  9. Viconics VWG-40 Manual

Viconics VWG-40 Manual

This manual suits for next models

3

Other Viconics Gateway manuals

Viconics VWG-50-5000 Manual

Viconics

Viconics VWG-50-5000 Manual

Viconics GW2 User manual

Viconics

Viconics GW2 User manual

Viconics GW2 User manual

Viconics

Viconics GW2 User manual

Popular Gateway manuals by other brands

Telecom FM onestream gfx Programming guide

Telecom FM

Telecom FM onestream gfx Programming guide

UfiSpace LoRa GPE810U Quick setup guide

UfiSpace

UfiSpace LoRa GPE810U Quick setup guide

Merak MMk-736F Quick setup guide

Merak

Merak MMk-736F Quick setup guide

Robustel R3010 user guide

Robustel

Robustel R3010 user guide

turck BL20-PG-EN-V3 user manual

turck

turck BL20-PG-EN-V3 user manual

IBM Security Web Gateway Appliance quick start guide

IBM

IBM Security Web Gateway Appliance quick start guide

SSS Siedle Smart Gateway Commissioning instructions

SSS Siedle

SSS Siedle Smart Gateway Commissioning instructions

ADTRAN 424RG Installation

ADTRAN

ADTRAN 424RG Installation

Chorus Hyperfibre XGS-250WX-A user guide

Chorus

Chorus Hyperfibre XGS-250WX-A user guide

Dragino G308 user manual

Dragino

Dragino G308 user manual

Data Domain DD690g Installation and setup guide

Data Domain

Data Domain DD690g Installation and setup guide

Raritan Laptop Release notes

Raritan

Raritan Laptop Release notes

Haivision Torpedo quick start guide

Haivision

Haivision Torpedo quick start guide

ATCOM AG-268 user manual

ATCOM

ATCOM AG-268 user manual

LST M500RFE-AS Specification sheet

LST

LST M500RFE-AS Specification sheet

Vega VEGA BS-3 user manual

Vega

Vega VEGA BS-3 user manual

Kinnex Media Gateway quick start guide

Kinnex

Kinnex Media Gateway quick start guide

2N Telekomunikace 2N StarGate user manual

2N Telekomunikace

2N Telekomunikace 2N StarGate user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

1
VWG-40
Viconics Wireless Gateway
Hardware Installation Guide
(Issue Date September 24, 2008 – 028-0179 R8)
Product overview
The VWG-40 and related wireless thermostats are targeted to retrofit applications where the
addition of communicating field bus wiring within the building space is prohibitive. The
Gateway and Communicating Thermostats with wireless field bus encourages the use of
existing wiring utilized by existing electronic thermostat type controls.
The VWG-40 when utilized in conjunction with the VT7xxxXxxxxW series wireless thermostats will offer the integrator
simple BACnet IP or BACnet MS/TP objects to integrate over standard building automation systems using familiar
integration toolsets.
A maximum of 30 wireless thermostats can be wirelessly attached to a single VWG
The following additional documentation is available on www.viconics.com
• Gateway BACnet integration guide (VWG-40-IP & VWG-40-MSTP), is available in document ITG-VWG-40-BAC-Exx
• Information on design consideration of wireless mesh networks and VWG set-up / diagnostics is available in document LIT-
VWG-40-SETUP-Exx
Part available
Part number Description
VWG-40-IP-1000 Viconics BACnet over IP wireless gateway. Includes:
- Supports up to 30 wireless thermostats
- Factory mounted wireless adapter
- 24 Vac panel mounted power supply
- Gateway mounted antenna
VWG-40-MSTP-1000 Viconics BACnet RS485 MS-TP wireless gateway. Includes:
- Supports up to 30 wireless thermostats
- Factory mounted wireless adapter
- 24 Vac panel mounted power supply
- Gateway mounted antenna
VWG-40-LON-1000
(Upcoming) Viconics LON wireless gateway. Includes:
- Supports up to 30 wireless thermostats
- Factory mounted wireless adapter
- 24 Vac panel mounted power supply
- Gateway mounted antenna
VWG-APP Interface software for VWG configuration and set-up. Operates under Windows XP ™.
Uses a LAN crossover IP connection for initial set-up.
VWG-RA Remote antenna for gateway when the gateway is installed inside a metal cabinet or
when remote antennal mounting is required by physical installation
VWG-WA Replacement antenna for gateway mounted antenna setup
VWG-PS-DC 24 Vac to 15 Vdc panel mounted power supply for VWG
VWG-PS-AC 120 Vac to 15 Vdc power supply for VWG with cord
VWG-BB Replacement battery backup pack for the VWG
Trademarks
Niagara, Niagara AX is a registered trademark of Tridium, Inc.
LON, LonWorks and LonTalk are registered trademarks of Echelon Corporation
BACnet is a registered trademark of ASHRAE
2
Disclaimers
NO WARRANTY. Viconics, Inc. ( herein after referred to as “Viconics” ) makes no warranty as to the accuracy of or
use of this technical documentation. Any use of the technical documentation or the information contained therein is
solely at the risk of the user.
Documentation may include technical or other inaccuracies or typographical errors. Viconics reserves the right to make
changes to this document without prior notice, and the reader should in all cases consult Viconics to determine
whether any such changes have been made. The information in this publication does not represent a commitment on
the part of Viconics.
Viconics shall not be liable for incidental or consequential damages resulting from the furnishing, performance, or use
of this material.
This guide contains links and references to third-party websites that are not under the control of Viconics, and Viconics
is not responsible for the content of any reference material or linked websites. If you access a third party website
mentioned in this guide, then you do so at your own risk. Viconics provides these links only as a convenience, and the
inclusion of the link does not imply that Viconics endorses or accepts any responsibility for the content on those third-
party sites.
Electronic controls are static sensitive devices. Discharge yourself properly before manipulation and installing the
Viconics wireless gateway.
All Viconics wireless gateways and related wireless thermostats are to be used only as operating controls. Whenever a
control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user to add
safety devices and/or alarm system to protect against such catastrophic failures.
All VT7000 series wireless thermostats and associated VWG (Viconics Wireless Gateway) have been rigorously tested
to ensure reliable operation in most building applications using the latest 2.4 ZigBee technologies. Viconics cannot
guarantee against potential network interference should additional wireless systems be deployed sharing close
proximity.
Best practices covered in this manual and all related Viconics VWG documents should be considered as a guide to
apply Viconics Wireless Network devices only. The instructions included in this manual are based upon Viconics in
house testing and should be referred to as a guide only.
Viconics Inc. may not be held liable for continued reliable, or robust operation of any and all wireless based devices.
Although Viconics has taken many precautions in assuring the robustness of the VT7000 series wireless thermostat
product line and associated network access point (VWG-40-XXXX-1000) Please note; future application of additional
wireless devices utilizing the same or similar channels and / or frequencies may degrade performance of overall
system and / or reliability.
Non-approved modifications or changes made to the VWG or wireless thermostats may void the FCC compliance of
the VWG and wireless thermostats.
Ferrites supplied with the power supply and VWG MUST be installed according to instructions. Failure to do so may
void the FCC compliance of the VWG and wireless thermostats.
Only VWG-PS-DC and VWG-PS-AC power supply can be used with the VWG. The usage of another non-approved
power supply may void the FCC compliance of the VWG and wireless thermostats.
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING
TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE
MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED
OPERATION.
3
Overview
This document covers the mounting and wiring of the Viconics VWG-40 series product. It assumes that you are an
engineer, technician, or service person who is performing control system installation. Instructions in this document
apply to the following products:
Models Description
VWG-40-IP-1000 Viconics BACnet over IP wireless gateway.
VWG-40-MSTP-1000 Viconics BACnet RS485 MS-TP wireless gateway.
VWG-40-LON-1000 Viconics LON wireless gateway. (Upcoming)
• Note Not covered in this document is the configuration appliance software required for fully setup the
gateway. This includes setting host IP address, passwords, database, and other thermostat and network utilities.
Refer to the document LIT-VWG-40-SETUP-Exx for more information.
Table of contents
These are the main topics included in this document:
• Preparation
• Precautions
• Mounting
• Board Layout
• About Expansion Options
• Wiring Details
• Power Up and Initial Checkout
Also included in this document are several appendixes, as follows:
• Using Status LEDs
• Maintaining the VWG
• Replacement and accessory
• Certifications
• Declaration of Conformity
Information and specifications published here are current as of the date of publication of this document. Viconics, Inc.
reserves the right to change or modify specifications without prior notice. One or more U.S. or foreign patents may
cover products or features contained herein.
Preparation
Unpack the VWG and power module (either VWG-PS-DC or VWG-PS-AC) and inspect the contents of the packages for
damaged or missing components. Be sure the factory-installed ferrite is on the cord of the power supply unit. If damaged,
notify the appropriate carrier at once and return any damaged components for immediate repair or replacement.
Included in this Package
Included in this package you should find the following items:
• VWG-40-XX-1000 base controller.
• Local antenna for the VWG
• This VWG-40-XX-1000 Hardware installation guide
• Configuration tool on a mini-CD
• Power module required for operation, are ordered and sold separately. The power module can be one of the
following:
– VWG-PS-DC: 24Vac in-line (DIN-mount capable), or
– VWG-PS-AC: External 120 Vac wall-mount power adapter
4
Material and Tools Required
The following tools and supplies may be required for installation:
• DIN rail, type NS35/7.5 (35mm x 7.5mm), recommended for panel mount installation. Length of DIN rail should be
minimum 6.5 “ ( 165 mm ).
• If using an VWG-PS-DC power supply, use UL listed, Class 2, 24Vac transformer, supplying a minimum of 5VA to
the VWG. Note that the VWG-PS-DC power supply provides isolation — a dedicated transformer is not required.
• Suitable screws and screwdriver for mounting DIN rail, or if DIN rail not used, for mounting bases of VWG
controller and VWG-PS-DC power supply (if used).
Precautions
This document uses the following warning and caution conventions:
Cautions remind the reader to be careful. They alert readers to situations where there is a chance that the reader might
perform an action that cannot be undone, might receive unexpected results, or might lose data. Cautions contain an
explanation of why the action is potentially problematic.
Warnings alert the reader to proceed with extreme care. They alert readers to situations where there is a chance that the
reader might do something that can result in personal injury or equipment damage. Warnings contain an explanation o
f
why the action is potentially dangerous.
Safety Precautions
The following items are warnings of a general nature relating to the installation and start-up of the VWG
controller. Be sure to heed these warnings to prevent personal injury or equipment damage.
• Depending on power module used, the circuit powering the VWG is 24Vac at 50/60 Hz (if using the VWG-PS-DC power
supply or 120 Vac at 50/60 Hz (if using the VWG-PS-AC power supply). Disconnect power before installation or servicing to
prevent electrical shock or equipment damage.
• Make all connections in accordance with national and local electrical codes. Use copper conductors only.
• To reduce the risk of fire or electrical shock, install in a controlled environment relatively free of contaminants.
• This device is only intended for use as a monitoring and control device. To prevent data loss or equipment damage, do
not use it for any other purpose.
• All Viconics wireless gateways and related wireless thermostats are to be used only as operating controls. Whenever a control
failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user to add safety devices
and/or alarm system to protect against such catastrophic failures.
Static Discharge Precautions
Static charges produce voltages high enough to damage electronic components. The microprocessors and
associated circuitry within a VWG controller are sensitive to static discharge. Follow these precautions when
installing, servicing, or operating the system:
• Work in a static-free area.
• Discharge any static electricity you may have accumulated. Discharge static electricity by touching a known,
securely grounded object.
• Do not handle the printed circuit board (PCB) without proper protection against static discharge. Use a wrist strap when
handling PCBs. The wrist strap clamp must be secured to earth ground.
5
Mounting
Mount the VWG in a location that allows clearance for wiring, servicing, and antenna removal.
Environmental Requirements
Note the following requirements for the VWG mounting location:
• This product is intended for indoor use only. Do not expose the unit to ambient conditions outside of the range of
0ºC (32ºF) to 50ºC (122ºF) and relative humidity outside the range 5% to 95% non-condensing (pollution degree 1).
• If mounting inside an enclosure, that enclosure should be designed to keep the unit within its required operating
range considering a 20-watt dissipation by the controller. This is especially important if the controller is mounted
inside an enclosure with other heat producing equipment.
• Do not mount the unit:
– In an area where excessive moisture, corrosive fumes, or explosive vapors are present.
– Where vibration or shock is likely to occur.
– In a location subject to electrical noise. This includes the proximity of large electrical contractors,
electrical machinery, welding equipment, and spark igniters.
Physical Mounting
The following information applies about physically mounting the unit.
• You can mount the VWG in any orientation. It is not necessary to remove the cover before mounting.
• Mounting on a 35mm wide DIN rail is recommended. The VWG unit base has a molded DIN rail slot and locking
clip, as does the VWG-PS-DS 24Vac power supply module.
• If DIN rail mounting is impractical, you can use screws in mounting tabs on the VWG
The following procedure provides step-by-step DIN rail mounting instructions for the VWG. Mount the VWG prior to
mounting any accessory items.
Procedure 1 - To mount on DIN rail
Step 1 Securely install the DIN rail using at least two screws, near both ends of the rail.
Step 2 Position the VWG on the rail, tilting to hook DIN rail tabs over one edge of the DIN rail
Step 3 Pull out the DIN rail clip and push down and in to force the DIN rail clip to snap over the other edge of the DIN
rail.
Step 4 To prevent the VWG from sliding on the DIN rail, secure with clips provided by the DIN rail vendor, or place a
screw in one of the four mounting tabs in the base of the VWG.
Step 5 If VWG-PS-DC 24 Vac power supply is used, mount onto the DIN rail in the same manner.
6
Removing and Replacing the Cover
You must remove the VWG cover to connect the battery (new unit) or to replace the battery. The cover snaps onto the
base with four plastic tabs (two on each end).
To remove the cover, press in the four tabs on both ends of the unit, and lift the cover off. If accessory modules are
plugged into the VWG, you may need to slide them away from the unit to get to the cover tabs. To replace the cover,
orient it so the cutout area for communication ports is correct, then push inwards to snap in place.
Installation Minimum Spacing Distance Requirements
Make sure minimum spacing distance requirements is available to freely rotate wireless antenna in all possible
orientations.
7
Board Layout
Figure below shows the location of LEDs, connections and other features of the VWG with the cover removed.
Wiring Details
See figure above to locate connectors and other components on the VWG controller. Make
connections to the VWG in the following order.
1. Connect earth-grounding wire with spade connector from the earth ground lug on the VWG. See “Grounding” for
details.
2. Prepare power wiring (leave the unit powered off). See “Power Wiring” for details.
3. Connect communications wiring. See “Communications Wiring,” page 14 for ports available on the VWG base unit.
For ports on any installed option board (LON, RS-485, modem) see the specific mounting and wiring guide for any
additional details.
4. Connect the backup battery to the VWG battery connector, and apply power to the unit. See “Power Up and Initial
Checkout,” page 17.
Grounding
Use an earth ground spade lug (0.187") on the base of the VWG for connection to earth ground. For maximum
protection from electrostatic discharge or other forms of EMI, you should connect this to earth ground using a #16 AWG
or larger wire. Keep this wire as short as possible.
If desired, you can use the wall mount VWG-PS-AC 120 Vac power supply in your office ( when initially commissioning
the VWG ), and then install the panel mount 24 Vac VWG-PS-DC power supply at the job. The following sections provide
more details:
• VWG-PS-AC ( 120 Vac Wall mounted power supply module )
• VWG-PS-DC ( Panel mount 24Vac-power supply module )
Battery
connecto
r
Ethernet IP connection
RJ-45
,
Net1
MS-TP RS-485
connection, COM2
Coaxial power
connector for wall
mounted
p
ower module
Earth ground spade
lug connector
VWG wireless card
reset button
VWG wireless card
Com status LED
Net1
status
LED
Net2
status
LED
BEAT
status
LED
SYS
status
LED
Antenna
connector
Ethernet IP connection
RJ-45
,
Net2
Location of serial numbe
r
8
VWG-PS-AC 120 Vac Wall mounted power supply module
Both the U.S. and International models of wall power modules are self-contained switching power supplies designed to
plug into a standard building power receptacle of appropriate voltage. To supply power to the VWG, you then simply plug
the coaxial connector from the VWG-PS-AC into the coaxial power connector on the VWG base board.
VWG-PS-DC Panel mount 24Vac-power supply module
Using the VWG-PS-DC module lets you power the VWG from a standard Class 2 24Vac transformer. The VWG-PS-
DC module provides power isolation (it makes no difference if the transformer output is “floating” or has one side tied to
ground). Therefore, you can use an existing nearby transformer, providing that it has 5 VA capacity available to power
the VWG.
Power Wiring
Only VWG-PS-DC and VWG-PS-AC power supply with factory installed ferrite
on the power cord can be used with the VWG. The usage of another non-
approved power supply may void the FCC compliance of the VWG and wireless
thermostats.
Connect power cord as showed into coaxialconnector.
Do not plug the coaxial connector from the power supply into the
VWG until all other mounting and wiring is completed. See “Power
Up and Initial Checkout,” section.
Communications Wiring
Connect communications wiring to the VWG using either Net1, Net2 or the RS-485 connection based on VWG model
used and configuration.
Note Prior to connecting cables, provide strain relief for them to prevent damage to the controller.
Ethernet—BACnet over IP wiring
Two, female 10/100-Mbit Ethernet connections are provided on the VWG. These are RJ-45 connectors labeled NET2 and
NET1. Use a standard Ethernet patch cable for connecting to a hub or Ethernet switch. An activity LED for each Ethernet
port is visible and labeled “NET2” and “NET 1” on the cover.
Note Typically, you only use NET1 (primary port), unless you have a specific application for isolating a driver’s
network traffic to a separate IP address (and LAN) using NET2. In all cases, port selection can be changed
and is dependent of configuration made using the VWG configuration tool.
The packing slip accompanying the VWG will provide the “factory-shipped” IP settings for both NET1 and NET2. Refer
to the document LIT-VWG-40-SETUP-Exx for more information for details on the default IP address and how to
change it. ( VWG-40-IP only )
The supplied ferrite in the VWG packaging needs to be installed on the IP wire in a specific way for FCC
compliance. Place IP wire into the provided ferrite as shown in diagram below. Make sure to follow the placement
dimension. Close and snap the ferrite casing as shown.
Wire IP cable into NET1 or NET2 as per configuration.
9
RS485—BACnet MS-TP wiring.
An RS485, optically isolated port uses a 3-position, screw terminal connector and always operates as COM2. Wire to
this connector with shielded 8-22 AWG wiring (refer to the TIA/EIA-485 standard). The screw terminals (from left-to-
right) are shield, plus (+), and minus (–).( VWG-40-MSTP only )
The supplied ferrite in the VWG packaging needs to be installed on the MS-TP wire in a specific way for FCC
compliance. Place MS-TP wire into the provided ferrite as shown in diagram below. Make sure to follow the
placement dimension. Close and snap the ferrite casing as shown.
Wire MS-TP cable into MS-TP RS-485 connector.
Antenna installation
Controller mounted antenna ( VWG-WA )
All VWG-40 are supplied with a controller-mounted antenna. The antenna is shipped loose in the
controller main packaging box.
This installation type is to be used only when the controller ( and antenna ) is not installed inside
a closed metal enclosure and that clear reception is expected.
Gently screw the antenna into the antenna connector at the top of the VWG. Do not over tight the
antenna.
Remote mounted antenna ( VWG-RA )
If a remote mounted antenna is required because of the location of the VWG, a separate antenna
can be ordered. Part number VWG-RA
This installation type can typically be used when the controller is installed inside a closed metal
enclosure.
Gently screw the female connection of the remote antenna into the VWG. Remote antenna has a
weighted magnetic base for metal surface mounting. Wire length is 1.5 M ( 4.9 Ft )
Power Up and Initial Checkout
Procedure - Initial power up and checkout
1. Connect the Backup Battery.
2. Apply Power.
3. Check the Status LEDs.
1) Connect the Backup Battery
With the cover removed from the VWG (see “Removing and Replacing the Cover,”), locate the red and black wires
coming from the backup battery, with 2-position connector plug. Plug the connector into the battery connector on the
bottom board (below option slot 2 area). The connector is keyed—you cannot insert it incorrectly. The red (positive)
connection should be the furthest from the two 30-pin option modules connectors.
For more details on the backup battery, see “About the Battery”.
10
2) Apply Power
Apply power to the VWG by plugging in the power plug into either the VWG (if wall mount AC adapter VWG-PS-
AC) or the 24Vac-powered VWG-PS-DC module.
3) Check the Status LEDs
When power is applied, the green LED labeled “SYS” will light. This is a green LED. Once the VWG boots, the yellow
“BEAT” (heartbeat) LED will begin blinking, with a typical rate of about 1 Hz. Boot time should begin within 30 seconds
after power is applied.
The blink pattern of the heartbeat LED under normal operation will differ for each installation (depending on station
activity). But, in general, the LED should blink about once per second. The rate will be slower when the control engine is
executing the station database, and as more objects / wireless thermostats are added.
After applying power, if the heartbeat LED comes on (steady) and stays lit longer than two minutes, contact technical
support for assistance. See also the “Using Status LEDs” section.
About the Battery
The VWG is provided with a custom 10-cell NiMH battery pack mounted to the unit (under the cover). This battery
allows the VWG to continue operation through very short power bumps (a few seconds in duration). If a longer power
outage occurs, the battery provides enough run time for the VWG to backup data and then shutdown. Typically, this is
one minute. Shutdown occurs automatically, after data is backed up to on-board flash memory.
The battery is trickle-charged by the VWG during normal operation. Following an extended power outage, the battery is
charged at a faster rate. The power and battery circuitry is monitored by the VWG. The battery should be replaced
approximately every three years, or more often if the unit is in a high temperature environment.
Note A NiMH battery characteristic is to lose charge if not left in charge mode (trickle charge). Leaving the battery
unconnected, or in the unit powered off will cause the battery to fully discharge in a matter of weeks. Note that
in the case of a new VWG, it ships from the factory with a completely discharged battery. Therefore, allow at
least 18 hours for the battery to charge if it has not been in a powered unit.
For more information on the use and replacement of the battery, refer to the “Required Battery Maintenance” section.
Related Documentation
For more information on configuring and using the VWG controller, consult the following documents available from the
VWG section at www.viconics.com:
• Gateway BACnet integration guide (VWG-40-BIP & VWG-40-MSTP), is available in document ITG-VWG-40-BAC-Exx
• Information on design consideration of wireless mesh networks and VWG set-up / diagnostics is available in document LIT-
VWG-40-SETUP-Exx