Veris Industries Hawkeye H749 User manual

TM
CURRENT MONITORING INSTALLATION GUIDE
Z201491-0A PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 02121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Solid-Core Current Switch, Adjustable Trip Point
With Command Relay, 120VAC/DC Status Output
Installer’s Specifications
Amperage Range 1-135 A continuous
Sensor Power Induced from monitored current
Insulation Class 600 VAC RMS
Frequency Range 50/60 Hz
Temperature Range -15° to 60°C (5°to 140°F)
Humidity Range 10-90% RH non-condensing
Hysteresis 10% of setpoint, typical
Terminal Block Maximum WIre Size 14 AWG
Terminal Block Torque (nominal) 4 in-lbs (0.45 N-m)
Status Output N.O. 0.2 A@120 VAC/DC
Relay Coil 24 VAC/DC, 10 mA
Relay Contact Resistive: 8 A@250 VAC, 30 VDC; Inductive: 3.5 A@250 VAC, 30 VDC
Agency Approvals UL508 E150462
Do not use the LED status indicators as evidence of applied voltage.
The product design provides for basic insulation only.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
Fan or Pump
CONTROLLER
DI
(Status)
DO
(Relay
Coil)
Motor
CONTACTOR
CONTROL
POWER
Wiring ExamplE
H749 TM 749
DimEnsions
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
installation
Disconnect and lock out power to the enclosure containing the
conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the center window when it is installed
and that will keep the device at least 1/2” from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.
2. Route the conductor through the sensor’s center window and slip the assembly
into the mounting bracket. Terminate the conductor. See Notes (page 2) for
currents under 1 Amp or above 135 Amps.
3. Wire the output connections to the DDC controller or switched load (solid state
contact).
4. Secure enclosure and reconnect power.
5. Calibrate the sensor (see Calibration section).
0.2”x 0.15”
slot (2x)
1.1"
(27 mm)
2.8"
(68 mm)
 0.7"
(19 mm)
0.9"
(23 mm)
3.0"
(75 mm)
Removable/Adjustable Mounting Bracket
3.8"
(95 mm)
4.2"
(106 mm)
Z201491-0A PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 02121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
INSTALLATION GUIDE
H749
opEration
The H749 is a current-sensitive switching device that monitors current (amperage) in
the conductor passing through it. A change in the conductor’s amperage that crosses
the adjustable switch threshold plus the hysteresis value causes the resistance of
the FET status output to change state, similar to the action of a mechanical switch.
In this model, the setpoint is adjustable through the action of a twenty (20) turn
potentiometer (see the CALIBRATION section). An integrated relay allows start/
stop control. The status output is suitable for connection to building controllers or
other appropriate data acquisition equipment operating at up to 120 volts. The H749
requires no external power supply to generate its output.
troublEshooting
Problem Solution
No Reading at Controller • Check sensor calibration (see above)
• Check for control voltage at sensor (<120 V)
• Check for amperage in monitored conductor (>1 A)
Setpoint screw has no
stops
The setpoint screw has a slip-clutch at both ends of its travel to
avoid damage. Twenty turns CCW will reset the sensor to be
most sensitive. Repeat calibration above.
Both LEDs are lit Setpoint screw is too far clockwise. See solution above.
Calibration
A. To monitor under-current (belt loss, coupling shear, status)
A
OK!
!
1. Turn setpoint screw
clockwise until Status OPEN
LED turns ON.
2. Slowly turn the screw counter-clockwise until the Status CLOSED LED just
turns ON.
3. Turn the screw an
additional 1/4 turn
counter-clockwise for
operational margin.
B. To monitor over-current (mechanical problems, seized impeller)
A
OK!
!
3. Turn the setpoint
screw an additional
1/4 turn clockwise for
operational margin.
1. Turn setpoint screw
counter-clockwise until Status
CLOSED LED turns ON.
2. Slowly turn the setpoint screw clockwise until the Status OPEN LED just turns ON.
OK!
STATUS
OK!
STATUS
Setpoint
Status
Open
STOP
Setpoint Status
Closed
STOP
1/4
Setpoint
+
Setpoint Status
Closed
STOP
Setpoint
Status
Open
STOP
+
1/4
Setpoint
Before beginning calibration, establish normal load conditions.
OK!
A
OK!
Then choose either A or B below.
4x
0.5A
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
H68xx-5A CT
240A
300A:5A
> 135 A (Sensor max.)
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
< 1 A (Sensor Min.)
notEs
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be
combined with wrapping (see below) to add range for a low current load on a high
current source.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns. This increases the current measured by the
transducer.

Other Veris Industries Measuring Instrument manuals

Veris Industries HW2 Series User manual

Veris Industries

Veris Industries HW2 Series User manual

Veris Industries E50H Series User manual

Veris Industries

Veris Industries E50H Series User manual

Veris Industries E31E Series User manual

Veris Industries

Veris Industries E31E Series User manual

Veris Industries E30 Series User manual

Veris Industries

Veris Industries E30 Series User manual

Veris Industries H5004 User manual

Veris Industries

Veris Industries H5004 User manual

Veris Industries E50B1 User manual

Veris Industries

Veris Industries E50B1 User manual

Veris Industries E31A004 User manual

Veris Industries

Veris Industries E31A004 User manual

Veris Industries H8030 User manual

Veris Industries

Veris Industries H8030 User manual

Veris Industries E51H2A User manual

Veris Industries

Veris Industries E51H2A User manual

Veris Industries E50C A Series User manual

Veris Industries

Veris Industries E50C A Series User manual

Veris Industries E31E84 User manual

Veris Industries

Veris Industries E31E84 User manual

Veris Industries E50H2A User manual

Veris Industries

Veris Industries E50H2A User manual

Veris Industries E30E Series User manual

Veris Industries

Veris Industries E30E Series User manual

Veris Industries E31 Series User manual

Veris Industries

Veris Industries E31 Series User manual

Veris Industries FSR Series User manual

Veris Industries

Veris Industries FSR Series User manual

Veris Industries H8150-1600-4-3 User manual

Veris Industries

Veris Industries H8150-1600-4-3 User manual

Veris Industries E30C184 User manual

Veris Industries

Veris Industries E30C184 User manual

Veris Industries ENERCEPT H8035 User manual

Veris Industries

Veris Industries ENERCEPT H8035 User manual

Veris Industries E50C1A User manual

Veris Industries

Veris Industries E50C1A User manual

Veris Industries E51H2 User manual

Veris Industries

Veris Industries E51H2 User manual

Veris Industries E54C3C User manual

Veris Industries

Veris Industries E54C3C User manual

Veris Industries E50 Series User manual

Veris Industries

Veris Industries E50 Series User manual

Veris Industries ENERCEPT H8051 Series User manual

Veris Industries

Veris Industries ENERCEPT H8051 Series User manual

Veris Industries E50C1 User manual

Veris Industries

Veris Industries E50C1 User manual

Popular Measuring Instrument manuals by other brands

Hilti PR 35 operating instructions

Hilti

Hilti PR 35 operating instructions

Vega VEGAPULS 56K Operating	 instruction

Vega

Vega VEGAPULS 56K Operating instruction

KAM Star Cluster Micro V2 instruction manual

KAM

KAM Star Cluster Micro V2 instruction manual

Kusam-meco KM-01 instruction manual

Kusam-meco

Kusam-meco KM-01 instruction manual

Siko DE04 User information

Siko

Siko DE04 User information

Grundfos AquaCel AQC-D3 Installation and operating instructions

Grundfos

Grundfos AquaCel AQC-D3 Installation and operating instructions

Sealey AK9991 manual

Sealey

Sealey AK9991 manual

Panasonic LH2H preset manual

Panasonic

Panasonic LH2H preset manual

Megger KF-875 user guide

Megger

Megger KF-875 user guide

AEM 30-5133 manual

AEM

AEM 30-5133 manual

Camille Bauer SINEAX CAM operating instructions

Camille Bauer

Camille Bauer SINEAX CAM operating instructions

BIOPAC Systems MP41 Hardware guide

BIOPAC Systems

BIOPAC Systems MP41 Hardware guide

Air Monitor OAM II Installation and operation manual

Air Monitor

Air Monitor OAM II Installation and operation manual

pico Technology TA061 user guide

pico Technology

pico Technology TA061 user guide

BART LAB-DFP operating manual

BART

BART LAB-DFP operating manual

Graytechnos photom MINI 364 instruction manual

Graytechnos

Graytechnos photom MINI 364 instruction manual

R3 ECHORING R3HM1000 user manual

R3

R3 ECHORING R3HM1000 user manual

Bosch DLE 50 Professional operating instructions

Bosch

Bosch DLE 50 Professional operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.