7SR21 & 7SR22 Data Communications
©2010 Siemens Protection Devices Limited Chapter 4 Page 9 of 15
There are two optional ports, com3 and com4, and when fitted the associated settings are available in the Data
Communication menu. To allow communication using either or both of these ports the relay settings must be
changed, via the fascia, in accordance with the method of connection and master device.
Setting name Range Default Setting Notes
Station Address
1 – 254 for IEC60870-5-103
0 – 247 for Modbus RTU
0 – 65520 for DNP3.0 0 As Required
An address within the range of
the relevant protocol must be
given to identify the relay. Each
relay must have a unique
address.
COM3 Protocol OFF, IEC60870-5-103,
MODBUS-RTU, DNP3.0 IEC60870-5-
103 As Required Sets the protocol used to
communicate on the connection
– Com3
COM3 Baud Rate 75 110 150 300 600 1200
2400 4800 9600 19200
38400 57600 115200 57600 As Required
The baud rate set on all of the
relays connected to the control
system must be the same as
the one set on the master
device.
COM3 Parity NONE, ODD, EVEN EVEN As Required
The parity set on all of the
relays connected to the control
system must be the same and
in accordance with the master
device.
COM3 Line Idle* LIGHT ON, LIGHT OFF LIGHT OFF As Required Sets the idle state of the line in
accordance with master device
COM3 Data Echo* ON,OFF OFF As Required
Set to ON when relays are
connected in a ring
configuration.
COM4 Protocol** OFF, IEC60870-5-103,
MODBUS-RTU, DNP3.0 IEC60870-5-
103 As Required Sets the protocol used to
communicate on the connection
– Com4.
COM4 Baud Rate** 75 110 150 300 600 1200
2400 4800 9600 19200
38400 57600 As Required
The baud rate set on all of the
relays connected to the control
system must be the same as
the one set on the master
device.
COM4 Parity** NONE, ODD, EVEN EVEN As Required
The parity set on all of the
relays connected to the control
system must be the same and
in accordance with the master
device.
COM4 Line Idle** LIGHT ON, LIGHT OFF LIGHT OFF As Required Sets the idle state of the line in
accordance with master device
COM4 Data Echo** ON,OFF OFF As Required
Set to ON when relays are
connected in a ring
configuration.
*Not applicable for RS 485 or RS 232 options
**COM 4 is fibre optic only