Vertiv Liebert MBX Busway Installation and maintenance instructions

Liebert® MBX Busway System
Optional Busway System Monitoring
Installer/User Guide

Vertiv™ | Liebert® MBX Monitoring Installer/User Guide
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent
section of this manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.Vertiv.com/en-us/support/ for additional assistance.
The information contained in this document is subject to change
without notice and may not be suitable for all applications. While
every precaution has been taken to ensure the accuracy and
completeness of this document, Vertiv™ assumes no responsibility
and disclaims all liability for damages resulting from use of this
information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods,
tools, and materials to be used in performing procedures not
specifically described in this document.
The products covered by this instruction manual are manufactured
and/or sold by Vertiv. This document is the property of Vertiv and
contains confidential and proprietary information owned by Vertiv.
Any copying, use or disclosure of it without the written permission
of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered
trademarks of the respective companies. Any questions regarding
usage of trademark names should be directed to the original
manufacturer.

Vertiv™ | Liebert® MBX Monitoring Installer/User Guide
ii
This page intentionally left blank

1 INSTALLATION
Vertiv™ offers optional monitoring packages for the Liebert® MBX Busway System End Feed Box and Tap-
Off Box using Socomec DIRIS Digiware.
• End Feed Box Only Package: Includes DIRIS Digiware G-30, I-45 and U-30
• End Feed Box and Tap-Off Box Package: Includes DIRIS Digiware G-30, I-45, U-30, I-30 and C-31
interface module.
1.1 End Feed Box Monitoring Setup
NOTE: Before beginning to test or program any Digiware components in the Tap-Off Box, ensure that
your G-30 and U-30 Modules are configured.
For the G-30 Module ensure:
•All settings are set to default unless otherwise required by the client.
•Set the address to 1.
For the U-30 Module ensure:
•All settings are set to default unless otherwise required by the client.
•Set the address to 2.
NOTE: The addresses for the G-30 Module and the U-30 Module must not conflict.
NOTE: The G-30 must be programmed first, followed by the U-30, then any I-modules. The U-30
Module governs all I-modules’ baud rate and parity. Always check when testing I-modules that the
baud rate programmed into the U-30 carried over to the I-module.
1.2 End Feed Box Ethernet Configuration
1. Power ON the
End Feed Box
.
2. Connect the
G-30 Module
to your laptop using a standard straight through CAT5 ethernet cable.
3. Browse to
www.Socomec.us,
download and install the latest Easy Config software.
4. Click the
Change Profile Button
in the upper right corner of Easy Config.
5. Log in to the
Super User
profile using password "sOcOmec".
6. Click
Add
a Device.
7. Enter a Name for the End Feed Box.
8. Select
DIRIS G-30/G-40/G-50/G60
from the Type drop down menu.
9. Enter the IP address. The default address is
192.168.0.2.
10. Click
Save
.
11. Click
Connect To Device
.
12. Check the following settings:
a. Verify that the latest firmware is installed on the device. You can check the latest firmware
version on the "Socomec" website. If firmware needs updated, see Firmware Update on page 9 for
instructions.
b. Set the IP address and set the address (Slave ID) to 1.
1 Installation 1

c. Set the Baud rate, Stop bits and Parity. The default settings are 38400/1/N. On the U-30
Modules, click the
Network Tab
. Confirm the power system settings are correct for the customer
site:
•Network Type
•Nominal Voltage
•Frequency
•Phase Rotation
NOTE: Record the serial number of each G-30 Module for future reference.
13. G-30 Only: Click the
Device Detection Tab
.
14. G-30 Only: Click the
New Discovery Button
and wait till discovery is complete, approximately 3
minutes.
15. After checking all the settings, click
Final Action
, then click
Send to Device
.
16. Select the
G-30
or
U-30 Module
being programmed, then click
Connect to Device
.
17. Click
Select All
, then click
OK.
18. Wait for the configuration to be sent to the device. When the successful operation message pops up,
click
OK
.
19. Return to the home screen in Easy Config. Click
Get From Device
.
20. Select the
U-30 Module
and Repeat Step 11 through Step 17, changing the address (Slave ID) to 2
for the U-30 Device.
1.3 End Feed Box USB Configuration
NOTE: Micro-USB cable must be a data and power cable. Power-only cables will not function.
To configure the End Feed Box monitoring device:
1. Power On the End Feed Box and ensure that the G-30 and U-30 Modules are On.
2. Connect the G-30 Module to your laptop using USB – micro USB lead.
3. Browse to
www.Socomec.us,
download and install the latest Easy Config software.
4. Click the
Change Profile
Button in the upper right corner of Easy Config.
5. Log in to the Super User profile using password "sOcOmec".
6. Open the
Easy Config
software and select
Get Configuration from Device.
7. Click the device to configure, then click
Connect to Device
. If no device is visible, verify that the G-30
Module is powered On and that the USB – Micro USB lead is connected correctly.
8. Check these settings:
a. Verify that the latest firmware is installed on the device. You can check the latest firmware
version on the "Socomec" website. If firmware needs updated, see Firmware Update on page 9 for
instructions.
b. Set the IP address and set the address (Slave ID) to 1.
c. Set the baud rate, stop bits and parity. The default settings are 38400/1/N. On U-30 Modules,
click the
Network Tab
. Confirm the power system settings are correct for the customer
site:
Vertiv™ | Liebert® MBX Monitoring Installer/User Guide
2

•Network Type
•Nominal Voltage
•Frequency
•Phase Rotation
NOTE: Record the serial number of each G30 Module for future reference.
9. G-30 Only: Click the
Device Detection Tab
.
10. G-30 Only: Click the
New Discovery Button
and wait till the discovery is complete, approximately 3
minutes.
11. After checking all settings, click
Final Action
, then click
Send to Device
.
12. Select the G-30 or U-30 Module being programmed, then click
Connect to Devic
e.
13. Click
Select All
, then click
OK
.
14. Wait for the configuration to be sent to the device. When the successful operation message pops up,
click
OK
.
15. Remove the micro USB from the G-30 Module and insert it into the U-30 Module to configure the U-
30 Module.
16. Repeat Step 6 through Step 14, changing the address (Slave ID) to 2for the U-30 Device.
NOTE: Record the serial number of each U-30 Module for future reference. The C-31 interface module
provides RS-485 Modbus and Digiware Bus communication support to an external network.
Figure 3.1 Optional Ethernet Connection
1 Installation 3

Vertiv™ | Liebert® MBX Monitoring Installer/User Guide
4
This page intentionally left blank

2 TAP-OFF BOX MONITORING
If your Tap-Off Box is equipped with a monitoring option, there will be two RJ-45 jacks on the side of the
enclosure. The Tap-Off Box RJ-45 connections must be daisy-chained from Tap-Off Box to Tap-Off Box
with the final connection made at the End Feed Box that houses the gateway device. The last Tap-Off Box
in the daisy-chain must have a "Socomec" termination plug installed in the final RJ-45 jack.
NOTE: You can daisy-chain a maximum of 26 Tap-Off Boxes to the network gateway device, located in
the End Feed Box. If you need to daisy chain more than 26, a repeater Tap-Off Box is required. Consult
your sales representative for information on repeater Tap-Off Boxes.
NOTE: Before beginning to test or program any Digiware components in the Tap-Off Boxes, ensure
that your G-30 Module and U-30 Module are configured. The U-30 Module governs the baud rate and
parity for all I-modules. Alwayas check when testing I-modules that the baud rate programmed into the
U-30 carried over to the I-module.
To configure Tap-Off Boxes:
1. Power On the I-30 or I-60 using a Socomec RJ-45 cable, which is looped out from the U-30 Module. A
green light appears on the I-30 or I-60 Module to indicate it is powered On.
2. Connect the I-module to your laptop via USB – micro USB lead.
3. Click the
change profile button
in the upper right corner of Easy Config.
4. Log in to the Super User profile using password "sOcOmec".
5. Click
Get from Device.
6. Click the
Device
to configure, then click
Connect to Device
.
7. Select the
Product
Tab and verify the following information:
• Identification – I-30 OR I-60 Serial Number
• Type – Device Connected
• Firmware Version – Latest firmware installed. You can check the latest firmware version on the
"Socomec" website. If firmware needs updated, see Firmware Update on page 9 for instructions.
•The ‘Communication Configuration’ shown is :
• Type – RS485.
• Address – Set a unique Modbus address. The G-30 is 1, U-30 is 2, I-45 (if present) is 5.
Continue numbering I-modules starting at 10.
• Baud Rate – Confirm match to U-30 settings.
• Stop Bits – Confirm match to U-30 settings.
• Parity – Confirm match to U-30 settings.
8. Select
Load
and confirm the following information:
• Load Enabled – If CTs are connected, option to change settings.
• Load Type – Select number of phases and amount of CTs.
• Nominal Current – circuit rating associated with each CT.
• CT Direction – If the CTs are reading an incoming or outgoing supply.
9. After the settings are updated, click
Final Action,
then click
Send to Device
.
2 Tap-Off Box Monitoring 5

10. Select the
I-module
being programmed, then click
Connect to Device
.
11. Click Select All, then click
OK
.
12. Wait for the configuration to be sent to the device. When the successful operation message pops up,
click
OK
.
NOTE: After completing all the I-module configurations or after adding new Tap-Off Box Modules to a
busway run, you must log into the G-30 module and re-perform device discovery.
1. Connect to the G-30 via Ethernet or USB.
2. Click
Device Detection
Tab.
3. Click
New Discovery
. All newly configured I-modules should appear.
4. Click
Final Action
.
5. Click
Send to Device
.
6. Select the G-30 Module and click
Connect To Device
.
7. Click Select All then Click
Ok
.
8. Wait for the configuration to be sent. Click
Ok
.
Vertiv™ | Liebert® MBX Monitoring Installer/User Guide
6

3 WEB PORTAL CONFIGURATION
After completing all the I-module configurations or after adding a new Tap-Off Box Module to a busway
run, you must log in into the Socomec web portal and update the configuration.
1. Click the
Change Profile
Button in the upper right corner.
2. Select
Admin
and enter password
Admin
.
3. Click the
Settings Gear
Icon on the top left.
4. Click
Devices.
5. Click
Read Configuration.
6. Confirm all modules appear.
7. Click
Save Configuration
.
3 Web Portal Configuration 7

Vertiv™ | Liebert® MBX Monitoring Installer/User Guide
8
This page intentionally left blank

4 FIRMWARE UPDATE
If the firmware for each device is not the latest available on the Socomec website, download the firmware
ZIP file for the module(s) to be updated. Firmware versions may be checked on the Socomec website:
https://www.socomec.com/product-upgrade-tool-software_en.html
.
To update a Socomec Digiware module firmware, perform the following steps:
1. Download the latest version of Socomec’s Product Upgrade Tool and firmware version from the page
above.
2. Install the Product Upgrade Tool on your laptop.
3. Connect the module to your laptop via USB – micro USB lead.
4. Open the Product Upgrade Tool program.
5. Verify the module to be upgraded is displayed in the Master field.
6. Click the
Browse
button and select the firmware ZIP file for the module.
7. Click
Update
and wait for the firmware upgrade to complete.
8. Configure the module per the instructions in section 1 or 2.
Figure 6.1 Product Upgrade Tool
4 Firmware Update 9

Vertiv™ | Liebert® MBX Monitoring Installer/User Guide
10
This page intentionally left blank

Vertiv™ | Liebert® MBX Monitoring Installer/User Guide

Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2020 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names
and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure
accuracy and completeness herein, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information
or for any errors or omissions. Specifications are subject to change without notice..
SL-70526_REV02_05-20
Table of contents
Other Vertiv Measuring Instrument manuals

Vertiv
Vertiv Alber Universal Xplorer Industrial Battery... Use and care manual

Vertiv
Vertiv Liqui-tect LP3000 Installation and maintenance instructions

Vertiv
Vertiv MPX IMS User manual

Vertiv
Vertiv Alber ELS User manual

Vertiv
Vertiv NetSure SM-IO2 User manual

Vertiv
Vertiv Alber UXIMe User manual

Vertiv
Vertiv NetSure M832DNA User manual

Vertiv
Vertiv Liebert RDU-A-G2 User manual

Vertiv
Vertiv Knurr DIS User manual

Vertiv
Vertiv GEIST WSCK User manual