Vents RS-PS Series User manual

RS-...-PS
Thyristor speed controller
USER'S MANUAL

EN
2
This user’s manual is a main operating document intended for technical, maintenance,
and operating staff.
The manual contains information about purpose, technical details, operating
principle, design, and installation of the RS-...-PS unit and all its modifications.
Technical and maintenance staff must have theoretical and practical training in the
field of ventilation systems and should be able to work in accordance with workplace
safety rules as well as construction norms and standards applicable in the territory of
the country.
Safety requirements 3
Brief description 5
Delivery set 5
Design and operating principle 8
Mounting and set-up 8
Connection to power mains 10
Technical maintenance 11
Troubleshooting 12
Storage and transportation regulations 13
Manufacturer’s warranty 14
CONTENTS
FOLLOW THE USER’S MANUAL REQUIREMENTS TO ENSURE
DURABLE AND
TROUBLE-FREE OPERATION OF THE UNIT

EN
3
SAFETY REQUIREMENTS
All user’s manual requirements as well as the provisions of all the applicable local
and national construction, electrical, and technical norms and standards must be
observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing,
maintenance, and repair operations.
Only qualied electricians with a work permit for electrical units up to 1000 V
are allowed for installation. The present user’s manual should be carefully read
before beginning works.
Check the unit for any visible damage of the impeller, the casing, and the grille before
starting installation. The casing internals must be free of any foreign objects that can
damage the impeller blades.
While mounting the unit, avoid compression of the casing! Deformation of the casing
may result in motor jam and excessive noise.
Misuse of the unit and any unauthorised modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky substances,
or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing spirits,
gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the efficient air
flow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the document’s
preparation.
The Company reserves the right to modify the technical characteristics, design,
or configuration of its products at any time in order to incorporate the latest
technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.

EN
4
This unit is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the unit by a
person responsible for their safety.
Children should be supervised to ensure that they do not play with the unit.
Connection to the mains must be made through a disconnecting device, which
is integrated into the fixed wiring system in accordance with the wiring rules for
design of electrical units, and has a contact separation in all poles that allows for full
disconnection under overvoltage category III conditions.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END
OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.

EN
5
BRIEF DESCRIPTION
The unit provides manual speed control of voltage-controlled motors (230 V/50 Hz)
by varying the voltage supplied by adjusting the phase angle.
Suitable for wall (IP44) and built-in (IP54) mounting.
The splash-proof casing allows the unit to be used in harsh working environments.
The orange LED indicates the operating status.
The controller allows the control of several motors, as long as the total current
consumption does not exceed the current limit of the controller.
All models have an optional (non-adjustable) 230 V output.
Technical data
• Smooth speed control.
• Adjustment from minimum to maximum speed.
• Adjustment of the minimum speed with the integrated trimmer.
• Fuse 5 x 20 mm, spare fuse included.
• Operating status indication.
Speed controller – 1 pc.
Fuse holder with a spare fuse – 1 pc.
User’s manual – 1 pc.
Packing – 1 pc.
DELIVERY SET

EN
6
Name RS-0.5-PS RS-1.5-PS RS-2.5-PS RS-4.0-PS
Voltage [V/Hz] 230/50
Fan motor operating
voltage [V/Hz] 230/50
Min. load current [A] 0.1 0.15 0.25 0..4
Max. load current [A] 0.5 1.5 2.5 4.0
Rated current of the fuse
[A] 0.63 1.5 2.5 4.0
Wire cross section [mm2] max. 2.5
Maximum ambient air
temperature [°C] +35
Weight [kg] 0,23 0,24 0,29 0,36
SEC class IP44 (flush mounting)
IP54 (surface mounting)
BEFORE MOUNTING MAKE SURE THE CASING DOES NOT
CONTAIN ANY FOREIGN OBJECTS (E.G. FOIL, PAPER).

EN
7
89 82
62
62
7
50
82 65 24 32
WHILE INSTALLING THE UNIT ENSURE CONVENIENT ACCESS
FOR SUBSEQUENT MAINTENANCE AND REPAIR.

EN
8
MOUNTING AND SET-UP
min
N N
Fuse
Minimum speed
adjustment trimmer
Operating status
indicator
DESIGN AND OPERATING PRINCIPLE
89 82
62
62
7
50
82 65 24 32
The controller should be installed on a vertical wall indoors in a hidden mounting box.
Inspect the unit visually and check the casing for integrity.

EN
9
Flush mounting (IP44)
To connect the controller to power mains, follow the steps below:
• Cut off power supply.
• Remove the control knob of the controller.
• Detach the fasteners and remove the decorative cover.
• Disconnect the controller fasteners from the mounting box and remove the
controller.
• Lead the connecting wires into the mounting box.
• Connect the controller as shown in the wiring diagram.
• The conductors are connected to the unit using screw terminals.
• Install the controller in the mounting box with the terminal block at the bottom.
• Install the mounting box in the wall with the connection terminals facing
downwards.
• Apply the mains voltage and switch on the controller.
• Adjust the minimum fan speed at the end position of the control knob.
• Turn of the controller.
• Wait for the fan to stop.
• Turn on the controller to the minimum speed, the fan should rotate steadily at the
minimum speed.
• Put on the decorative cover.
• Put on the control knob.
• Unscrew the knob to the off position.
• The system is ready for operation.
Surface mounting (IP54)
To connect the controller to power mains, follow the steps below:
• Cut off power supply.
• Fasten the casing to the wall, including cable routing.
• Remove the control knob of the controller.
• Detach the fasteners and remove the decorative cover.
• Lead the connecting wires into the mounting box.
• Connect the controller as shown in the wiring diagram.
• The conductors are connected to the unit using screw terminals.

EN
10
Power supply 230 V/50 Hz
Non-regulated 230 V/2 A output
N Neutral
Regulated motor output
CONNECTION TO POWER MAINS
• Install the inner part of the controller into the mounting box with the screws.
• Apply the mains voltage and switch on the controller.
• Adjust the minimum fan speed at the end position of the control knob.
• Turn of the controller.
• Wait for the fan to stop.
• Turn on the controller to the minimum speed, the fan should rotate steadily at the
minimum speed.
• Install the decorative cover.
• Put on the control knob.
• Unscrew the knob to the off position.
• If necessary, drill a 5 mm hole for condensation water outlet at the base in case of
wall mounting.
• The system is ready for operation.

EN
11
TECHNICAL MAINTENANCE
The unit is maintenance-free under normal operating conditions.
In case of light soiling, it is cleaned with a dry or slightly damp cloth.
In case of heavy soiling, clean with non-aggressive detergents.
In this case, the unit must be disconnected from the power supply.
Note that no liquids must be allowed to enter the unit.
The unit may only be reconnected to power mains after it has dried completely!
Periodically clean the unit of dust, lint, etc.
Make sure that the external electrical leads are securely attached to the screwed
terminals of the unit.
Replacing the fuse
Return the fuse knob to its original position by turning it to the end position and
then pull it towards you.
Remove the cover.
Remove the fuse holder with a screwdriver.
Replace the fuse holder.
Assemble the unit in the reverse order.
Use only recommended fuses (industrial, high breaking capacity).
The unit warranty does not apply if unsuitable fuses are used.
DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY
MAINTENANCE OPERATIONS!
MAKE SURE THE UNIT IS DISCONNECTED FROM POWER MAINS
BEFORE REMOVING THE PROTECTION

EN
12
TROUBLESHOOTING
Problem Possible reasons Troubleshooting
The controller does
not work.
Limited or no connection. Check the correctness of
connection to power mains.
The fuse is broken. Replace the fuse.
The fan does not
rotate when the
controller is on.
The minimum fan speed is
not set correctly.
Adjust the minimum fan
speed.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL
ENSURE A LONG AND TROUBLE-FREE OPERATION OF THE
UNIT.

EN
13
STORAGE AND TRANSPORTATION REGULATIONS
• Store the unit in the manufacturer’s original packaging box in a dry closed
ventilated premise with temperature range +5 ˚С...+40 ˚С and relative humidity
up to 70 %.
• Storage environment must not contain aggressive vapors and chemical mixtures
provoking corrosion, insulation, and sealing deformation.
• Use suitable hoist machinery for handling and storage operations to prevent
possible damage to the unit.
• Follow the handling requirements applicable for the particular type of cargo.
• The unit can be carried in the original packaging by any mode of transport provided
proper protection against precipitation and mechanical damage. The unit must be
transported only in the working position.
• Avoid sharp blows, scratches, or rough handling during loading and unloading.
• Prior to the initial power-up after transportation at low temperatures, allow the unit
to warm up at operating temperature for at least 3-4 hours.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW
ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT
DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE
DATE STAMP.

EN
14
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage guidelines
and electromagnetic compatibility. We hereby declare that the product complies
with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of
the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/
EU of the European Parliament and of the Council and CE-marking Council Directive
93/68/EEC. This certificate is issued following test carried out on samples of the
product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months after
the retail sale date provided the user's observance of the transportation, storage,
installation, and operation regulations. Should any malfunctions occur in the course
of the unit operation through the Manufacturer's fault during the guaranteed period
of operation, the user is entitled to get all the faults eliminated by the manufacturer
by means of warranty repair at the factory free of charge. The warranty repair includes
work specific to elimination of faults in the unit operation to ensure its intended use
by the user within the guaranteed period of operation. The faults are eliminated by
means of replacement or repair of the unit components or a specific part of such unit
component.
The warranty repair does not include:
• routine technical maintenance
• unit installation/dismantling
• unit setup
To benefit from warranty repair, the user must provide the unit, the user's manual with
the purchase date stamp, and the payment paperwork certifying the purchase. The
unit model must comply with the one stated in the user’s manual. Contact the Seller
for warranty service.
The manufacturer’s warranty does not apply to the following cases:
• User’s failure to submit the unit with the entire delivery package as stated in the
user’s manual including submission with missing component parts previously
dismounted by the user.
• Mismatch of the unit model and the brand name with the information stated

EN
15
on the unit packaging and in the user's manual.
• User’s failure to ensure timely technical maintenance of the unit.
• External damage to the unit casing (excluding external modifications as
required for installation) and internal components caused by the user.
• Redesign or engineering changes to the unit.
• Replacement and use of any assemblies, parts and components not approved
by the manufacturer.
• Unit misuse.
• Violation of the unit installation regulations by the user.
• Violation of the unit control regulations by the user.
• Unit connection to power mains with a voltage different from the one stated in
the user's manual.
• Unit breakdown due to voltage surges in power mains.
• Discretionary repair of the unit by the user.
• Unit repair by any persons without the manufacturer’s authorization.
• Expiration of the unit warranty period.
• Violation of the unit transportation regulations by the user.
• Violation of the unit storage regulations by the user.
• Wrongful actions against the unit committed by third parties.
• Unit breakdown due to circumstances of insuperable force (fire, flood,
earthquake, war, hostilities of any kind, blockades).
• Missing seals if provided by the user’s manual.
• Failure to submit the user’s manual with the unit purchase date stamp.
• Missing payment paperwork certifying the unit purchase.

www.ventilation-system.com
V20-3EN-04
Quality Inspector's
Stamp
Manufacture Date
Sold by
(name and stamp of the
seller)
Purchase Date
This manual suits for next models