3 V1.04
VG-6637 Digital Heat Detector
Installation and Operation Manual V1.04
Address setting
1. VG-6537Digital Programmer is used to write an address of the Detector. Connecting Programmer with loop
terminals:1,2 of the Detector before it installation.
2.Set address, Pressing Write key, the address will be shown on the numeric display if successful. It is fail if there
is no address. Please refer to VG-6537 Digital Programmer Manual for details.
3.Address range should be within 0-255. The address is unique in a loop.
Mode setting
Static Response Temperature
Mode 1 is Factory Setting.
The letter “R”suffix mean that the detector class incorporate a rate-of-risecharacteristic. It will give rapid
response even when high rates of rise of air temperature starting at air temperaturessubstantially below the
typical application temperature.
TheVG-6637sensitivity mode can be set by Control Panel, please refer to the corresponding Manual for details.
Testing
Warning:Power is switched on after all devices are installed completely.
The detector must be tested after installation or regular maintenance.
Registration: The fire alarm control panel will registers the detector on line to check if the address of the
detectors mounted is the same address as that registered in the control panel.
Firecondition: After registration, make detector under fire conditions by using hot air generator to test
whether the detector alarms normally and control panel displays its registered address.
Reset:After testing, reset the detector through control panel.
Fault Finding
Detector Fault on Control Panel
Check wiring of Common base, no water no short-circuits and open circuit.
Check the connection between detector and common base.
The detector still in alarm status if there is no Fire and other unusual, means it
damaged.
Address is set incorrectly, Reset by VG-6537 Digital Programmer.