
9
RECYCLE AT THE END OF THE SERVICE LIFE.
DO NOT DISPOSE THE PRODUCT WITH UNSORTED MUNICIPAL TRASH.
Parameter
Code Parameter Measurement
Units
Measurement
Range Purpose Default
Value
6 Duct Temperature °С 10-30 Temperature in the air duct. 25
7 Room Temperature °С 10-30 Room temperature. 20
11 Timer Operation - Temperature °С 10-40 Room temperature for timer operation. 20
12 Timer Operation - Air Flow. - 1, 2, 3 Ventilation mode for timer operation. 1
18 Air Flow at Low Speed in Air
Supply Mode % 0-99 Air ow in the supply air duct at low speed (dened as a
percentage of the maximum unit capacity). 40
19 Air Flow at Medium Speed in
Air Supply Mode % 0-99 Air ow in the supply air duct at medium speed (dened
as a percentage of the maximum unit capacity). 70
20 Air Flow at High Speed in Air
Supply Mode % 0-99 Air ow in the supply air duct at high speed (dened as
a percentage of the maximum unit capacity). 99
21 Temperature Sensor Selection. - 0.1
Selection of the Active Temperature Sensor:
0 — Duct;
1 — Room.
0
22 Standby Mode Air Flow - 0.1 Air Flow Rate in the Standby Mode. 1
23 Standby Mode Temperature °С 10-30 User-dened Temperature in the Standby Mode. 20
29 Air Flow at Low Speed in Air
Extract Mode % 0-99 Air ow in the exhaust air duct at low speed (dened as
a percentage of the maximum unit capacity). 40
30 Air Flow at Medium Speed in
Air Extract Mode % 0-99 Air ow in the exhaust air duct at medium speed
(dened as a percentage of the maximum unit capacity). 70
31 Air Flow at High Speed in Air
Extract Mode % 0-99 Air ow in the exhaust air duct at high speed (dened as
a percentage of the maximum unit capacity). 99
33 Supply Fan Shutdown. -1.0
Selection of the freezing protection logic by shutting
down the supply fan:
1 — ON;
0 — OFF.
0
34 Supply Fan Operation Time min. 5-60 Supply fan operation time while the supply fan
shutdown mode is enabled. 20
35 Supply Fan Idling Time min, 5-60 Supply fan idling time while the supply fan shutdown
mode is enabled. 5
36 Supply Fan Shutdown
Temperature °С -5 ... +5
The air duct temperature set point to enable freezing
protection activation logic by shutting down the supply
fan.
+3
39 Bypass Operation Mode. - 1.0
Bypass operation mode selection:
0 — Regular operation mode to prevent heat exchanger
freezing at low temperatures;
1 — Bypass opening for the ventilation mode.
1
41 Duct Humidity % 10-80 Humidity level in the air duct. 50
FACTORY SETTINGS