Vents PU SENS 01 A11 User manual

PU SENS 01 (A11)
PU SENS 01 (A19)
Sensor Control Panel
USER'S MANUAL
All manuals and user guides at all-guides.com
all-guides.com

2
PU SENS 01
www.ventilation-system.com
Safety requirements..................................................................................................................................................................... 3
Purpose................................................................................................................................................................................................ 4
Technical data.................................................................................................................................................................................. 4
Overall dimensions [mm]......................................................................................................................................................... 4
Mounting and set-up.................................................................................................................................................................. 5
Battery replacement.................................................................................................................................................................... 6
Control panel operation............................................................................................................................................................ 7
Control panel ................................................................................................................................................................................... 7
1. Main menu................................................................................................................................................................................... 7
2. Unit activation and deactivation .................................................................................................................................... 7
3. Fan speed changeover.......................................................................................................................................................... 8
4. Temperature setting ............................................................................................................................................................... 9
5. User menu .................................................................................................................................................................................... 9
6. Engineering menu................................................................................................................................................................... 10
7. Air flow setting........................................................................................................................................................................... 11
8. Temperature sensor ................................................................................................................................................................ 11
9. Language selection................................................................................................................................................................. 11
10. Extra options............................................................................................................................................................................. 12
11. Password change................................................................................................................................................................... 13
12. Standby mode setting........................................................................................................................................................ 13
13. Display brightness adjustment..................................................................................................................................... 13
14. Humidity setting .................................................................................................................................................................... 14
15. Error control.............................................................................................................................................................................. 14
16. Control panel temperature sensor correction..................................................................................................... 15
17. Default settings....................................................................................................................................................................... 15
18. Current temperature review........................................................................................................................................... 15
19. AUTO mode (scheduled operation)........................................................................................................................... 16
20. Date and time.......................................................................................................................................................................... 17
21. Timer.............................................................................................................................................................................................. 18
22. Motor hours .............................................................................................................................................................................. 19
23. Errors.............................................................................................................................................................................................. 19
Error code description................................................................................................................................................................ 20
Factory settings .............................................................................................................................................................................. 20
CONTENTS
This user’s manual is a main operating document intended for technical, maintenance, and operating staff.
The manual contains information about purpose, technical details, operating principle, design, and installation of the PU SENS 01 unit
and all its modifications.
Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to
work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.
The information in this user’s manual is correct at the time of the document’s preparation.
The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to
incorporate the latest technological developments.
No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means in any information
search system or translated into any language in any form without the prior written permission of the Company.
All manuals and user guides at all-guides.com

3
www.ventilation-system.com
UNIT MOUNTING AND OPERATION SAFETY PRECAUTIONS
• Disconnect the unit from power mains prior
to any installation operations.
• Do not operate the unit outside the
temperature range stated in the user's
manual.
• Do not operate the unit in aggressive or
explosive environments.
• Do not lay the power cable of the unit in
close proximity to heating equipment.
• While installing the unit follow the safety
regulations specific to the use of electric
tools.
• Do not change the power cable length at
your own discretion.
• Do not bend the power cable.
• Avoid damaging the power cable.
• Do not put any foreign objects on the
power cable.
• Unpack the unit with care.
• Do not use damaged equipment or cables
when connecting the unit to power mains.
• When the unit generates unusual sounds,
odour or emits smoke disconnect it from
power supply and contact the Seller.
• Do not touch the unit controls with wet
hands.
• Do not carry out the installation and
maintenance operations with wet hands.
• Do not wash the unit with water.
• Protect the electric parts of the unit against
ingress of water.
• Do not allow children to operate the unit. • Disconnect the unit from power mains prior
to any technical maintenance.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED MUNICIPAL WASTE.
SAFETY REQUIREMENTS
• Please read the user’s manual carefully prior to installing and operating the unit.
• All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical
norms and standards must be observed when installing and operating the unit.
• The warnings contained in the user’s manual must be considered most seriously since they contain vital personal safety information.
• Failure to follow the rules and safety precautions noted in this user’s manual may result in an injury or unit damage.
• After a careful reading of the manual, keep it for the entire service life of the unit.
• While transferring the unit control, the user’s manual must be turned over to the receiving operator.
All manuals and user guides at all-guides.com

4
PU SENS 01
www.ventilation-system.com
TECHNICAL DATA
88
130 34 70
R3
4,5
4,5 65,5
Overall dimensions [mm]
PURPOSE
The sensor control panel is designed to control domestic and industrial air handling units as well as other air processing units. It is rated
for continuous operation.
THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED
PHYSICAL, MENTAL, OR SENSORY CAPACITIES, OR THOSE WITHOUT THE APPROPRIATE
TRAINING. THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY
QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING.
THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED
ACCESS BY UNATTENDED CHILDREN.
PARAMETER VALUE
Ambient temperature [°C] from +5 up to +40
Relative humidity [%] from 5 to 80 (no condensation)
Cable cross section [mm] from 0.25 up to 0.75
Material plastic
Dimensions (WхHхD) [mm] 130х86х30
Cable length [m] from 10 up to 30
Ingress protection IP20
All manuals and user guides at all-guides.com

5
www.ventilation-system.com
READ THE USER'S MANUAL BEFORE INSTALLING THE UNIT.
DO NOT LAY THE CABLE IN CLOSE PROXIMITY TO THE CONTROL PANEL CABLE!
WHILE ROUTING THE CONTROL PANEL CABLE DO NOT COIL THE EXTRA LENGTH.
Control panel mounting sequence
• Make a recess in the wall for a mounting box and lay the
cable from the air handling unit.
Recommended cable length
from the wall surface is 90 mm
• Install the mounting box.
• Remove the screws on the panel edge. • Disassemble the panel by separating the frontal part from
the back part.
• Pass the cable into the rectangular opening on the back
part of the control panel and fix the panel on the mounting
box.
• Connect the cable to the control board and install the
frontal part of the panel using the screws.
MOUNTING AND SET-UP
RECOMMENDED CROSS-SECTIONS OF THE CABLE CONNECTING THE CONTROL PANEL TO THE UNIT
Cable cross section ≥ 0.25 mm² ≥ 0.5 mm² ≥ 0.75 mm²
Cable length up to 10 m up to 20 m up to 30 m
All manuals and user guides at all-guides.com

6
PU SENS 01
www.ventilation-system.com
Battery replacement
The battery keeps the internal clock running while the unit is disconnected from power supply.
If the unit is disconnected from power supply and the battery is low, the clock stops and the day and time settings are reset. This leads
to incorrect date and time indication when the unit is on and, as a result, to incorrect scheduled operation of the unit. In this case, the
battery should be replaced.
To replace the battery use a new battery only.
1. Disconnect the unit from power supply.
2. Remove two screws in the bottom part of the casing.
3. Pull the top part of the casing aside to allow access to the upper circuit board. Replace the battery. The control panel uses a CR1220
lithium battery.
4. Assemble the control panel in the reverse order. If the terminal block wires on the upper circuit board were unplugged make sure to
reconnect them correctly. Failure to reconnect the wires properly may knock the equipment out of service.
5. Connect the panel to the power supply and set the current date and time.
All manuals and user guides at all-guides.com
all-guides.com

7
www.ventilation-system.com
CONTROL PANEL OPERATION
Control panel
Ventilation units are controlled via a sensor control panel.
The Main menu is shown after switching on the control panel.
1. Main menu
The Main menu contains the date, current humidity, time, temperature and
set air flow. This menu also works as a hub for accessing the main control
panel functions and menus.
MENU — access to the User menu, see para. 5.
AUTO — scheduled operation activation/deactivation.
TEMPERATURE — display of the current indoor temperature.
After pressing this button the Temperature Setting menu is opened, see
para. 4.
ON/ OFF — turning the unit on/off.
TIMER — turning the timer on/off.
AIR FLOW — current fan speed display. The Fan Speed Setting menu is
accessible through this button, see para. 3.
CONTROL PRIORITIES:
1. Timer: When the timer is active, the unit switches to the timer-scheduled
operation and ignores the schedule settings (AUTO mode) and manual
control settings (AIR FLOW and TEMPERATURE).
2. Auto: When the AUTO mode is active, the unit switches to scheduled
operation and ignores manual control settings of air flow and temperature,
provided that the timer is off.
3. Manual control settings of air flow and temperature: If the TIMER and
AUTO modes are off, the unit operates in accordance with manual control
settings of air flow and temperature.
EXAMPLE 1FOR UNIT OPERATION IN ACCORDANCEWITH CONTROL
PRIORITIES:
1. The AUTO mode is on, the unit follows the schedule: the 2nd speed in
accordance with schedule settings.
2. The user activates the timer by pushing the appropriate button. The unit
switches to the TIMER mode: the 3rd speed during 4 hours in accordance
with timer settings.
3. When 4 hours of timer-scheduled operation expire, the timer turns off
and the unit switches to the scheduled operation mode automatically: the
2nd speed in accordance with schedule settings.
2. Unit activation and deactivation
• The unit is switched on/off using the ON (green color) / OFF
(red color) buttons.
Upon deactivation of the ventilation unit the icon changes from green to
red.
The STANDBY mode parameters are set in the Engineering menu (see
para. 12).
All manuals and user guides at all-guides.com

8
PU SENS 01
www.ventilation-system.com
3. Fan speed changeover
• Press the AIR FLOW button to select the desired fan speed.
The unit has four speed stages:
— first speed
— second speed
— third speed
— humidity control mode. The fan speed is regulated depending
on the humidity setting. The unit does not provide additional built-in
humidifiers or dehumidifiers. If the room humidity is higher than the set
level, the unit slowly increases the speed. If the room humidity is lower
than the set level, the unit slowly decreases the speed.
In this way, the humidity is maintained at the set level.
The humidity level is set via the Engineering menu, see para. 14.
• If the AUTO or TIMER mode is activated the current airflow value is
displayed in real time operation no matter of the air flow value set by
means of the AIR FLOW button.
1
• Set the required speed using or .
• Then press ENTER .
• To return to the Main menu without saving changes press EXIT .
All manuals and user guides at all-guides.com

9
www.ventilation-system.com
4. Temperature setting
• Press the TEMPERATURE button .
• Select the set temperature type: DUCT (temperature in the air
duct) ROOM (temperature in the room).
25
• Then use and to set the desired temperature parameter value.
• Press ENTER to save the set parameter.
• To return to the Main menu without saving changes press EXIT .
5. User menu
• To enter the User menu press MENU in the control panel Main
menu.
• The User menu contains basic menu items and functions for parameters
setting:
ENG. MENU — access to the Engineering menu. The menu is password-
protected.
AUTO ADJUST. — scheduled operation setting.
DATE AND TIME — date and time setting.
TIMER ADJUST. — setting time and speed operation on timer basis.
MOTOR HOURS — setting filter replacement periodicity.
EXIT — return to the Main menu.
All manuals and user guides at all-guides.com

10
PU SENS 01
www.ventilation-system.com
6. Engineering menu
• To enter the Engineering menu press ENG. MENU in the User
menu.
• Enter the password (1111 by default).
• Press OK.
When the incorrect password is entered press RESET and enter the
password again.
• To return to the Engineering menu press EXIT .
• If you forgot the user-defined password, see para. 11 Password Change,
press and hold RESET until you hear a long sound signal (20 clicks,
approximately 20 seconds).
• The default password 1111 is set.
FOR NAVIGATING IN THE ENGINEERING MENU USETHE FOLLOWING
BUTTONS:
— moving upwards in the list
— moving downwards in the list
— select the value from the parameter list
— return to the User menu
All manuals and user guides at all-guides.com

11
www.ventilation-system.com
7. Air ow setting
40
40
70
70
99
99
• Select the AIR FLOW SETTING item from the Engineering menu and
press ENTER .
• Select the edited speed value (the selected value is highlighted with a
rectangle).
• Use or buttons to set the air flow value for each fan speed
stage.
• The air flow is set as a percentage of the maximum performance of each
fan.
• To return to the Engineering menu without saving changes press
EXIT .
8. Temperature sensor
• To select the heating control sensor from the Engineering menu select the
TEMPERATURE SENSOR submenu and press ENTER .
• Select a desired sensor type.
• Press ENTER to confirm.
• To return to the Engineering menu without saving changes press
EXIT .
The duct temperature sensor is installed in the supply air duct downstream
of the heat exchanger.
The room temperature sensor is integrated in the control panel.
9. Language selection
• To select the control panel interface language select the LANGUAGE
submenu from the Engineering menu and press ENTER .
• Select the desired language from the list.
• Press ENTER to confirm.
• To return to the Engineering menu without saving changes press
EXIT .
All manuals and user guides at all-guides.com
all-guides.com

12
PU SENS 01
www.ventilation-system.com
10. Extra options
• Select the EXTRA OPTIONS item in the Engineering menu and press
ENTER .
• HEATING CONTROL activates heater operation.
Before activating the HEATING CONTROL MODE turn off the SUPPLY
FAN OFF MODE by selecting the OFF button.
• The SUPPLY FAN OFF MODE activates the heat exchanger freeze
protection and can only be activated when the HEATING CONTROL
option is OFF.
To activate the heat exchanger freezing protection function by means of
the supply fan deactivation set the HEATING CONTROL parameter value
to OFF.
To proceed to the mode settings set the SUPPLY FAN OFF MODE
parameter to ON.
• HUMIDITY SENSOR SELECTION - selection of the humidity sensor for
controlling the unit.
1 — the sensor is installed in the extract air duct.
2 — the sensor is installed indoors.
• BYPASS OPERATION MODES:
1 — automatic mode for set temperature maintenance and freeze
protection.
2 — manual mode for positive air damper opening for natural ventilation.
The Summer Bypass only works for outdoor temperatures over 10°C
WARNING: It is not recommended to use the manual bypass mode (2)
during the winter period to prevent room overcooling.
Only AUTO mode (1) should be used during the winter period.
• To save the changes and return to the Engineering menu press .
20
5
+3
• If the SUPPLY FAN OFF MODE parameter is set to ON the control panel
switches to the SUPPLY FAN OFF MODE setting.
• Select an item by touching the respective field: WORKING HOURS,
DOWNTIME and SWITCH-OFF TEMPERATURE (the temperature is set
according to the outdoor temperature sensor readings defined in the range
from +10 °C to -20 °C).
• Then use and to set the desired value.
• Press ENTER to confirm the set parameters.
• To return to the Engineering menu without saving changes press
EXIT .
All manuals and user guides at all-guides.com

13
www.ventilation-system.com
11. Password change
• Select the PASSWORD CHANGE submenu from the Engineering menu
and press ENTER .
• Then enter the new password for accessing the Engineering menu.
• Press OK.
• When the incorrect password is entered press RESET and enter the
password again.
• To return to the Engineering menu press EXIT .
12. Standby mode setting
0 20
• Select the STANDBY MODE item in the Engineering menu and press
ENTER .
• Then use the or buttons to select:
0 — deactivation of the unit
1 — standby mode
While in the Standby mode the ventilation unit runs at the first speed at the
pre-set temperature.
• Press ENTER to confirm.
• To return to the Engineering menu without saving changes press
EXIT .
13. Display brightness adjustment
50 1
• Select the BRIGHTNESS ADJUSTMENT submenu from the Engineering
menu and press ENTER .
• Then use the or to set the brightness for the OPERATION
and SLEEP modes.
The panel switches to the SLEEP mode 30 seconds after the last screen
interaction.
• Press ENTER to confirm.
• To return to the Engineering menu without saving changes press
EXIT .
All manuals and user guides at all-guides.com

14
PU SENS 01
www.ventilation-system.com
14. Humidity setting
50
• Select the HUMIDITY SETTING item in the Engineering menu and press
ENTER .
• Then select the humidity control location:
DUCT — the humidity level is controlled in the extract duct
upstream of the heat exchanger.
Make sure that a duct humidity sensor is included in the scope of delivery
to control duct humidity.
ROOM — the humidity level is controlled in the room where the
control panel is installed.
The control panel is equipped with a humidity sensor.
• Then use or to set the desired humidity level.
• Press ENTER to confirm.
• To return to the Engineering menu without saving changes press
EXIT .
In the HUMIDITY CONTROL mode the minimum air ow is equal to the air
ow at the low speed.
15. Error control
• To receive information regarding the last error select ERROR CONTROL
submenu from the Engineering menu and press ENTER .
• The display shows the error date and code.
• To return to the Engineering menu press EXIT .
• Errors description is stated in the respective table below.
All manuals and user guides at all-guides.com

15
www.ventilation-system.com
16. Control panel temperature sensor correction
4
• TocorrectthepaneltemperaturesensorindicationsselectTEMPERATURE
CORRECTION submenu from the Engineering menu and press
ENTER .
• Then use the or buttons to set the temperature correction for
the room temperature sensor installed in the control panel casing.
THE DEFAULT FACTORY SETTING FOR THE TEMPERATURE
SENSOR CORRECTION IS -4 °C.
CORRECTION IS NECESSARY TO COMPENSATE SENSOR ERRORS
CAUSED BY HEATING OF CONTROL PANEL INTERNAL ELEMENTS.
• To return to the Engineering menu without saving changes press
EXIT .
17. Default settings
• To reset the controller settings to the factory defaults select DEFAULT
SETTINGS submenu from the Engineering menu and press ENTER .
• Press ENTER to confirm the reset.
• To return to the Engineering menu without saving changes press
EXIT .
• The default settings are given in the table below.
18. Current temperature review
6
15
20
OFF
OFF
• Select the CURRENT TEMPERATURES item in the Engineering menu
and press ENTER .
• The display will show the current temperature sensor readings:
OUTDOOR — readings of the temperature sensor installed outdoors or in
the outdoor air duct upstream of the heat exchanger.
DUCT — readings of the temperature sensor installed in the supply duct
downstream of the heat exchanger.
AFTER THE HEAT EXCHANGER — readings of the temperature sensor
installed in the extract duct downstream of the heat exchanger.
REVERSE FLUID — return heat medium temperature sensor readings.
AFTER THE AIR HEATER — readings of the temperature sensor installed
in the supply duct downstream of the water heater.
• If any temperature sensor of the ventilation unit is missing its configuration
value is displayed as OFF.
• To return to the Engineering menu press EXIT .
All manuals and user guides at all-guides.com

16
PU SENS 01
www.ventilation-system.com
19. AUTO mode (scheduled operation)
• The AUTO mode enables scheduled operation of the ventilation unit.
The unit runs at the preset speed and temperature during the specified
time periods.
The unit is in the STANDBY mode between the operating periods.
• To activate the AUTO mode press the AUTO button in the Main
menu.
• Activation of the AUTO mode is confirmed with a tick .
The AUTO mode has a higher priority than manual control settings of air
ow and temperature but lower priority than the TIMER mode. When the
TIMER mode is activated the AUTO mode is inactive.
When the AUTO mode is active, the unit switches to scheduled operation
and ignores manual control settings of air ow and temperature, provided
that the timer is o.
• To set up the AUTO mode press the button to enter the User
menu, see para. 5, and press AUTO ADJUST .
• Select the day to enable the AUTO mode. Upon entering the menu the
value is set to the current day. To change the day press the DAY field.
• Then use the or buttons to set the time, air flow and temperature
for the selected day by pressing the respective parameter field.
• Depending on the STANDBY mode settings, the unit remains in the
STANDBY mode or turns off between the operating periods.
• To return to the Engineering menu and save changes automatically press
EXIT .
All manuals and user guides at all-guides.com
all-guides.com

17
www.ventilation-system.com
The date and time on the control panel must be set correctly (described in the present manual).
• The unit operation schedule is programmed for each day of the week individually.
• The schedule contains 6 lines with parameters for setting the operating modes within one day.To select the other day of the week, click
on the day of the week in the upper right corner of the screen.
• Each schedule line can contain any time values, but within one day.
The initial value of the time in the line (the one on the left) should not exceed the finite time interval (the one on the right). Otherwise,
the difference in these intervals will be negative and the AUTO mode will not work.
• If the time intervals of different schedule lines overlap in time, the priority will be given to the line that Is listed lower.
Example:
1st line 10:00 -12:00 120
2nd line 11:00 -13:00 220
In the interval from 10:00 to 11:00, the unit will operate at the first speed, and from 11:00 will switch to the second speed, since the lower
line has a higher priority than the top line.
• If there are temporary breaks between different lines of the schedule, the unit will operate in the STANDBY mode in these time
intervals (between lines).
• If"0" is set in the STANDBY mode settings, the unit will turn off. If "1" is set in the STANDBY mode settings, then the unit will operate
at minimum speed.
Example:
1st line 10:00 -12:00 120
2nd line 13:00 -14:00 220
• The unit will operate in the STANDBY mode in the range between 12:00 and 13:00.
20. Date and time
• To set the date and time on the control panel go to the User menu by
pressing (see para. 5) and then press DATE, TIME .
11 1501
012012
• Then adjust the year, month, date, hour and minutes by pressing
and .
• Press ENTER to confirm the set parameter.
• To return to the Engineering menu without saving changes press
EXIT .
All manuals and user guides at all-guides.com

18
PU SENS 01
www.ventilation-system.com
2020
21. Timer
• To activate the timer press TIMER in the control panel Main menu.
• To set up the TIMER mode press to enter the User menu, see
para. 5, and press TIMER ADJUST .
The TIMER mode has a higher priority than the AUTO mode and manual
control settings of air ow and temperature. When the timer is active, the
unit switches to the timer-scheduled operation and ignores the schedule
settings (AUTO mode) and manual control settings (AIR FLOW and
TEMPERATURE).
• Activation of the TIMER function is confirmed with a tick .
The timer cannot be activated once the HUMIDITY CONTROL mode is on.
01 00 0 20
• Use or buttons to set the time, air flow and air temperature
values.
• Press ENTER to confirm the set parameters.
• To return to the Engineering menu without saving changes press
EXIT .
All manuals and user guides at all-guides.com

19
www.ventilation-system.com
22. Motor hours
The MOTOR HOURS function enables the user to set up filter cleaning
or replacement periodicity. Upon expiration of the preset time the panel
displays a filter cleaning or replacement indicator. The indicator is displayed
every 24 hours.
Press the RESET button to reset the motor hours.
• To set up the MOTOR HOURS function enter the User menu by pressing
the button, see para. 5, and press MOTOR HOURS .
4000
2569
• Use the or buttons to set the filter replacement interval.
• The OPERATING HOURS window shows the time elapsed from the filter
installation.
• Press RESET after replacement of the filter.
• To save the changes and return to the Engineering menu press
EXIT .
23. Errors
• The control panel displays the following message in case of any
malfunctions in the ventilation unit operation.
• To enter the ERROR LIST press EXIT .
• The ERROR LIST can also be accessed from the Engineering menu.
The error code details are stated in the table below.
The error message appears every 30 seconds until the system emergency
cause has been troubleshooted.
• To reset the error alert restart the unit once the malfunction cause has
been eliminated.
All manuals and user guides at all-guides.com

20
PU SENS 01
www.ventilation-system.com
FACTORY SETTINGS
PARAMETER DEFAULT SETTINGS MEASUREMENT
UNIT
Air flow rate 1 -
Temperature Duct 25 °С
Room 20
Air flow setting
Air supply
first speed 40 %
second speed 70 %
third speed 99 % %
Air extract
first speed 40 %
second speed 70 %
third speed 99 %
Temperature sensor Duct -
Language selection English -
Extra options
Heating control OFF ON/OFF
Supply fan off mode OFF ON/OFF
Humidity sensor selection 2 -
Bypass operation mode 1 -
Supply fan off mode
Working hours 20 Minute
Downtime 5 Minute
Switch-off temperature -1 °С
Standby mode setting Air flow rate 0 -
Temperature 20 °С
Display brightness adjustment Operation 50 -
Sleep 1 -
Humidity setting Duct 50 %
Room 50 %
Temperature sensor correction -4 °С
Timer settings
Hours 01 Hour
Minutes 00 Minute
Air flow rate 1 -
Temperature 20 °С
Motor hours Air handling unit 3000 Hour
ERROR CODE DESCRIPTION
ERROR
CODE
HEATER TYPE
ELECTRIC WATER
TE1 Outdoor temperature sensor malfunction.
TE2 Malfunction of the heat exchanger freezing protection sensor.
TE3 Return heat medium temperature sensor malfunction.
TE4 Water heater freeze protection sensor malfunction.
TE5 Duct temperature sensor malfunction.
MIN Supply fan malfunction.
MEX Exhaust fan malfunction.
ERP Control panel communication error.
DI1 TK60 overheating sensor activation.
DI2 Fire alarm sensor actuation.
DI3 TK90 overheating sensor activation.
DI5 Water pressure sensor malfunction.
All manuals and user guides at all-guides.com
Other manuals for PU SENS 01 A11
1
This manual suits for next models
1
Table of contents
Other Vents Control Panel manuals