different LANs, a router needs to be connected between them, and the address of the
router should be set to the default gateway.
・What is a connection?
Virtual circuit(s) provided between the pieces of equipment to carry out communications is called
connection.
・What is the establishment of a connection?
A state in which communications can be carried out between the pieces of communicating
equipment by providing virtual circuit(s) for communications is called the establishment of a
connection.
Taking a telephone as an example, it refers to: picking up the telephone receiver, inputting the
telephone number of the other end, and the other end answering the telephone.
The F381A/F388A does not send a reply to commands (set value read/write, waveform read/write,
etc.) until connection with the F381A/F388A is established.
・What is a host?
The equipment that is capable of transmission and reception in communication by using a protocol
is called a host.
・What is a client?
The host that tries connecting to establish a connection is called a client.
・What is a server?
The host waiting for a connection in establishing a connection is called a server.
The F381A/F388A is a server, and after power-on, it is brought to a state in which it waits for
connection from the client side.
F381A/F388A
IP address:
192.168.1.2
Subnet mask:
255.255.255.0
Default gateway:
192.168.1.3
F381A/F388A
IP address:
192.168.1.1
Subnet mask:
255.255.255.0
Default gateway:
192.168.1.3
Client
IP address:
192.168.2.5
Subnet mask:
255.255.255.0
Default gateway:
192.168.2.3
Network 1
Network address
192.168.1
Network 2
Network address
192.168.2
IP address
①
:
192.168.1.3
Subnet mask:
255.255.255.0
IP address
②
:
192.168.2.3
Subnet mask:
255.255.255.0

7.Cautions in creating client software
12
・What is PING?
It is a client side program to diagnose the network status.
You can check the communication status according to the replay made by sending packet data that
requests a replay to the equipment the network status of which you want to check.
* For the method of operation, check with your network administrator for the use environment.
・What is "keep-alive"?
Communications are carried out periodically to check that the connection is valid.
Under circumstances where communications are not carried out for a long time, it is not clear
whether communications are not carried out intentionally or communications cannot be carried out
due to some problem.
Therefore, even under such circumstances where communications are not carried out for a long
time, whether or not the connection is valid is checked by sending a packet informing that the
connection is continuing to the other end and checking the arrival of the packet at the other end.
If the connection is invalid, it is cut off by a predetermined number of times.
7. Cautions in creating client software
- Protocol TCP/IP
- Port number Set 50381 to the port number.
- Keep alive The F381A/F388A sends a packet at intervals of 30 seconds, and checks three
times.
-Checking of communications carried out with an intended F381A/F388A
For use of two or more F381A/F388As, set the equipment ID avoiding
overlap to identify them.
After power-on and the establishment of a connection with the F381A/F388A,
read the equipment ID and check the consistency between the IP address and
equipment ID.

8.Communication commands
13
8. Communication commands
By transmitting commands from the host, operations corresponding to the commands are executed.
(①F381A ②F388A)
-List of items that can be communicated
Item group Set value, operation,
display item Read Write Cal. Reference
Main Load (display) 〇× × Display read command
DPM (display) 〇× × Display read command
Work No. (display) 〇× × Display read command
Measurement status
display ○××
Display read command
Waveform update check
〇××
Waveform update check/
equipment ID read
command
Measurement waveform 〇××
Waveform read command
Equipment ID
〇××
Waveform update check/
equipment ID read
command
Result Result (display) 〇××
Hold result read
command
Result 〇× × Result read command
Wave No. 〇〇 ×Wave No. read/wave No.
write command
First Setting Y-axis Setting ①Exc. Voltage
②Input Select 〇〇 ×Set value read/
set value write command
Unit 〇〇 ×Set value read/
set value write command
Decimal Place 〇〇 ×Set value read/
set value write command
Zero Cal. 〇×〇Set value read/
Zero cal. command
Equiv. Cal.
(rated output) 〇〇 ×Set value read/
set value write command
Equiv. Cal.
(rated capacity) 〇〇 ×Set value read/
set value write command
Actual Cal. × × 〇Actual cal. command
Overload 〇〇 ×Set value read/
set value write command
Increment 〇〇 ×Set value read/
set value write command
Analog Filter 〇〇 ×Set value read/
set value write command
Digital Filter 〇〇 ×Set value read/
set value write command
DZ Limit 〇〇 ×Set value read/
set value write command

8.Communication commands
14
Item group Set value, operation,
display item Read Write Cal. Reference
First Setting X-axis Setting Time/DPM Change 〇〇 ×Set value read/
set value write command
Phase Select 〇〇 ×Set value read/
set value write command
Wave Reference 〇〇 ×Set value read/
set value write command
Unit 〇〇 ×Set value read/
set value write command
Decimal Place 〇〇 ×Set value read/
set value write command
Zero Cal. 〇×〇Set value read/
Zero cal. command
Equiv. Cal.
(number of pulses)
(voltage value)
〇〇 ×
Set value read/
set value write command
Equiv. Cal.
(displacement value) 〇〇 ×Set value read/
set value write command
Actual Cal. × × 〇Actual Cal. command
Measure Length 〇〇 ×Set value read/
set value write command
DPM Positioning 〇〇 ×Set value read/
set value write command
Analog Filter
(Only ①)〇〇 ×Set value read/
set value write command
Digital Filter 〇〇 ×Set value read/
set value write command
Communication
Setting
Speed 〇〇 ×Set value read/
set value write command
Data Bit 〇〇 ×Set value read/
set value write command
Parity Bit 〇〇 ×Set value read/
set value write command
Stop Bit 〇〇 ×Set value read/
set value write command
Delimiter 〇〇 ×Set value read/
set value write command
Header 〇〇 ×Set value read/
set value write command
Flow Control 〇〇 ×Set value read/
set value write command
Com. Mode 〇〇 ×Set value read/
set value write command

8.Communication commands
15
Item group Set value, operation,
display item Read Write Cal. Reference
First Setting System
Setting
Backlight
(ON Time) 〇〇 ×Set value read/
set value write command
Backlight
(bright→dark) 〇〇 ×Set value read/
set value write command
Language 〇〇 ×Set value read/
set value write command
Work Protect 〇〇 ×Set value read/
set value write command
First Protect 〇〇 ×Set value read/
set value write command
Time adjust 〇〇 ×Time read/
time write command
Option Setting
Settings by
work
[Work 0 to 15]
Work Setting Work No. (for Ethernet
I/F communications) 〇〇 ×Set value read/
set value write command
Measurement
Start Condition
Setting
Start Condition 〇〇 ×Set value read/
set value write command
Start Level 〇〇 ×Set value read/
set value write command
Stop Condition 〇〇 ×Set value read/
set value write command
Stop Level 〇〇 ×Set value read/
set value write command
Display Range
Setting
Y Start Point 〇〇 ×Set value read/
set value write command
Y End Point 〇〇 ×Set value read/
set value write command
X Start Point 〇〇 ×Set value read/
set value write command
X End Point 〇〇 ×Set value read/
set value write command

8.Communication commands
16
Item group Set value, operation,
display item Read Write Cal. Reference
Settings by
work
[Work 0 to 15]
Hold Setting Change of Sct.
(common to all work) 〇〇 ×Set value read/
set value write command
Use Sct. 〇〇 ×Set value read/
set value write command
Sct. No. (for Ethernet I/F
communications) 〇〇 ×Set value read/
set value write command
Use Hold 〇〇 ×Set value read/
set value write command
Sct. Start-End
(start point) 〇〇 ×Set value read/
set value write command
Sct. Start-End
(end point) 〇〇 ×Set value read/
set value write command
Load HI/LO Limit
(HI limit) 〇〇 ×Set value read/
set value write command
Load HI/LO Limit
(LO limit) 〇〇 ×Set value read/
set value write command
DPM HI/LO Limit
(HI limit) 〇〇 ×Set value read/
set value write command
DPM HI/LO Limit
(LO limit) 〇〇 ×Set value read/
set value write command
Start Load 〇〇 ×Set value read/
set value write command
Load Difference 〇〇 ×Set value read/
set value write command
Rate 〇〇 ×Set value read/
set value write command
Ordinal 〇〇 ×Set value read/
set value write command
Interval AB (A) 〇〇 ×Set value read/
set value write command
Interval AB (B) 〇〇 ×Set value read/
set value write command
Waveform
Comparison
Setting
Relative 〇〇 ×Set value read/
set value write command
Compare Area
(start point) 〇〇 ×Set value read/
set value write command
Compare Area
(end point) 〇〇 ×Set value read/
set value write command
Compare Margin 〇〇 ×Set value read/
set value write command
Relative Point (X-axis) 〇〇 ×Set value read/
set value write command
Relative Point (Y-axis) 〇〇 ×Set value read/
set value write command
Comparison Wave
〇〇 ×
Waveform read/
Waveform write
command
Section 1 to 5

8.Communication commands
17
- Set value read command (First Setting)
Example: Reading ①Excitation Voltage/②Input Selection, Y-axis Setting, First Setting
- Set value read command (Work Setting)
Example: Reading Y-axis Start Point, Display Range Setting, Work No. 10, Work Setting
①Writing “10” to Work No.
R100
Delimiter
0
Host
(Transmission to the F381A/F388A)
Item No. (See the list of set value commands.)
①Excitation Voltage/ ②Input Selection in the example
Item group (See the list of set value commands.)
Y-axis Setting in the example
(
STX
)
Delimiter
N1G
F381A/F388A’s return
(In normal processing)
F381A/F388A’s return
(In abnormal condition)
Data of the specified set value
Command received by the F381A/F388A
Header (If there is no header, no data will result.)
Header (If there is no header, no data will result.)
(
STX
)
Delimiter
00R1 000+00010
NG No.
1: Receipt of a statement different from the command format
Host
(Transmission to the F381A/F388A)
Item No. (See the list of set value commands.)
Work No. in the example
Item group (See the list of set value commands.)
Work Setting in the example
00+0000010W1 0
Delimiter
Data to write
The amount of data varies depending on the set value.
F381A/F388A’s return
(In normal processing)
Command received by the F381A/F388A
Header (If there is no header, no data will result.)
(
STX
)
Delimiter
00W0 010+00001
(
STX
)
Delimiter
N1G
F381A/F388A’s return
(In abnormal condition)
Header (If there is no header, no data will result.)
NG No.
1: Receipt of a statement different from the command format
2: Attempt to write a set value outside the setting range
4: Attempt to write a set value through communications
during measurement
5: Attempt to write while protecting
Other manuals for DeviceNet F381A
3
This manual suits for next models
1
Table of contents
Other Unipulse Touch Panel manuals
Popular Touch Panel manuals by other brands

Ltech
Ltech D Series manual

Winmate
Winmate W10FA3S-GCH1 user manual

Cincoze
Cincoze CO-100/P2002 Series user manual

IEI Technology
IEI Technology AFL3-W15C-ULT5-P-PC-4G user manual

interactive scape
interactive scape Scape Tangible st65-004 operating manual

AMX
AMX MXR-1001-SL Installation & hardware reference manual