Vector OPA2-VC Instruction manual

OPA2-VC Operation Terminal
Technical Data
Doc: 70-00-0196A, V1.3, 20220222 © Vector Controls GmbH, Switzerland Page 1-4
Subject to alterations www.vectorcontrols.com
OPA2-VC
Communicating Operation terminal
Features
•Display and change of operation state and set points
•Display input values according to real values not voltage signals
•Display and change of configuration parameters
•Integrated temperature sensor (-T)
•Surface mounting
Applications
•Configuration and operation of TCX2 controllers
•Remote supervision (RS485)
General Description
The OPA2-VC is a remote display and operation terminal for TCX2 series controllers.
Ordering
Item Name
Item Code
Passive inputs
Humidity sensor
Description/Option
OPA2-VC
40-50 0007
Operation terminal for TCX2 controller
with internal temperature sensor
Mounting location
•Install the operation terminal on an easy accessible interior wall, approx. 1.5 m above the floor in an area of average
temperature.
•Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting equipment.
•Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.
•Location of mounting is less critical if external temperature sensors are used.
Installation
See installation sheet no. 70-000113C (www.vectorcontrols.com).
Dimensions
Important notice and safety advice
This device is for use as operating controls. It is not a safety device! Where a device failure endangers human life and/or
property, it is the responsibility of the client, installer and system designer to add additional safety devices to prevent a
system failure caused by such a device failure. Ignoring specifications and local regulations may cause equipment damage
and endangers life and property. Tampering with the device and misapplication will void warranty.
88 (3.5)
88 (3.5)
21
(0.8)
9
(0.3)

OPA2-VC Operation Terminal
Technical Data
Doc: 70-00-0196A, V1.3, 20220222 © Vector Controls GmbH, Switzerland Page 2-4
Subject to alterations www.vectorcontrols.com
Technical Specification
Power Supply
Operating voltage
10-30VDC, 10-26V AC
Power consumption
Max 0.5 VA
Electrical Connection
Terminal Connectors,
wire 0.34…2.5 mm2(AWG 24…12)
Temperature Input
Type
NTC 10kΩ @ 25°C (77°F)
Range
0…50 °C (32…122 °F)
Accuracy
0.2 K
Communication
Communication Type
Protocol
RS485, Peer to peer,
VCPP: Vector Controls Proprietary Protocol
Cabling
Impedance
Nominal capacitance
Nominal velocity
Shielded Twisted Pair (STP), CAT5 or CAT6.
balanced 100 to 120 ohm
50 pF/m 16pF/ft or lower
65% or higher
Environment
Operation
Climatic Conditions
Temperature
Humidity
To IEC 721-3-3
class 3 K5
0…50 °C (32…122 °F)
<95 % r.H. non-condensing
Transport & Storage
Climatic Conditions
Temperature
Humidity
Mechanical Conditions
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-25…70 °C (-13…158 °F)
<95 % r.H. non-condensing
class 2M2
Standards
Pollution Class
Normal acc. to EN 60 730
Degree of Protection
IP30 to EN 60 529
Safety Class
III
General
OPA Dimensions (H x W x D)
88 x 88 x 30 mm (3.5” x 3.5” x 1.1”)
Housing Material
Fire proof ABS plastic
Mounting Plate
Zinc coated steel
Standard Color
White RAL 9003
Weight (including package)
185 g (6.5 oz)
Product testing and certification
Declaration of conformity
Information about the conformity of our products can be found on our website
www.vectorcontrols.com on the corresponding product page under "Downloads"
Connection Diagram
Installation
See installation sheet no:
OPA2-VC 70-000113 ( www.vectorcontrols.com )
OPA2-VC
OP1
1
OP2
2
OP3
3
OP4
4
CAT5/CAT6
+V
⊥
Description
1 OP1 V+ Power supply
2 OP2 ⊥Power supply
3 OP3 RS485
4 OP4 RS485

OPA2-VC Operation Terminal
Engineering
Doc: 70-00-0196A, V1.3, 20220222 © Vector Controls GmbH, Switzerland Page 3-4
Subject to alterations www.vectorcontrols.com
Display and Operation
Operation modes
Control symbols
Occupied: (Comfort) All control functions operating per set points.
Heating (reverse) active
Unoccupied: (Standby, Economy) If enabled, alternative setpoints
are used with the intention to reduce energy consumption.
Cooling (direct) active
OFF
OFF: (Energy Hold Off, EHO) Normal control functions are inactive,
inputs are monitored for alarms.
Schedule set
Manual override,
delay on enable function
Fan active
Idle display
•The idle display is activated when no key has been pressed for 30 seconds.
•The contents of the idle display are selectable through parameters UP08 to UP14.
•Setting UP08 to OFF will disable idle display. Last active control loop or manual output will remain displayed.
Display of control loop
•Active when changing set points. Large digits show input value. Small digits show set point. Horizontal bars top left
show which loop is being displayed.
Operation manual
This operation terminal works with the latest generation X2 control devices. Detailed operating instructions for all devices
equipped with this operating system can be downloaded here:
http://www.vectorcontrols.com/products/x2
Also available are programming instructions for technicians and an application database.
Left (POWER)
Press < 2 sec.: Toggle STANDBY-
COMFORT mode or switch from OFF
to ON
Press > 2 sec.: Turn unit OFF. Text
OFF displayed with current time
(deluxe) temperature (standard)
(Parameter setting: ENTER to
select menu option, accept
parameter change)
Up
Increment SET POINT
(Parameter setting:
SCROLL menu options
and parameters)
Down
Decrement SET POINT
(Parameter setting: SCROLL menu
options and parameters)
Loop indication
Standard display (no button pressed
for 30 sec.): Not visible.
Loop display: Bar at 1 = Loop 1, Bar at
2 = Loop 2
Mode
Display of operation
mode
Large Digits
Display of input or parameter
value.
Indicators
Standard display:
Active digital
output (at 1, 2)
Loop display:
Active digital stages
(at 8,9,10)
Vertical Bar
(scrolls up/down, 10% resolution)
Small Digits
Display of setpoint, clock or
parameter number.
Right (OPTION)
Press < 2 sec.: Select Control Loop
Press > 2 sec.: Enter set-up
CLOCK, SCHEDULES, H/C
(Parameter setting: ENTER to
select menu option, accept
parameter change)

OPA2-VC Operation Terminal
Engineering
Doc: 70-00-0196A, V1.3, 20220222 © Vector Controls GmbH, Switzerland Page 4-4
Subject to alterations www.vectorcontrols.com
Smart Sensors and Controls
Made Easy!
Quality - Innovation –Partnership
Vector Controls GmbH
Switzerland
www.vectorcontrols.com