manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Viking
  6. •
  7. Irrigation System
  8. •
  9. Viking VK3502 Instruction manual

Viking VK3502 Instruction manual

This manual suits for next models

1

Other Viking Irrigation System manuals

Viking VK1001 SR Upright Sprinkler K5.6 Instruction Manual

Viking

Viking VK1001 SR Upright Sprinkler K5.6 Instruction Manual

Viking VK1001 Instruction manual

Viking

Viking VK1001 Instruction manual

Viking VK3541 Instruction manual

Viking

Viking VK3541 Instruction manual

Viking VK638-D Instruction manual

Viking

Viking VK638-D Instruction manual

Viking MicrofastHP VK340 Instruction manual

Viking

Viking MicrofastHP VK340 Instruction manual

Viking MICROFAST VK302 Instruction manual

Viking

Viking MICROFAST VK302 Instruction manual

Viking HORIZON H-3 Instruction manual

Viking

Viking HORIZON H-3 Instruction manual

Viking MICROFAST VK327 User manual

Viking

Viking MICROFAST VK327 User manual

Viking VK482 User manual

Viking

Viking VK482 User manual

Viking MIRAGE VK464 Instruction manual

Viking

Viking MIRAGE VK464 Instruction manual

Viking VK960 Instruction manual

Viking

Viking VK960 Instruction manual

Viking VK2021 Instruction manual

Viking

Viking VK2021 Instruction manual

Viking VK4611 Instruction manual

Viking

Viking VK4611 Instruction manual

Viking HORIZON MIRAGE B-1 Instruction manual

Viking

Viking HORIZON MIRAGE B-1 Instruction manual

Viking VK2002 Instruction manual

Viking

Viking VK2002 Instruction manual

Viking FREEDOM VK480 Instruction manual

Viking

Viking FREEDOM VK480 Instruction manual

Viking MICROFAST VK350 Instruction manual

Viking

Viking MICROFAST VK350 Instruction manual

Viking VK449 Instruction Manual

Viking

Viking VK449 Instruction Manual

Viking V-HIP Instruction manual

Viking

Viking V-HIP Instruction manual

Viking ESFR User manual

Viking

Viking ESFR User manual

Viking VK531 Instruction manual

Viking

Viking VK531 Instruction manual

Viking VK2022 Instruction manual

Viking

Viking VK2022 Instruction manual

Viking 10224 Instruction manual

Viking

Viking 10224 Instruction manual

Viking M Instruction manual

Viking

Viking M Instruction manual

Popular Irrigation System manuals by other brands

Tyco TY-B Series manual

Tyco

Tyco TY-B Series manual

Toro ZSERIES 570Z brochure

Toro

Toro ZSERIES 570Z brochure

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Tyco Fire Product Star Galaxy SGQR instruction manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR instruction manual

Tyco Fire Product CENTRAL A instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL A instruction manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Tyco Fire Product Gem F892 instruction manual

Tyco Fire Product

Tyco Fire Product Gem F892 instruction manual

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

VK3502 QUICK RESPONSE
UPRIGHT SPRINKLER (K8.0)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 1 of 5
Form No. F_111220 Rev 22.1 February 22, 2022 Replaces page F_111220 Rev 21.2
(Added LPCB and VdS details)
1. DESCRIPTION
The Viking VK3502 Quick Response Upright Sprinkler is a small thermosensitive
glass bulb spray sprinkler available with various finishes and temperature ratings
to meet design requirements. The special Polyester and Electroless Nickel PTFE
(ENT) coatings can be used in decorative applications where colors are desired.
In addition, these coatings have been investigated for installation in corrosive
environments and are Listed and Approved as indicated in the Approval Chart.
2. LISTINGS AND APPROVALS
UL Listed: Category VNIV
FM Approved: Classes 2001, 2043
Also approved for use in FM Approved vacuum dry sprinkler
systems with a maximum supervisory vacuum pressure of -3 PSI
(-207 mbar).
CE: Standard EN12259-1, DOP_XT1A
LPCB Approved: reference no. 096m
VdS Approved: Certificate no. G 422009
Not approved for new installations per NFPA 13. Refer to the Approval Chart and Design
Criteria for requirements that must be followed.
3. TECHNICAL DATA
Rated to: 175 PSI (12 bar) water working pressure.
Factory tested hydrostatically to 500 PSI (34.5 bar)
Thread size: 1/2” NPT or 15 mm BSPT
Nominal K-factor: 8.0 U.S. (115 metric*)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
* Metric K-factor measurement shown is in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass CW602N, UNS-C84400 or QM Brass
Deflector: Stainless Steel UNS S30400
Pip Cap Shell - Stainless Steel UNS-S44400
Pip Cap Disc - Stainless Steel UNS-S30100
Belleville Spring - Nickel Alloy
Pip Cap Seal - Polytetrafluoroethylene (PTFE)
Compression Screw: Brass CW612N, CW508L, UNS-C36000 or UNS-C26000
Shipping Cap: Polyethylene
Bulb: Glass, nominal 3 mm diameter
Ordering Information: (Refer to Table 1 and the current Viking List Price Book.)
4. INSTALLATION
Refer to appropriate NFPA, FM Global, and/or any other applicable installation standards. Refer to Figure 3
NOTICE Risk of permanent damage.
Over-tightening the sprinkler can cause permanent damage.
> Tighten the sprinkler to a MAXIMUM torque of 14 ft-lbs (19 N-m).
5. OPERATION
During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat-sensitive liquid in the
glass bulb expands, causing the bulb to shatter, releasing the pip cap assembly. Water flowing through the sprinkler orifice strikes
the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.

VK3502 QUICK RESPONSE
UPRIGHT SPRINKLER (K8.0)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 2 of 5
Form No. F_111220 Rev 22.1 February 22, 2022
7. AVAILABILITY
Viking Sprinklers are available through a network of domestic and international distributors. See the website for the closest distributor
or contact Viking.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
VK3502 QUICK RESPONSE
UPRIGHT SPRINKLER (K8.0)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 3 of 5
Form No. F_111220 Rev 22.1 February 22, 2022
Figure 2: Sprinkler Dimensions
7/16” (11 mm)
Nominal Pipe
Engagement
1-15/16”
(49 mm)
1/2” NPT or
15 mm BSPT
TABLE 1: ORDERING INFORMATION
Instructions: Using the sprinkler base part number,
(1) add the suffix for the desired Finish
(2) add the suffix for the desired Temperature Rating.
Sprinkler
Base Part
Number
Size 1: Finishes 2: Temperature Ratings
NPT
Inch
BSPT
mm
Description Suffix1Nominal Rating Bulb Color Max. Ambient Ceiling
Temperature2Suffix
23873 1/2 -- Brass A 135 °F (57 °C) Orange 100 °F (38 °C) A
23885 -- 15 Chrome F 155 °F (68 °C) Red 100 °F (38 °C) B
White Polyester 3,5 M-/W 175 °F (79 °C) Yellow 150 °F (65 °C) D
Black Polyester 3,5 M-/B 200 °F (93 °C) Green 150 °F (65 °C) E
ENT 3,4,5 JN 286 °F (141 °C) Blue 225 °F (107 °C) G
Open -- -- Z
Example: 23873MB/W = VK3502 with white polyester finish and 155 °F (68 °C) nominal temperature rating. This sprinkler is to be
installed into an area with a maximum ambient temperature of 100 °F (38 °C) meaning if the area will experience temperatures above
the maximum ambient rating, you shall use a higher temperature-rated sprinkler.
Accessories
Sprinkler Wrenches (see Figure 1):
Standard (straight) Wrench: Part number 23559MB.
Sprinkler Cabinet:
A. Up to 6 sprinklers: Part number 01724A (available since 1971).
B. 6-12 sprinklers: Part number 01725A (available since 1971).
Footnotes
1. Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
2. Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
3. UL Listed as corrosion resistant.
4. FM Approved as corrosion resistant.
5. The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.
Figure 1: Sprinkler Wrench
Top View
VK3502 QUICK RESPONSE
UPRIGHT SPRINKLER (K8.0)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 4 of 5
Form No. F_111220 Rev 22.1 February 22, 2022
APPROVAL CHART
Viking Quick Response Upright Sprinkler
VK3502 K8.0 (115 metric)
Sprinkler Base
Part Number1,6
Thread Size Listings and Approvals2
Maximum WWP 175 PSI (12 bar)
NPT BSPT cULus FM
Inch mm Approval Specification Approval Specification
23873 1/2 -- A1 A1
23885 -- 15 A1 A1
Additional Listings and Approvals
Maximum WWP 175 PSI (12 bar)
CE7LPCB8VdS9
23873 1/2 -- B1 A1 A1
23885 -- 15 B1 A1 A1
Approved Temperature Ratings
A= 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C) and 286 °F (141 °C)
B= 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C) and 286 °F (141 °C)
Approved Finishes
1= Brass, Chrome, White Polyester 3,4, Black Polyester 3,4, and ENT 4,5
Footnotes
1. Base Part number is shown. For complete part number, refer to Viking’s current price schedule.
2. This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
3. Other colors are available upon request with the same Listings and Approvals as the standard colors.
4. cULus Listed as corrosion resistant.
5. FM Approved as corrosion resistant.
6. Sprinklers with a K-factor exceeding K5.6 (80.6 metric) with 1/2” NPT (15 mm BSPT) are listed and approved for retrofit only.
7. CE: Standard EN12259-1, Declaration of Performance DOP_XT1A.
8. LPCB Approved; reference no. 096m
9. VdS Approved; Certificate no. G 422009
VK3502 QUICK RESPONSE
UPRIGHT SPRINKLER (K8.0)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Page 5 of 5
Form No. F_111220 Rev 22.1 February 22, 2022
DESIGN CRITERIA - UL
cULus Listing Requirements:
The Viking VK3502 Quick Response Upright Sprinkler is cULus Listed as indicated in Approval Chart for installation in accordance
with the latest edition of NFPA 13 for standard spray sprinklers.
• Designed for use in Light and Ordinary Hazard occupancies.
• The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers shall be followed.
DESIGN CRITERIA - FM
FM Approval Requirements:
The Viking VK3502 Quick Response Upright Sprinkler is FM Approved as quick response Non-Storage upright sprinkler as indicated
in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention
Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to:
minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing,
and deflector distance below the ceiling.
NOTE:The FM Installation guidelines may differ from UL and/or NFPA criteria.
IMPORTANT: Always refer to Form Number F_091699 - Care and Handling of Sprinklers. Also refer to Form Number
F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance
with the latest edition of Viking Technical Data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or
other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever
applicable.
Figure 3: Installation
Frame arms must be
parallel to the pipe.
1
2
1. Carefully slide the wrench onto the
wrench flats.
2. Install the sprinkler into the pipe fitting.
NOTE:The sprinkler frame arms shall be
parallel to the pipe.
Replaces page F_111220 Rev 21.2
(Added LPCB and VdS details)
BULLETIN
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
CARE AND HANDLING
OF SPRINKLERS
Page 1 of 4
Form No. F_091699 18.10.11 Rev 16.1.P65
SPRINKLERS ARE FRAGILE - HANDLE WITH CARE!
General Handling and Storage:
• Store sprinklers in a cool, dry place.
• Protect sprinklers during storage, transport, handling, and after installation.
• Use the original shipping containers. DO NOT place sprinklers loose in boxes, bins,
or buckets.
• Keep sprinklers separated at all times. DO NOT allow metal parts to contact sprinkler
operating elements.
For Pre-Assembled Drops:
• Protect sprinklers during handling and after installation.
• For recessed assemblies, use the protective sprinkler cap (Viking Part Number 10364).
Sprinklers with Protective Shields or Caps:
• DO NOT remove shields or caps until after sprinkler installation and there no longer is
potential for mechanical damage to the sprinkler operating elements.
• Sprinkler shields or caps MUST be removed BEFORE placing the system in
service!
• Remove the sprinkler shield by carefully pulling it apart where it is snapped together.
• Remove the cap by turning it slightly and pulling it off the sprinkler.
Sprinkler Installation:
• DO NOT use the sprinkler deflector or operating element to start or thread the sprinkler
into a fitting.
• Use only the designated sprinkler head wrench! Refer to the current sprinkler tech-
nical data page to determine the correct wrench for the model of sprinkler used.
• DO NOT install sprinklers onto piping at the floor level.
• Install sprinklers after the piping is in place to prevent mechanical damage.
• DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings, pipe,
or couplings in close proximity to sprinklers. Sprinklers can be damaged from direct or
indirect impacts.
• DO NOT attempt to remove drywall, paint, etc., from sprinklers.
• Take care not to over-tighten the sprinkler and/or damage its operating parts!
Maximum Torque:
1/2” NPT: 14 ft-lbs. (19.0 N-m)
3/4” NPT: 20 ft-lbs. (27.1 N-m)
1” NPT: 30 ft-lbs. (40.7 N-m)
WARNING
Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed. Never install sprinklers
that have been dropped, damaged, or exposed to temperatures exceeding the maximum ambient temperature allowed. Sprinklers that
have been painted in the field must be replaced per NFPA 13. Protect sprinklers from paint and paint overspray in accordance with
the installation standards. Do not clean sprinklers with soap and water, ammonia, or any other cleaning fluid. Do not use adhesives
or solvents on sprinklers or their operating elements.
Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance
instructions. For additional product and system information Viking data pages and installation instructions are available on
the Viking Web site at www.vikinggroupinc.com.
CORRECT
(Original container used)
INCORRECT
(Placed loose in box)
CORRECT
(Protected with caps)
INCORRECT
(Protective caps not used)
CORRECT
(Piping is in place at the
ceiling)
INCORRECT
(Sprinkler at floor level)
CORRECT
(Special installation
wrenches)
INCORRECT
(Designated wrench not
used)

Replaces Form No. F_091699 Rev 16.1
(Added P65 Warning)
BULLETIN
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
CARE AND HANDLING
OF SPRINKLERS
Page 2 of 4
Form No. F_091699 18.10.11 Rev 16.1.P65
PROTECTIVE SPRINKLER SHIELDS AND CAPS
General Handling and Storage:
Many Viking sprinklers are available with a plastic protective cap or shield temporarily covering the operating elements. The snap-
on shields and caps are factory installed and are intended to help protect the operating elements from mechanical damage during
shipping, storage, and installation. NOTE: It is still necessary to follow the care and handling instructions on the appropriate sprin-
kler technical data sheets* when installing sprinklers with bulb shields or caps.
WHEN TO REMOVE THE SHIELDS AND CAPS:
NOTE: SHIELDS AND CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE!
Remove the shield or cap from the sprinkler only after checking all of the following:
• The sprinkler has been installed*.
• The wall or ceiling finish work is completed where the sprinkler is installed and there no longer is a potential for mechanical damage
to the sprinkler operating elements.
SHIELDS AND CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE!
Figure 1: Sprinkler shield being
removed from a pendent sprinkler.
Figure 2: Sprinkler cap being
removed from a pendent sprinkler.
Figure 3: Sprinkler cap being re-
moved from and upright sprinkler.
HOW TO REMOVE SHIELDS AND CAPS:
No tools are necessary to remove the shields or caps from sprinklers. DO NOT use any sharp objects to remove them! Take care
not to cause mechanical damage to sprinklers when removing the shields or caps. When removing caps from fusible ele-
ment sprinklers, use care to prevent dislodging ejector springs or damaging fusible elements. NOTE: Squeezing the sprinkler cap
excessively could damage sprinkler fusible elements.
• To remove the shield, simply pull the ends of the shield apart where it is snapped together. Refer to Figure 1.
• To remove the cap, turn it slightly and pull it off the sprinkler. Refer to Figures 2 and 3.
Refer to the current sprinkler technical data page to determine the correct sprinkler wrench for the model of sprinkler used.
Never install sprinklers that have been dropped, damaged, or exposed to temperatures in excess of the maximum ambient
temperature allowed.
* Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data
pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www.
vikinggroupinc.com.
BULLETIN
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
CARE AND HANDLING
OF SPRINKLERS
Page 3 of 4
Form No. F_091699 18.10.11 Rev 16.1.P65
GENERAL HANDLING AND STORAGE INSTRUCTIONS:
• Do not store in temperatures exceeding 100 °F (38 °C). Avoid direct sunlight and confined areas subject to heat.
• Protect sprinklers and cover assemblies during storage, transport, handling, and after installation.
-- Use original shipping containers.
-- Do not place sprinklers or cover assemblies loose in boxes, bins, or buckets.
• Keep the sprinkler bodies covered with the protective sprinkler cap any time the sprinklers are shipped or handled, during testing of the system, and
while ceiling finish work is being completed.
• Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is
temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed.
• Do not over-tighten the sprinklers into fittings during installation.
• Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation.
• Do not attempt to remove drywall, paint, etc., from the sprinklers.
• Remove the plastic protective cap from the sprinkler before attaching the cover plate assembly. PROTECTIVE CAPS MUST BE REMOVED FROM
SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE!
Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data
pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www.
vikinggroupinc.com.
Concealed Sprinkler and Adapter
Assembly with Protective Cap
CAUTION: CONCEALED COVER ASSEMBLIES ARE FRAGILE!
TO ASSURE SATISFACTORY PERFORMANCE OF THE PRODUCT, HANDLE WITH CARE.
Cover Plate Assembly
(Pendent Cover 12381 shown)
Concealed Sprinkler and Adapter
Assembly (Protective Cap Removed)
BULLETIN
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
CARE AND HANDLING
OF SPRINKLERS
Page 4 of 4
Form No. F_091699 18.10.11 Rev 16.1.P65
USE THE FOLLOWING PRECAUTIONS WHEN HANDLING WAX-COATED SPRINKLERS
Many of Viking’s sprinklers are available with factory-applied wax coating for corrosion resistance. These sprinklers MUST receive
appropriate care and handling to avoid damaging the wax coating and to assure satisfactory performance of the product.
General Handling and Storage of Wax-Coated Sprinklers:
• Store the sprinklers in a cool, dry place (in temperatures below the maximum ambient temperature allowed for the sprinkler temperature rating. Refer
to Table 1 below.)
• Store containers of wax-coated sprinklers separate from other sprinklers.
• Protect the sprinklers during storage, transport, handling, and after installation.
• Use original shipping containers.
• Do not place sprinklers in loose boxes, bins, or buckets.
Installation of Wax-Coated Sprinklers:
Use only the special sprinkler head wrench designed for installing wax-coated Viking sprinklers (any other wrench may damage
the unit).
• Take care not to crack the wax coating on the units.
• For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after
sprinkler installation to protect the corrosion-resistant properties of the sprinkler.
• Use care when locating sprinklers near fixtures that can generate heat. Do not install sprinklers where they would be exposed to temperatures exceed-
ing the maximum recommended ambient temperature for the temperature rating used.
• Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant coating. Thereafter, inspect representative
samples of the coated sprinklers in accordance with NFPA 25. Close up visual inspections are necessary to determine whether the sprinklers are being
affected by corrosive conditions.
Never install sprinklers that have been dropped, damaged, or exposed to temperatures in excess of the maximum ambi-
ent temperature allowed.
Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data
pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www.
vikinggroupinc.com.
TABLE 1
Sprinkler Temperature Rating
(Fusing Point)
Wax Part
Number Wax Melting Point Maximum Ambient
Ceiling Temperature1Wax Color
155 °F (68 °C) / 165 °F (74 °C) 02568A 148 °F (64 °C) 100 °F (38 °C) Light Brown
175 °F (79 °C) 04146A 161 °F (71 °C) 150 °F (65 °C) Brown
200 °F (93 °C) 04146A 161 °F (71 °C) 150 °F (65 °C) Brown
220 °F (104 °C) 02569A 170 °F (76 °C) 150 °F (65 °C) Dark Brown
286 °F (141 °C) 02569A 170 °F (76 °C) 150 °F (65 °C) Dark Brown
1 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
Replaces Form No. F_091699 Rev 16.1
(Added P65 Warning)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
SPRINKLER OVERVIEW
Page 1 of 3
Form No. F_080814 18.12.06 Rev 14.1.P65
1. DESCRIPTION
Viking fire sprinklers consist of a threaded frame with a specific waterway or orifice size and a deflector for distributing water in a
specified pattern. A closed or sealed sprinkler refers to a complete assembly, including the thermosensitive operating element. An
open sprinkler does not use an operating element and is open at all times. The distribution of water is intended to extinguish a fire
or to control its spread.
Viking sprinklers are available in several models and styles. Refer to specific sprinkler technical data pages for available styles,
finishes, temperature ratings, thread sizes, and nominal K-Factors for the particular model selected.
2. LISTINGS AND APPROVALS
Refer to the Approval Charts on the appropriate sprinkler technical data page(s) and/or
approval agency listings.
3. TECHNICAL DATA
Pressure Ratings:
Maximum allowable water working pressure is 175 psig (12 Bar) unless rated and specified for high water working pressure [250
psig (17.2 bar)].
Sprinkler Identication:
Viking sprinklers are identified and marked with the word “Viking”, the sprinkler identification number (SIN) consisting of “VK” plus
a three digit number*, the model letter, and the year of manufacture.
Available Finishes:
Viking sprinklers are available in several decorative finishes. Some models are available with corrosion-resistant coatings or are
fabricated from non-corrosive material. Refer to the sprinkler technical data page for additional information.
Available Temperature Ratings:
Viking sprinklers are available in several temperature ratings that relate to a specific temperature classification. Applicable installa-
tion rules mandate the use and limitations of each temperature classification. In selecting the appropriate temperature classifica-
tion, the maximum expected ceiling temperature must be known. When there is doubt as to the maximum temperature at the
sprinkler location, a maximum-reading thermometer should be used to determine the temperature under conditions that would
show the highest readings to be expected. In addition, recognized installation rules may require a higher temperature classifica-
tion, depending upon sprinkler location, occupancy classification, commodity classification, storage height, and other hazards. In
all cases, the maximum expected ceiling temperature dictates the lowest allowable temperature classification. Sprinklers located
immediately adjacent to a heat source may require a higher temperature rating.
K-Factors:
Viking sprinklers are available in several orifice sizes with related K-Factors. The orifice is a tapered waterway and, therefore, the
K-Factor given is nominal. Nominal U.S. K-Factors are provided in accordance with the 1999 edition of NFPA 13, Section 3-2.3.
Refer to the specific data page for appropriate K-Factor information.
Available Styles:
Viking sprinklers are available for installation in several positions as indicated by a stamping on the deflector. The deflector style
dictates the appropriate installation position of the sprinkler; it breaks the solid stream of water issuing from the sprinkler orifice to
form a specific spray pattern. The following list indicates the various styles and identification of Viking sprinklers.
UPRIGHT SPRINKLER:A sprinkler intended to be installed with the deflector above the frame so water flows upward through the
orifice, striking the deflector and forming an umbrella-shaped spray pat-
tern downward. Marked “SSU” (Standard Sprinkler Upright) or “UPRIGHT”
on the deflector.
PENDENT SPRINKLER:A sprinkler intended to be oriented with the deflec-
tor below the frame so water flows downward through the orifice, striking
the deflector and forming an umbrella-shaped spray pattern downward.
Marked “SSP” (Standard Sprinkler Pendent) or “PENDENT” on the de-
flector.
CONVENTIONAL SPRINKLER:An “old style” sprinkler intended to be installed with the deflector in either the upright or pendent
position. The deflector provides a spherical type pattern with 40 to 60 percent of the water initially directed downward and a
proportion directed upward. Must be installed in accordance with installation rules for conventional or old style sprinklers. DO
NOT USE AS A REPLACEMENT FOR STANDARD SPRAY SPRINKLERS. Marked “C U/P” (Conventional Upright/Pendent) on
the deflector.
Viking Technical Data may be found on
The Viking Corporation’s Web site at
http://www.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
Replaces Form No. F_080814 Rev 14.1
(Added P65 Warning.)
