Viking M Instruction manual

1. PRODUCT NAME
Viking Model M Quick Response
Extended Coverage Light Hazard
Extra-Large Orifice Pendent Sprinkler
•Base Part Number 08339
•Available since 1993.
2. MANUFACTURER
The Viking Corporation
210 N. Industrial Park Road
Hastings, Michigan 49058, U.S.A.
Telephone:(616) 945-9501
(877) 384-5464
Fax:(616) 945-9599
e-mail: [email protected]m
3. PRODUCT DESCRIPTION
The Viking Model M Quick Response
Extended Coverage Light Hazard Ex-
tra-Large Orifice (QR-ECLH-ELO) Pen-
dent Sprinkler is a thermosensitive
glass-bulbspraysprinklerequippedwith
an extra-large orifice and a special de-
flector. The pip-cap and sealing assem-
bly of the sprinkler are held in place by a
rugged,fast-actuating,3mmglassbulb.
The sprinkler is listed as a quick re-
sponse sprinkler when installed in the
specific spacing, temperature rating,
and escutcheon combinations indicated
in Table 2 on page 71 d.
The special deflector is designed to
meet Light-Hazard density require-
mentsfor specifically listedextendedar-
easof coverage whenthe requiredmini-
mum water supply is provided at the
sprinkler.
The extra-large orifice produces the
flows required to meet Light Hazard
densityrequirementsatlowerpressures
than standard orifice or large orifice
sprinklers require.
Viking Model M QR-ECLH-ELO Pen-
dent Sprinklers are available with fin-
ishes and temperature ratings to meet
design requirements. The special Tef-
lon®andPolyestercoatingscanbeused
in decorative applications where colors
are desired. In addition, these two fin-
ishes are corrosion resistant and pro-
vide protection against many corrosive
environments.
Duringfireconditions,whenthe temper-
ature around the sprinkler reaches its
operating temperature, the
heat-sensitiveliquidintheglassbulbex-
pands, causing the bulb to shatter, re-
leasing the pip-cap and sealing spring
assembly. The water flowing through
the sprinkler orifice strikes the sprinkler
deflector, forming a uniform spray pat-
tern to extinguish or control the fire.
4. TECHNICAL DATA
LISTINGS AND APPROVALS
Refer to Table 2 on page 71 d.
Glass-bulb fluid temperature rated to
-65 °F (-55 °C).
Rated 175 psi (1,207 kPa) water work-
ing pressure.
Factory tested hydrostatically to 500 psi
(3,448 kPa).
Thread size: 3/4" NPT (20 mm BSP)
Orifice Size: Nominal 5/8" (16 mm)
K-Factor: 11.5 (16,6 metric, for use
when pressure is measured in kPa).
Minimumoperatingpressure:SeeTable
2 on page 71 d.
Spring: USA Patent No. 4,167,974
Bulb: USA Patent No. 4,796,710
MATERIALS
Frame: Brass castings UNS-C84400
Deflector: Brass UNS-C26000
Bulb: Glass, nominal 3 mm diameter
Seal: Teflon®Tape
Spring: Nickel Alloy
Pintle Screw: Brass UNS-C36000
Pip Cap: Bronze UNS-C31600
Teflon®-Coated Sprinklers:
Spring: Nickel alloy, exposed
Pintle Screw: Brass UNS-C36000
Painted black for appearance only.
Pip Cap: Bronze UNS-C31600, Teflon ®
coated
Polyester-Coated Sprinklers:
Spring: Nickel alloy, exposed
Pintle Screw: Brass UNS-C36000
Paintedwhiteorblackforappearance
only.
Pip Cap: Bronze UNS-C31600
ACCESSORIES
Sprinkler Wrenches*:
•Standard ELO wrench: Part No.
07297W/B.
•Wrench for coated and recessed
ELO sprinklers: Part No.
07565W/B.
*A½"ratchetisrequired(notsuppliedbyVi-
king).
AVAILABLE FINISHES
Chrome-Enloy®(patents pending),
Brass,BlackTeflon®,andWhitePolyes-
ter [Black Polyester is available for the
155 °F (68 °C) temperature-rated sprin-
kler only].
5. AVAILABILITY AND SERVICE
Vikingsprinklersare availablethrougha
network of domestic, Canadian, and in-
ternational distributors. See the Yellow
FormNo.F_051293
TECHNICAL DATA
MODEL M QUICK RESPONSE
EXTENDED COVERAGE
LIGHT HAZARD
EXTRA-LARGE ORIFICE SPRINKLER
Sprinkler 71 a
Model M Quick Response
Extended Coverage
Light Hazard Extra-Large Orifice
Pendent Sprinkler
Replaces sprinkler page 71 a-c, dated May 21, 1998
(added 155 °F (68 °C) Black Polyester finish option).
June 4, 1999
Note: Units of measure in parentheses may be approximations.
Sprinkler
Temperature
Classification
Nominal Sprinkler
Temperature Rating
(Fusing Point)
Ceiling Temperature at SprinklerBulb
Color
Max. Ambient
Temp.Allowed 1Max. Recommended
Ambient Temp. 2
Ordinary135 °F (57 °C)115 °F (46 °C)100 °F (38 °C)Orange
Ordinary155 °F (68 °C)135 °F (57 °C)100 °F (38 °C)Red
Intermediate175 °F (79 °C)155 °F (68 °C)150 °F (65 °C)Yellow
Sprinkler Finishes: Brass, Bright Brass, Chrome-Enloy ®(patents pending), and White
Polyester Black Polyester is also available with the 155 °F (68 °C)temperature rating
only.
Corrosion-resistant Coatings 3: Black Teflon ®and White Polyester[Black Polyester is also
available with the 155 °F (68 °C)temperature rating only.
Footnotes
1 Based on National Fire Prevention and Control Administration Contract No. 7-34860.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location,
and other requirements of the Authority Having Jurisdiction. Refer to specific installation
standards.
3The corrosion-resistant coatings have passed standard corrosion tests required by
particular approving agencies. Refer to the approval chart on page 71 d. These tests can-
not and do not represent all possible corrosive environments. Prior to installation, ve rify
through the end-user that the coatings are compatible with or suitable for the proposed
environment. The coatings indicated are applied to the exposed exterior surfaces only an d,
therefore, cannot be used as open sprinklers.
NOTE: The spring is exposed on the Teflon ®-coated and Polyester-coated sprinklers.
Table 1
OBSOLETE
Pagesofthetelephone directoryforalo-
cal distributor (listed under “Sprin-
klers-Automatic-Fire”)orcontactViking.
Viking Technical Data may be found on
The Viking Corporation’s Web site at
http://www.vikingcorp.com.
The Web site may include a more recent
edition of this Technical Data page.
6. GUARANTEES
For details of warranty, refer to Viking’s
currentpricescheduleorcontactTheVi-
king Corporation directly.
7. INSTALLATION
WARNING:Viking sprinklers are manu-
factured and tested to meet the rigid re-
quirements of the approving agency.
The sprinklers are designed to be in-
stalled in accordance with recognized
installation standards. Deviation from
the standards or any alteration to the
sprinkler after it leaves the factory in-
cluding, but not limited to: painting, plat-
ing,coating,ormodification,mayrender
the sprinkler inoperative and will auto-
matically nullify the approval and any
guaranteemadebyTheViking Corpora-
tion.
A.Sprinklersaretobe installedinaccor-
dance with the latest published stan-
dards of the National Fire Protection
Association, Factory Mutual, Loss
Prevention Council, Assemblee
Pleniere, Verband der
Sachversicherer or other similar or-
ganizations, and also with the provi-
sions of governmental codes, ordi-
nances,andstandardswheneverap-
plicable. The use of QR-ECLH-ELO
Sprinklers may be limited due to oc-
cupancyandhazard.RefertotheAu-
thority Having Jurisdiction prior to in-
stallation.
B.Sprinklersmustbehandledwithcare.
They must be stored in a cool, dry
place in their original shipping con-
tainer. Never install sprinklers that
have been dropped or damaged in
anyway.Never installanyglass-bulb
sprinkler if the bulb is cracked or if
there is a loss of liquid from the bulb.
If a glass bulb lacks the appropriate
amountof fluid, it should beset aside
and returned to Viking (or an autho-
rized Viking distributor) for analysis
assoonaspossible. If thesprinkleris
not returned to Viking, it should be
destroyed. Never install sprinklers
whichhave been exposedtotemper-
aturesinexcessofthemaximumam-
bient temperature allowed (these
sprinklers should be destroyed im-
mediately).
C. Corrosion-resistant sprinklers must
be installed when subject to corro-
sive atmospheres. When installing
sprinklers with a corrosion-resistant
coating, care must be taken not to
damage the coating. Use only the
special wrench designed for install-
ing coated and recessed Viking ELO
sprinklers. (Any other wrench may
damage the coating.)
D. The sprinklers must be installed after
the piping is in place to prevent me-
chanicaldamage.Beforeinstallation,
besuretohavetheappropriatesprin-
kler model and style, with the correct
orifice size, temperature rating, and
response characteristics.
1. Installescutcheon(ifused), which
is designed to thread onto the ex-
ternal threads of the sprinkler.
2. Apply a small amount of pipe-joint
compound or tape to the external
threads only, taking care not to al-
lowa build-upofcompoundinside
the sprinkler inlet.
3. Install the sprinkler on the piping
usingthe special sprinkler wrench
only, taking care not to damage
the sprinkler operating parts. DO
NOT use the sprinkler deflector to
start or thread the sprinkler into a
fitting.
E. After installation, the entire sprinkler
systemmustbetestedinaccordance
with the recognized installation stan-
dards. The test is applied after the
sprinklerinstallationtoensurethatno
damagehasoccurredtothesprinkler
during shipping and installation, and
to make sure the sprinkler has been
properly tightened. If a thread leak
occurs, normally the sprinkler must
be removed, new pipe-joint com-
pound or tape applied, and then rein-
stalled. This is due to the fact that
when the joint seal is damaged, the
sealing compound or tape is washed
out of the joint. Air testing the sprin-
kler piping prior to testing with water
may be considered in areas where
leakage during testing must be pre-
vented. Refer to the Installation
Guides and the Authority Having Ju-
risdiction.
F. Sprinklers must be protected from
mechanical damage. Wet pipe sys-
tems must be provided with ade-
quate heat. When installing Model M
QR-ECLH-ELO Sprinklers on dry
systems, refer to the Installation
Guides and the Authority Having
Jurisdiction.
8. MAINTENANCE
NOTICE:The owner is responsible for
maintaining the fire-protection system
and devices in proper operating condi-
tion. For minimum maintenance and in-
spection requirements, refer to the Na-
tional Fire Protection Association’s
pamphlet that describes care and main-
tenance of sprinkler systems. In addi-
tion, the Authority Having Jurisdiction
may have additional maintenance, test-
ing, and inspection requirements that
must be followed.
A. Sprinklers must be inspected on a
regular basis for corrosion, mechani-
cal damage, obstructions, paint, etc.
The frequency of the inspections
may vary due to corrosive atmo-
spheres, water supplies, and activity
around the device.
B. Sprinklers that have been field
painted or mechanically damaged
must be replaced immediately.
Sprinklers showing signs of corro-
sion shall be tested and/or replaced
immediately as required. Installation
standards require sprinklers to be
tested and, if necessary, replaced
immediately after a specified term of
service. For Viking Model M
QR-ECLH-ELO Sprinklers, refer to
the Installation Standards and the
Authority Having Jurisdiction for the
specified period of time after which
testing and/or replacement is re-
quired.Sprinklersthat haveoperated
cannot be reassembled or re-used,
but must be replaced. When replac-
ing sprinklers, use only new sprin-
klers.
C.Thesprinklerdischargepatterniscrit-
icalforproperfireprotection.Nothing
should be hung from, attached to, or
otherwiseobstructthe dischargepat-
tern. All obstructions must be imme-
diately removed or, if necessary, ad-
ditional sprinklers installed.
D. When replacing existing sprinklers,
the system must be removed from
service.Refer to the appropriate sys-
tem description and/or valve instruc-
tions. Prior to removing the system
from service, notify all Authorities
Having Jurisdiction. Consideration
should be given to employment of a
fire patrol in the affected area.
1. Remove the system from service,
drain all water, and relieve all
pressure on the piping.
2.Usingthespecialsprinklerwrench,
remove the old sprinkler and in-
stall the new unit. Care must be
taken to ensure that the replace-
mentsprinkler istheproper model
and style, with the correct orifice
size, temperature rating, and re-
sponse characteristics. A fully
stocked spare sprinkler cabinet
TECHNICAL DATA
Sprinkler 71 b
MODEL M QUICK RESPONSE
EXTENDED COVERAGE
LIGHT HAZARD
EXTRA-LARGE ORIFICE SPRINKLER
June4,1999
OBSOLETE
should be provided for this pur-
pose.
3.Place the system back in service
and secure all valves. Check and
repair all leaks.
E. Sprinkler systems that have been
subjected to a fire must be returned
to service as soon as possible. The
entire system must be inspected for
damage and repaired or replaced as
necessary.Sprinklersthathavebeen
exposed to corrosive products of
combustion or high ambient temper-
atures,buthavenotoperated,should
be replaced. Refer to the Authority
Having Jurisdiction for minimum re-
placement requirements.
TECHNICAL DATAMODEL M QUICK RESPONSE
EXTENDED COVERAGE
LIGHT HAZARD
EXTRA-LARGE ORIFICE SPRINKLER
Sprinkler 71 c
June 4, 1999
Model M QR ECLH-ELO
Pendent Sprinkler
Installed with a 1/8" (3,1 mm)
Standard Surface Escutcheon
Model M QR ECLH-ELO
Pendent Sprinkler
Installed with the Microfast ®
Model F-1 Adjustable Escutcheon
Model M QR ECLH-ELO
Pendent Sprinkler
Installed with the Micromatic ®
Model E-1 Recessed Escutcheon
Model M Quick Response
Extended Coverage
Light Hazard
ELO Pendent Sprinkler
Figure 1
Figure 2
OBSOLETE
Form No. F_051293
Replaces sprinkler page 71 a-c, dated May 21, 1998
(added 155 °F (68 °C) Black Polyester finish option).
Deflector StyleThread SizeNominal OrificeNominal K-FactorOverall LengthBase
P/N 2
N.P.T.B.S.P.InchmmUSmetric 1Inchmm
Pendent3/4205/81611.516,62.7569,908339
Approval Chart
Model M Quick Response Extended Coverage
Light Hazard Extra-Large Orifice Sprinklers
Maximum Sprinkler Spacing
Length x Width4Maximum Area
per SprinklerMinimum Water Supply Requirements
(Flow and Pressure)Listings3
UL 5C-UL 5NYC 6
16' Wide x 16' Throw (4,9 m x 4,9 m)256 ft. 2(23,8 m2) 30.4 gpm @ 7.0 psi (115,1 L/min @ 48,3 kPa)A1XA1X–
18' Wide x 18' Throw (5,5 m x 5,5 m)324 ft. 2(30,1 m2) 33 gpm @ 8.2 psi (124,9 L/min @ 56,6 kPa)C1X, D1YC1X, D1Y–
20' Wide x 20' Throw (6,1 m x 6,1 m)400 ft.2(37,2 m 2)40 gpm @ 12.1 psi (151,0 L/min @ 83,5 kPa)B1X, E1Y 7B1X, E1Y 7–
Approved Temperatures
A - 135 °F (57 °C), 155 °F (68 °C), and
175 °F (79 °C)
B - 135 °F (57 °C)
C - 135 °F (57 °C) and 175 °F (79 °C)
D - 155 °F (68 °C)
E - 175 °F (79 °C)
Approved Finishes
1 - Chrome-Enloy®, Brass, Black
Teflon ®, and White Polyester
[Black Polyester is approved
for 155 °F (68 °C) temperature
rating only].
Approved Escutcheons
X - Standard surface-mounted escutcheon or the
Microfast ® Model F-1 Adjustable Escutcheon 8,
orrecessed with the Micromatic®Model E-1
Adjustable Recessed Escutcheon
Y - Standard surface-mounted escutcheon or the
Microfast ®Model F-1 Adjustable Escutcheon 8
Footnotes
1 Metric K-Factor shown is for use when pressure is measured in kPa. When pressure is measured in BAR, multiply the metric K-Factor
shown by 10.0.
2Part number shown is the base part number. For complete part number, refer to current Vikin g Price List.
3This chart shows listings and approvals available at time of printing. Other approvals are in process. Check with the manufacturer for
additional approvals.
4To determine "Minimum Water Supply Requirement" for areas of coverage where length and width of actual sprinkler spacing are not
equal, select the "Maximum Sprinkler Spacing" from the chart that is equal to or greater than the larger of the actual spacing (length or
width) dimensions used. Example: When using 15' - 0" x 17' - 0" actual sprinkler spacing, p rovide the "Minimum Water Supply Require-
ment" listed in the chart for 18'-0" x 18'-0" spacing. For areas of coverage smaller than shown , use the "Minimum Water Supply Require-
ment" for the next larger area listed. The distance from sprinklers to walls shall not exceed on e-half the "Maximum Sprinkler Spacing"
listed for the "Minimum Water Supply Requirement" used.
5Listing is limited to Light-Hazard occupancies with smooth, flat, horizontal ceilings.
6Acceptance by City of New York Department of Buildings is pending.
7This sprinkler is also listed for use at 20 ft. x 20 ft. (6,1 m x 6,1 m) spacing, with other temperature rating and escutcheon combinations, as
a standard response sprinkler. Refer to the Model M ECLH-ELO technical data page.
8The Microfast® Model F-1 Adjustable Escutcheon is considered a surface-mounted escutcheon because it does not allow the fusible
element of the sprinkler to be recessed behind the face of the wall or ceiling.
Table 2
TECHNICAL DATAMODEL M QUICK RESPONSE
EXTENDED COVERAGE
LIGHT HAZARD
EXTRA-LARGE ORIFICE SPRINKLER
Sprinkler 71 dJune 4, 1999
KEY
Temperature
Finish
A1XEscutcheon (if applicable)
OBSOLETE

Other manuals for M

6

Other Viking Irrigation System manuals

Viking VK530 Instruction manual

Viking

Viking VK530 Instruction manual

Viking SIN VK520 Instruction manual

Viking

Viking SIN VK520 Instruction manual

Viking SupplyNet DS21-24 User manual

Viking

Viking SupplyNet DS21-24 User manual

Viking VK506 Service manual

Viking

Viking VK506 Service manual

Viking FREEDOM VK494 Instruction manual

Viking

Viking FREEDOM VK494 Instruction manual

Viking MIRAGE VK464 Instruction manual

Viking

Viking MIRAGE VK464 Instruction manual

Viking MICROMATIC VK104 Instruction manual

Viking

Viking MICROMATIC VK104 Instruction manual

Viking VK512 K25.2 Instruction manual

Viking

Viking VK512 K25.2 Instruction manual

Viking SIN VK500 Instruction manual

Viking

Viking SIN VK500 Instruction manual

Viking D-1 Sprinkler Guard Instruction manual

Viking

Viking D-1 Sprinkler Guard Instruction manual

Viking FREEDOM VK486 Instruction manual

Viking

Viking FREEDOM VK486 Instruction manual

Viking MIRAGE VK465 Instruction manual

Viking

Viking MIRAGE VK465 Instruction manual

Viking VK4921 Instruction manual

Viking

Viking VK4921 Instruction manual

Viking VK506 Instruction manual

Viking

Viking VK506 Instruction manual

Viking GB 460 User manual

Viking

Viking GB 460 User manual

Viking VK1001 Instruction manual

Viking

Viking VK1001 Instruction manual

Viking MICROFAST VK354 Instruction manual

Viking

Viking MICROFAST VK354 Instruction manual

Viking FREEDOM VK480 Instruction manual

Viking

Viking FREEDOM VK480 Instruction manual

Viking VK595 Instruction manual

Viking

Viking VK595 Instruction manual

Viking MICROFAST VK328 Instruction manual

Viking

Viking MICROFAST VK328 Instruction manual

Viking K5-6 Instruction manual

Viking

Viking K5-6 Instruction manual

Viking MICROFAST M-4 Instruction manual

Viking

Viking MICROFAST M-4 Instruction manual

Viking VK3542 Instruction manual

Viking

Viking VK3542 Instruction manual

Viking MIRAGE VK632 Instruction manual

Viking

Viking MIRAGE VK632 Instruction manual

Popular Irrigation System manuals by other brands

Rain Bird STP-400i Operation manual

Rain Bird

Rain Bird STP-400i Operation manual

Tyco TY-FRB Series Installation and operation manual

Tyco

Tyco TY-FRB Series Installation and operation manual

Tyco RFII Series quick start guide

Tyco

Tyco RFII Series quick start guide

Tyco TY-B Series manual

Tyco

Tyco TY-B Series manual

Tyco ELO-231B Series manual

Tyco

Tyco ELO-231B Series manual

Hunter Institutional I-40 quick start guide

Hunter

Hunter Institutional I-40 quick start guide

Tyco ESFR-17 manual

Tyco

Tyco ESFR-17 manual

Tyco DS-1 Series quick start guide

Tyco

Tyco DS-1 Series quick start guide

Netafim NMC-JUNIOR PRO installation guide

Netafim

Netafim NMC-JUNIOR PRO installation guide

Hunter I-31 Plus instructions

Hunter

Hunter I-31 Plus instructions

Tyco Grinnell F692 DESIGNER manual

Tyco

Tyco Grinnell F692 DESIGNER manual

Solem LoRa LR-BST-25 installation guide

Solem

Solem LoRa LR-BST-25 installation guide

Weathermatic D50 Series installation guide

Weathermatic

Weathermatic D50 Series installation guide

Eden 94141EDAMZ quick start guide

Eden

Eden 94141EDAMZ quick start guide

Tyco K17-231 Installation

Tyco

Tyco K17-231 Installation

Autopot 36Pot XL Set-up guidelines

Autopot

Autopot 36Pot XL Set-up guidelines

Weathermatic SmartLink SL-AIRCARDFLOW owner's manual

Weathermatic

Weathermatic SmartLink SL-AIRCARDFLOW owner's manual

Eden 94135EDAMZ manual

Eden

Eden 94135EDAMZ manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.