3 INITIAL SYSTEM COMMUNICATIONSETUP
Once the LP3000 controller and leak-detection cable are installed and tested, configure communication
with the web UI.
3.1 Configuring Communication totheWebInterface
NOTE: Consult your IT administrator before configuring communication. If you intend to change the IP
Address or Subnet Mask, obtain appropriate addresses from your IT department.
The default addresses for the LP3000 controller are:
•Default IP address: 169.254.24.7
•Default subnet mask: 255.255.0.0
If the address has been changed, use the following steps to get the IP address for the web interface.
Verify the IP address in use:
1. On the front of the LP3000 panel, press and hold the Test/Reset button.
After 5 seconds, the versions and IP address scroll across the display.
2. Keep holding the display until you note the IP address of the LP3000 controller.
When you release the button, the display resumes normal operation.
Connect the computer:
1. On the computer to use for configuration, make sure that WiFi is off and that DHCP is enabled.
2. Using the included cross-over cable, connect to the Ethernet port on the controller.
It may take a minute or two for the computer to connect with the LP3000 controller.
3. Open a Web browser and enter the default IP address, 169.254.24.7, in the address bar.
The Authentication Required dialog opens.
•If the authentication dialog does not appear, temporarily change the computer’s IP
address to the following: IP address 169.254.24.10, subnet mask 255.255.0.0 then re-enter
the default IP address in theweb browser.
4. Enter the default read/write user name and password:
•Default user name: Liebert (case sensitive)
•Default password: Liebert (case sensitive)
The Web UI opens to the home page.
5. On the home page, select Configuration >Network Settings.
Network Settings opens.
6. Enter the values provided by the IT administrator in IP Address, Net Mask (subnet mask), and
Def Route (default gateway), and click Submit Changes.
7. Connect LP3000 to the network with an Ethernet cable.
NOTE: The cross-over cable is not intended to be connected to a network hub, and will not work if it is
connected to a hub.
8. Verify that the change is successful, open a web browser and enter the new IP address entered
for the LP3000 controller, then enter the default user name and password (from Step Enter the
default read/write user name and password: on page 19).
The home page opens.
Vertiv | Liqui-tect LP3000 Installer/User Guide | 19