Vinotemp WINE-MATE WM-2520SSL Installation guide

-1-
Important Safety Information
WARNING
To avoid the risk of electrical shock, property damage, personal injury, or death:
•The power cord must be plugged into a 3-prong grounding type wall
receptacle, grounded in accordance with the National Electrical Code,
ANSI/NFPA 70 –latest edition and local codes and ordinances.
•It is the personal responsibility of the consumer to have a proper 3-prong wall
receptacle installed by a qualified electrician.
•DO NOT, UNDER ANY CIRCUMSTANCES, REMOVE THE POWER CORD
GROUNDING PRONG.
•A separate adequately fused and grounded circuit should be available for this
appliance.
•Do not remove any grounding wires from individual components while servicing
unless the component is to be removed and replaced. It is extremely important
to replace all grounding wires when components are replaced.
WARNING
ELECTRICAL SHOCK HAZARD
•Disconnect electrical supply from appliance before servicing.
•Replace all panels before operating.
•Failure to do so could result in death or electrical shock.

-2-
Table of Contents
Cellar Construction Guide-----------------------------------------3
Features & Specifications -- -4
Temperature & Humidity -- - 6
Care Guide- - -- - 10
User’ Troubleshooting - -11
Installer’s Instructions- - -14
Electrical Wirings -- -- 26
Warranty --- --- -- - -- --- -- --- - --- --- -29

-3-
Cellar Construction Guide
This is only a guide and shall be considered as the minimum requirements.
All interior walls, ceilings and floors shall have a vapor barrier and a minimum of
R13 insulation. All exterior walls and ceiling shall have a vapor barrier and a
minimum of R19 insulation. The vapor barrier shall be installed on the warm side
of insulation. All joints, door frames, electrical outlets or switches and any pipes
or vents that go through the cellar shall be sealed to prevent air and moisture leaking
into the cellar. Concrete, rock, and brick are not insulations or vapor barriers. Doors
shall be of a minimum size, insulated to at least R13 and tightly sealed with high
quality weather stripping. Be sure to seal the bottom of the door and fill gap between
the door’s frame and wall before installing the cap molding.
In order to maintain 55 °F in the wine cellar, the ambient temperature surrounding
the cellar shall not exceed the temperature of the cellar by more than 25 °F. No
cellar walls shall receive direct sun or strong wind.
Lighting shall be of low wattage, with a timer to insure lights are not left on when the
cellar is not occupied.
The cooling system will not be able to maintain the proper temperature if fresh
moisture-laden air is constantly being introduced to the cellar. Symptoms of this
condition are; cooling unit runs all the time with only a slight reduction in temperature
and/or water overflows from the cooling unit. Because of the temperature difference
between the inside and outside, very small cracks can allow large amounts of
outside air to enter into the cellar. Please be aware that moisture can pass through
solid concrete, paint and wood. Often a newly constructed cellar contains fresh
wood, paint, concrete and other building materials. These materials contain large
amounts of moisture. When placed into operation in this type of environment, the
system will work harder to remove this extra moisture resulting in increased “run”
time.

-4-
Features and Specifications
•
WINE~MATE split low-profile cooling systems WM-2520~8520SSL and WM-
2520~8520SSL-LA are designed to provide a cold environment between 50~65
°F with a humidity range within 50~70% RH for a properly insulated wine cellar.
•
These temperature and humidity ranges are optimized for long term storage of
wine like that in natural caves.
•
SSL evaporator units can be installed on the ceiling in a small cabinet or
room. The evaporator units provide low profile and whisper quiet operation.
•
SSL cooling systems consist of a remote condensing unit and an evaporator unit
and they are connected by a liquid line and an insulated suction line.
•
SSL condensing units can be located away from the wine cellars up to 75 ft so
that noise and compressor vibration are isolated.
Fig. 1 SSL Split Low-Profile Cooling System

-5-
CAUTION
If the condensing unit will operate below 50°F, install a low
ambient condition kit.
NOTE
The cooling capacity is determined under 55°F cellar temperature,
75°F cellar ambient temperature and 90°F condensing unit ambient
temperature, with R13 interior and R19 exterior insulations. Higher
ambient temperatures or lower insulations will cause reducing
capacity and the cellar temperature may not be maintained at 55°F.
The specifications are listed as follows:
Model No.
Capacity (Btu/h) / Airflow (CFM)
Max Cellar Size (cu ft)
WM-2520SSL WM-
2520SSL-LA
2100 / 230
230
WM-4520SSL WM-
4520SSL-LA
3700 / 380
900
WM-6520SSL WM-
6520SSL-LA
5400 / 480
1400
WM-8520SSL WM-
8520SSL-LA
7100 / 695
1800
NOTE
“LA” refers the unit equipped with a low ambient kit.
For further info, see Fig. 3~7.

-6-
Temperature and Humidity
1. The controller
Fig. 2 TEMPERATURE CONTROLLER
1) Keys
SET: To display set-point; in programming mode it selects a parameter or
confirms an operation.
: To start a manual defrost.
: To see the maximum stored temperature; in programming mode it browses
the parameter codes or increases the displayed value.
: To see the minimum stored temperature; in programming mode it browses
the parameter codes or decreases the displayed value.
: To turn on/off the power to the unit.
+ : To lock/unlock the keypad.
SET+ : To enter in the programming mode.
SET+ : To return to the temperature display.
2) Lock and unlock the keys
To lock the keys, press up + down keys + until POF is displayed; to unlock
the keys, press up + down keys + until PON is displayed.
3) Display
During normal operating conditions, the display shows the value measured by the
air temperature probe. In case of active alarm, the temperature flashes alternately
to the code alarm. The LED functions are listed as follows.
LED
MODE
FUNCTION
ON
Compressor enabled
Flashing
Anti-short cycle enabled
ON
Defrost enabled
ON
Fan enabled
Flashing
Fan delay after defrost enabled
ON
Alarm occurring
ON
Temperature measuring unit
Flashing
Programming mode

-7-
4) Alarm Signals
The alarm codes are described as follows.
MESSAGE
CAUSE
FUNCTION
P1
Temperature probe
faulty
Compressor switching to Con and
CoF
HA
High temperature
alarm
Probe temperature ALU higher than
the
setting temperature; Outputs
unchanged
LA
Low temperature
alarm
Probe temperature ALL lower than
the
setting temperature; Outputs
unchanged
CA
External alarm
All outputs off
Probe alarms P1”, start a few seconds after the fault in the related probe; they
automatically stop a few seconds after the probe restarts normal operation. Check
connections before replacing the probe. Temperature alarms “HA”, “LA”
automatically stops as soon as the temperature returns to normal value. Alarm “CA”
(with i1F=PAL) recovers only by switching off and on the instrument.
2. Temperature Setting
•
Set the temperature at 55 °F for the optimum aging of wine
•
On initial start-up, the time required to reach the desired temperature will vary,
depending on the quantity of bottles, temperature setting and surrounding
temperature.
•
Allow 24 hours to stabilize the temperature for each new temperature setting
operation
3. How to see temperature set-point
1) Press and immediately release the SET key, the display will show the set-point
value.
2) Press again and immediately release the SET key to display the probe value.
4. How to change the set-point
1) Press and hold the SET key until the “°C” or “°F” LED starts flashing and the
set-point is displayed.
2) Press the up/down keys / to change the set-point value within 10 sec.
3) Press the SET key again to store the new set-point value.
NOTE
The unit turns on at set-point Set plus regulation differential Hy after
anti-short cycle AC has elapsed; the unit turns off at set-point Set.

-8-
5. Manual Defrost
Press and hold the defrost key until defrost starts. The defrost indicator will be
on.
6. Parameter Programming
1) Press and hold the SET + keys until the “°C” or “°F” LED starts flashing,
then release the keys.
2) Press and hold again the SET + keys until the Pr2 label is displayed, then
release the keys. The first parameter Hy will be displayed.
3) Press up/down keys / to scroll to the required parameter within 10 sec.
4) Press the “SET”key to display its value.
5) Use up/down keys to change its value within 10 sec.
6) Press “SET”to store the new value and the display will flash 3 times.
7) To exit: Press SET + or wait 15sec without pressing a key.
PARAMETER
DESCRIPTION
DEFAULT VALUE
Set
set-point (°)
55
Hy
temperature regulation differential
(°)
4
AC
anti-short cycle delay (min)
10 (hidden)
Con
compress on with probe faulty (min)
15
CoF
compress off with probe faulty (min)
30
CF
temperature unit (°F/ °C)
F: Fahrenheit
rES
display resolution
in: integer
dLy
temperature display delay (min)
1
ot
probe calibration (°)
0
LS
minimum set-point (°)
50
US
maximum set-point (°)
65
idF
defrost interval time (hour)
12
MdF
defrost endurance time (min)
30
ALC
temperature alarm type
rE: relative to set-point
ALU
high temperature alarm (°)
10
ALL
low temperature alarm (°)
10
AFH
alarm recovery differential (°)
5
ALd
temperature alarm delay (min)
60
dAO
temperature alarm delay on startup
(hr)
23
SAA
heater set-point (°)
40
SHy
heater regulation differential (°)
4
FSU
fan action
Std
FnC
fan operating mode
C-n: on with compressor & off during
defrost
Fon
fan on with compressor off (min)
0
FoF
fan off with compressor off (min)
15
NOTE
Depending on the controller, not all parameters are available.

-9-
7. How to calibrate the air probe
If the actual cellar temperature differs from the setting temperature, set
parameter ot = actual cellar temperature minus set-point.
8. How to adjust defrost settings
In case there is excessive frost, the parameters FnC = C-y, idF = 4 and MdF =
20 can be used to avoid frost.
9. How to adjust the humidity
The parameter Fon is used to adjust the humidity in the wine cellar. Higher Fon
results in higher relative humidity. Use a separate hygrometer to monitor the
humidity.
10. How to set alarm call
1) Speech notice will be sent to your phones when the cellar temperature is ALU
higher or ALL lower than the set-point Set.
2) In order to test the call function, set parameters Ald = 0 and dAO = 0. After
testing, set Ald = 60 and dAO = 23.
11. How to set cellar heater
The heater turns on at SAA minus Shy; the heater turns off at SAA.
NOTE
Use a forced air heater to warm up the wine cellar.
If there is a thermostat on the heater, bypass it or set thethermostat
at the highest level.
If the heater runs more than 10 A current, use a 120VAC coil
contactor.

-10-
Care Guide
In general, always unplug system or disconnect power while doing care.
1. Condenser Coil Cleaning
•
Clean the condenser coil regularly. Coil may need to be cleaned at leastevery
6 months.
•
Use a vacuum cleaner with an extended attachment to clean the coil when it
is dusty or dirty.
2. Condensate Removing
•
Remove the excessive condensate if it is accumulated in the wine cellarunder
high humidity conditions.

-11-
User’s Troubleshooting
This Troubleshooting Chart is not prepared to replace the training required for a
professional refrigeration service person, not is it comprehensive.
Complaint
Possible Causes
Response
1. Unit not
running
Power cord not plugged
No power from supply
Incorrect or loose wirings
Low voltage
Settinghigher than ambient
temperature
Waiting for cut-in
Defrost light blinking
Compressor light blinking
Defective controller
Check power cord
Check receptacle and fuses
Check all wirings and connections
Contact an authorized electrician
Lower temperature setting
Wait
Unit is under defrost mode
Unit is under anti-short cycle delay
Call service for diagnosis
2. Unit not
starting
, but temperature
rising high
a. Anti-short cycle
a. Reset AC
3. Temperature
fluctuating
a. Air probe
a. When using an air probe, the
wine bottle temperature is mainly
controlled by the average air
temperature. If the set-point is 55°F
with the differential 4F, the cooling
unit turns on at 59°F of air
temperature (It may be higher than
59°F if it is in anti-short cycle or
defrost) and turns off at 55°F of air
temperature. The average air
temperature is 57°F, and then the
wine temperature is around 57+/-
0.5°F. The air is light enough to
change so quickly that it maintains
relatively constant average
temperature that would prevent
wine
bottle temperature from
fluctuating.
4. Temperature
high, unit
stopping and
starting normally
a. Temperature setting high
a. Lower the setting
5. Temperature
high, unit
stopping and
starting with short
running
time
Air probe touching the
evaporator coil, displaying
temperature ok
Air probe in cold-air supply,
displaying temperature ok
Failed controller and probe
Move the air probe away from the
evaporator
Move the air probe away from the
cold-air supply
Call service for diagnosis

-12-
6. Temperature
high or not
cooling and
running
continually
Improper cellar insulation & seal
Cellar too large
Ambient temperature too high
Exhaust restricted
Check insulation, gasket and door
opening
Check for excessive size
Check installation location
Leave minimum 3 feet clearance
forthe hot air exhaust side and
leave

-13-
Malfunctioning fans
Evaporator or condenser airflow
Dirty Condenser
Iced evaporator
Refrigeration system restriction
Refrigerant leak
Undercharge or overcharge
Failed components
minimum 1 foot clearance for the
ambient air intake side
Check for both evaporator and
condenser fans
Check for air restrictions, air short-
circulation, grille directions
Clean condenser
Defrost and reset temperature
Call service
Call service
Call service
Check compressor windings, startrelay
and overload protector
7. Unit running too
long
Improper cellar insulation & seal
Exhaust restricted
Cellar too large
Ambient temperature > 90°F
Dirty Condenser
Improper condenser air flow
Check insulation, gasket and door
opening
Leave minimum 3 feet clearance for the
hot air exhaust side and leaveminimum
1 foot clearance for the ambient air
intake side
Check for excessive size
Check for installation location
Clean condenser
Check for fan and air short circulation
8. Condenser fan
running but
compressor not
running
Incorrect or loose wirings
Failed components
Liquid refrigerant in the
compressor
Check all wirings and connections
Check start relay, start capacitor,
overload protector, compressor.
Call service.
9. Compressor
running but
condenser fan
not running
Fan blade stuck
Incorrect or loose wirings
Failed motors
Fan cycle control
Check for proper clearance
Check all wirings
Call service
Check for setting
10.Temperature
high, compressor
stopping and
starting but very
short
running time
Failed components
Improper condenser airflow
Dirty condenser
Overcharge of refrigerant
Discharge or suction pressuretoo
high
Check compressor windings, startrelay
and overload protector.
Check for condenser fan
Clean condenser
Call service for removing refrigerant
Call service for information
11.Evaporator fan
running toolong
a. Post-compressor fan
runningmode for humidity
modulation
a. Reset FON
12. Evaporator fan
running but
condensing
unit notrunning
Incorrect or loose wirings
Failed components
Low refrigerant
Check all wirings and connections
Check start relay, start capacitor,
overload protector, compressor.
Call service
13.Temperaturelow
Low temperature setting
Low ambient temperature
Air probe fault
Temperature controller fault
Raise the setting
Move to another location
Check probe connections or changea
new one
Change a new one
14.Evaporator
freezing up
Evaporator air flow restriction
Condenser air flow restriction
Check for fans and CFM
Check for fans and CFM

-14-
Not stopping due to air leak, high
ambient temperature or low
temperature setting
Defective controller or probe
Low ambient temperature
Initially working then stopping,
moisture in the system
Refrigerant low or leaking
Expansion valve blockage
Check for seal, door opening, ambient
temperature and
temperature setting
Check for controller and probe
Change defrost settings
Call service
Call service
Call service
15.Water leak
Air leak in the wine cellar causing
excessive condensate
High humidity causing excessive
condensate
Evaporator air flow restriction
Drain restricted or unit not level,
and water overflowing
Drip tray leak (No overflow butleak)
Check for air leak
Use drain line
Check supply air flow or air TD
Clean the drip tray and drain line
Seal the leak using silicone sealant
16.Excessive
condensate inwine
cellar
Air leak in the wine cellar causing
excessive condensate
High humidity causing excessive
condensate
Drain restricted
Check for any air leak
Use drain line
Clean the drip tray and drain line
17.Condensate
inside ducts
Drain line restricted
Continually running not stopping
Too cold supply air
Check for drain
raise temperature setting or
increase defrost
Increase air flow or
raise
temperature setting
18.Condensate
outside ducts
Duct not insulated
High humidity
Too cold supply air
Check for insulation
Use dehumidifier
Increase air flow or
raisetemperature setting
19.Circuit tripping
Incorrect fuse or breaker
Incorrect wirings
Failed components
Check for proper fuse or breaker
Check for wirings and connections
Call service
20.Noisy
operation
Mounting area not firm
Loose parts
Compressor overloaded due to high
ambient temperatures orairflow
restriction
Defective components
Add support to improve installation
Check fan blades, bearings, washers,
tubing contact and loosescrews.
Check for airflow
Call service for checking internal loose,
inadequate lubrication and
incorrect wirings

-15-
Installer’s Instructions
WARNING
•Always check wiring harness connections before initiating any test procedures.
•Disconnect electric power from the appliance before performing any
maintenance or repairs.
•Voltage checks should be made by inserting meter proves beside the wires in
the connector blocks with the electric power source on and the connector block
plugged in.
•Resistance checks should be made on components with the electric power off
and the connector block disconnected.
Federal law requires that WINE~MATE split cooling systems be
installed by an EPA certified refrigeration technician.
1. General Instructions
WINE~MATE split system is shipped as components and is ready for use only after
a certified refrigeration technician has properly installed the system. Proper
installation is critical. Vinotemp can only warrant the quality of the components.The
installation and proper operation of the system must be warranted by the installer.
Installation of the system must be done in accordance with all state and local
building and electrical codes.
The condensing unit and evaporator unit are connected by a liquid line and an
insulated suction line that are supplied by the installer. These lines must beproperly
sized for the distance between the two units. After the units and linesare
connected, the system must be checked for restriction, pressurization andleak.
Then the system must be evacuate and charged with refrigerant. Refrigerant
amount will vary depending on the length of line set.
Parts included:
Temperature Controller
Evaporator Unit (liquid line solenoid valve and expansion valve are installed)
Condensing Unit (discharge, suction valves and pressure controls are installed)
Liquid Filter
Liquid Indicator
WARNING
Do not use a ground fault interrupter (GFI).A
dedicated circuit is required.

-16-
Parts not included:
Liquid line copper tubing
Suction line copper tubing
CAUTION
Liquid and suction line locations may differ from that they areshown
below, please check on the units for proper installations.
NOTE
To prepare rough-in, leave minimum 4” clearances for electrical
wiring and refrigeration piping.
Model No.
Evap Unit
W” x D” x H”-
A”xB”
Cond Unit
L” x W” x
H”
Electrical Rating
Evap Unit / Cond
Unit
Min Circuit
Ampacity
Weight (lb) Evap
Unit / Cond Unit
WM-
2520SSL
WM-252SFCL
31.75 x 14.5 x
4.75-
29.75 x 14.75
WM-
252SCUR18
x 14 x 12
220V-50Hz-.2A
220V-50Hz-3A
10A
29 / 40
WM-
2520SSL-LA
WM-252SFCL
31.75 x 14.5 x
4.75-
29.75 x 14.75
WM-
252SCUR-
LA
18 x 14 x 12
220V-50Hz-.2A
220V-50Hz-3.5A
10A
29 / 40
WM-
4520SSL
WM-452SFCL
40.25 x 14.5 x
4.75-
38.25 x 14.75
WM-
452SCUR18
x 14 x 12
220V-50Hz-.4A
220V-50Hz-3.5A
10A
37 / 60
WM-
4520SSL-LA
WM-452SFCL
40.25 x 14.5 x
4.75-
38.25 x 14.75
WM-
452SCUR-
LA
18 x 14 x 12
220V-50Hz-.4A
220V-50Hz-4A
10A
37 / 60
WM-
6520SSL
WM-652SFCL
53.75 x 16.5 x
6.75-
51.75 x 16.75
WM-
652SCUR24
x 18 x 18
220V-50Hz-.4A
220V-50Hz-6A
15A
61 / 90
WM-
6520SSL-LA
WM-652SFCL
53.75 x 16.5 x
6.75-
51.75 x 16.75
WM-
652SCUR-
LA
24 x 18 x 18
220V-50Hz-.4A
220V-50Hz-6.5A
15A
61 / 90
WM-
8520SSL
WM-852SFCL
64.25 x 18.25 x 9-
53.25 x 19.3125
WM-
852SCUR24
x 18 x 18
220V-50Hz-.8A
220V-50Hz-7.5A
15A
80 / 115
WM-
8520SSL-LA
WM-852SFCL
64.25 x 18.25 x 9-
53.25 x 19.3125
WM-
852SCUR-
LA
24 x 18 x 18
220V-50Hz-.8A
220V-50Hz-8A
15A
80 / 115

-17-
Fig. 3 Temperature Controller (4.5”L X 4.5”W X 3.75H)

-18-
Fig. 4 WM-252SFCL Evaporator Unit
Fig. 5 WM-452~852SFCL Evaporator Unit

-19-
Fig. 6 WM-252~452SCUR Condensing Unit
Fig. 7 WM-652~852SCUR Condensing Unit
This manual suits for next models
7
Table of contents
Other Vinotemp Computer Hardware manuals