manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Visonic
  6. •
  7. Security Sensor
  8. •
  9. Visonic MCW-570 User manual

Visonic MCW-570 User manual

D-300767 1
MCW-570
Automatic Flood Prevention System
Installation Instructions
1. INTRODUCTION
1.1 Purpose and Use
The MCW-570 is a fully supervised flood prevention system. It is triggered
by up to 10 flood detectors that are located inside the protected site
where presence of water flooding or leakage is probable.
Upon cold/hot water flood detection, the system automatically shuts off
the water supply to the protected site (by means of 1 or 2 cold/hot electro-
mechanical ball valves) and provides valve status indication, on the
Control Unit and on the water valve(s).
Turning ON the water supply, after repairing the water leak, is performed
by pressing the OPEN button - see figure 1.
Manual turning OFF the electro-mechanical ball valve is also possible, by
pressing the CLOSE button - see figure 1.
In case of power failure, it is possible, on some models, to manually
open/close the valve (see Fig. 8).
Optional - In addition to flood preventing, the system can also send ALARM,
TROUBLE and LOW BATTERY signals to a remote control unit for remote
indication (see figure 7).
Up to 10 detectors
Flood
Sensor
WATER
MCT-550
Flood detector
WATER
Flood
Sensor
Close
button Open
button
CONTROL UNIT
CLOSED LED
(red)
READY LED
(green)
MCT-550
Flood detector
Alarm, trouble and
low battery signals
to a remote
control panel
(option)
(see spec.)
1 or 2 cold/hot
Electro-mechanical
ball valves
Figure 1 - Typical System Application
1.2 Kit Contents
The MCW-570 system includes the following (see figure 1):
a. One Control Unit: In case of flood, the Control Unit receives signal
from up to 10 wireless water flood detectors, sends OFF command to
the water electro-mechanical valve(s) and provides indication of the
closed valve(s).
b. One wireless flood detector MCT-550: The flood detector transmits
an alarm signal to the Control Unit upon flood detection.
c. One cold water electro-mechanical ball valve: The electro-
mechanical ball valve is directly installed on pipe of central water
supply. The valve automatically turns OFF the water supply in case of
flood detection.
d. One power transformer - 9VAC output.
Note: The system is designed for use with water valves that are supplied
by the system manufacturer only.
1.3 LEDs Operation
The Control Unit includes 2 main LED indicators (see Fig. 1), that function
according to the following table:
Valve Status Red LED Green LED
Power-up High frequency
flashing High frequency
flashing
Opened (no flood) Does not light Lights
Closed Lights Lights
During opening / closing High frequency
flashing Lights
Opened manually (override) by
user although flood still exists Low frequency
flashing Lights
The Control Unit includes 2 additional LED indicators (in the receiver module -
see Fig. 6), that are visible only after removal of the Control Unit cover:
•Red SIGNAL / MEMORY STATUS LED - illuminates as long as the
receiver receives signal from recognized flood detector. This LED is
also used during the flood detectors “learning” process (described
in par. 3.3).
•Yellow MEMORY LOCATION STATUS LED indicator - used during
the “learning” process.
2. SPECIFICATIONS
2.1 Control Unit Specifications
RF SECTION
Front-End Module: Super-regenerative UHF receiver.
Operating Frequency (MHz): 315, 433, 868.95 or other frequency
according to local requirements in country of use .
DATA PROCESSING SECTION
ID codes: Over 16,000,000 possible 24-bit combinations
Total Message Length: 36 bits
ID Learning Capacity: Up to 10 different ID codes
ELECTRICAL DATA
Input Voltage (according to the electronic module type and cold water
valve diameter): Valve diameter
Electronic Module Cat. # Cold water Hot water Input Voltage
E-200856 3/4' or 1" 1/2" 9V / 0.35A Min.
E-202355 1-1/4" - 12VAC / 1A Min.
Current Drain @9VAC: Standby - 30 mA. During 2 valves
closing/opening process only - up to 200 mA.
Relay Outputs: Form 1C (N.C. and N.O.)
Relay Contact Ratings: 1A resistive, 30 VDC or AC.
Status Outputs: 2, up to 100 mA each, open-collector type
ELECTRO-MECHANICAL BALL VALVE
Max water pressure: 8 Bar
Valve Diameter for Hot Water: 1/2"
Valve Diameter for Cold Water: 3/4", 1" or 1-1/4".
Valve closing Time: 5-11 seconds
PHYSICAL
Operating Temperatures: 0˚C to 49˚C (32˚F to 120˚F)
Control Unit Dimensions (HxWxD): 108x165x38 mm (4-1/4x6-1/2x1-1/2”).
Weight: Control Unit - 217 g (7.6 oz.), 3/4" WATER VALVE - 345g (12
oz.), 1" WATER VALVE - 526g (18 oz.), 1-1/4" WATER VALVE 1.6Kg
(3-1/2 Lb), AC ADAPTER - 200g (7 oz.).
Control Unit Color: Off white
COMPLIANCE WITH STANDARDS
EN13564-1, EN13564-2, EN60950, EN300220, EN301489
2.2 Flood Detector MCT-550 Specifications
TRANSMITTER
Frequency (MHz): 315, 433, 868.95 or other frequency according to local
requirements in country of use
Transmitter's ID Code: 24-bit digital word, over 16 million combinations,
pulse width modulation.
Overall Message Length: 36 bits
Message Repetition: One-shot transmission (default) or once every 3
minutes (selectable).
Supervision: Signaling at 60-minute intervals (U.S. version) or 15 minute
interval (UK version), or according to the local standards.
Response to Tamper Event: Tamper report every 3 minutes (until the
tamper switch is restored).
ELECTRICAL DATA
Power Source: 3V Lithium battery, Panasonic type CR-2 or equivalent.
Note: Dispose of used battery according the manufacturer's instructions.
Nominal Battery Capacity: 750 mAh
Current Drain: 6µA STBY, 17mA average in operation (including LED).
Battery Life with LED on: 3 years (for typical use)
Battery Supervision: Automatic reporting of battery condition data as
part of any transmission.
ALARM REPORT:
Every 20 sec. for the first 3 minutes. Every 3 min. for the next 27 minutes.
Alarm stops reporting after 30 min., or if the detector goes into "alarm restore".
Length of Flood Sensor Cable: 3 meters (10 ft)
2 D-300767
PHYSICAL DATA
Weight of Flood Sensor Cable: Approx. 60 gr.
Operating Temperature: 0°C to 49°C (32°F to 120°F).
Dimensions: 81 x 22 x 23.5 mm (3-3/16 x 7/8 x 15/16 in.).
Weight (including battery, without cable): 45 g (1.6 oz)
Standards: Meets FCC Part 15, Directive 1999/5/EC and EN 50131-1
Grade 2, Class II
This device complies with Part 15 of the FCC Rules and RSS 210 of Industry
and Science Canada. Operation is subject to the following two conditions: (1)
This device may not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause undesired
operation.
This device complies with the essential requirements and provisions of Directive
1999/5/EC of the European Parliament and of the Council of 9 March 1999 on
radio and telecommunications terminal equipment.
3. FLOOD DETECTORS ENROLLING IN THE CONTROL UNIT MEMORY
Note: The system is supplied with 1 flood detector whose enrolling
process was already performed by the manufacturer. If the system will
include 1 flood detector only, proceed to chapter 4. If more detectors will
be used, proceed to paragraph 3.1 to "teach" the system to identify the
additional detectors.
3.1 Helpful Tips
A learning session is required to let the Control Unit learn the ID codes of
individual wireless flood detectors that will control the electro-mechanical
water valve.
The quickest way to conduct a learning session is on the work bench,
where every required flood detector is within reach, and where you may
observe the Control Unit indication LEDs.
3.2 Initial Steps
A. Remove Control Unit cover (see figure 5 steps 1 & 2).
B. Temporarily power up the Control Unit by using the supplied 9VAC
adapter.
C. Open the flood detector and insert battery (see figure 3).
3.3 Learning Flood Detector IDs
A single transmission (Flood alarm, Tamper or Restore) is required
to enroll a flood detector’s ID in the Control Unit memory.
For “teaching” flood detector IDs into the receiver memory, proceed as
follows:
A. Set the OPERATE / LEARN jumper (see Fig. 6) to
LEARN as shown at the right. The yellow LED (see
Fig. 6) will start flashing at a constant rate.
Description of Yellow LED (Memory Location) Indications
The flood detectors identification, in the receiver module memory, is
divided into 10 locations, one per each flood detector ID. Memory
locations may be selected in ascending order from 1 to 10, by clicking the
receiver module tamper switch (see Fig. 6).
The yellow LED (see figure 6) indicates which memory location is
selected. The information is conveyed by flashing sequences as
demonstrated in the following chart:
No. of
Clicks Mem.
Loc.
Flashing Sequence of the Yellow LED
One 1st ——.......
Two 2nd ——......
Three 3rd — — ......
Four 4th — — ......
Five 5th — —
............ and so on, until the tenth click
= Flash; —= Pause
B. Click the receiver tamper switch (see figure 6) the correct number of
times (1 - 10) to select the desired memory location. Each click of the
tamper switch advances to the next memory location according to the
above table. The SIGNAL / MEMORY STATUS LED (red, see Fig. 6)
will show the status of the selected location as follows:
Memory Status Red LED Response
Location is free LED Flashes
Location already contains an ID LED Lights steadily
C. If the memory status is free (as shown in the above table) initiate a
transmission from the flood detector you wish to enroll in the selected
location, by inserting battery into the flood detector or (if it's battery
was already inserted) click the flood detector tamper switch (see
figure 6).
Two kinds of response may be expected:
Red LED Response (Fig. 6) Significance
Lights steadily flood detector ID enrolled
Continues to flash flood detector ID not enrolled
Note: You can not enroll a flood detector in a busy location.
D. Repeat Steps B through C for all of the remaining flood detectors.
E. Caution: During the next action be careful not to touch the DELETE
button, otherwise the flood detector enrolling may be erased!
Quit the LEARN mode by setting the OPERATE /
LEARN jumper back to OPERATE, as shown at the
right.
CAUTION! While handling the jumper, take care not to touch the
TOGGLE/PULSE jumper and DELETE button located close to the
jumper. Verify that the TOGGLE/PULSE jumper is in PULSE position!
Note
If you leave the jumper in the LEARN position and no further learning
activity takes place for 5 minutes, the LEARN mode will be automatically
abandoned.
3.4 Clearing Flood Detector IDs
A. Set the OPERATE/LEARN jumper to LEARN position. The internal yellow
LED (see Fig. 6) will start flashing at a constant rate.
B. Click the receiver tamper switch (see Fig. 6) the correct number of
times (up to 10) to select the desired memory location (see Para. 3.3).
The red LED (see Fig. 6) will show the status of the selected location
as follows:
Status Red LED Response
Memory location is free LED Flashes
Memory location already contains an ID LED lights steadily
C. Click the DELETE pushbutton (see Fig. 6) once. The red LED (see Fig.
6) will respond as follows:
Red LED Response Significance
Flashes at a constant rate Success (ID deleted)
Continues to light steadily Failure
D. When done, quit the LEARN mode by setting the OPERATE/ LEARN
jumper back to OPERATE.
3.5 What if the ID is Not Enrolled?
If the flood detector ID has not been accepted even though the memory
location is free (the red LED continues to flash), try transmitting again. If
the second attempt is unsuccessful, the flood detector in question may be
faulty. Try enrolling another flood detector.
4. FLOOD DETECTOR AND FLOOD SENSOR INSTALLATION
4.1 Flood Sensor Installation
a. locate the flood sensor on the wall, near the floor, according to the
required height. The recommended height is 0-3 cm from the floor.
b. Fasten the sensors' cable to the wall with 3 clamps. The first clamp
should be very close to the sensor and the other 2 clamps as desired.
Note: To protect the cable from rats, it is recommended that the cable will
be inside a plastic/iron tube.
4.2 MCT-550 Flood Detector Installation
The detector must be installed vertically (see figure 2) and fastened to the
wall as high as possible, to improve the radio communication and prevent
contact with water in case of flood. The installation process is shown in
figure 3. Countersunk head screws should be used to prevent short circuit
in printed circuit.
D-300767 3
4.3 Connection of flood Sensor's cable
to the Flood Detector
Connect the 2 sensor's wires to the AUX terminals of the MCT-560 flood
detector (see figure 4). Either one of the wires may be connected to either
terminal.
4.4 Detector Closure
Close the detector (refer to figure 3).
Note:
Flood sensor height
according to required flood
detection. Recommended 0-3cm
from floor.
FLOOD
DETECTOR
FLOOD
SENSOR
CABLE
2 - 3 m
(recommended
length)
WATER
FLOOD
SENSOR
Figure 2
Flood Sensor Installation
2
4
3
1
Remove
screw
Press the flexible
catch and remove
the printed circuit
Mark and drill 2 holes in mounting
surface and fix the base to the wall
with 2 countersunk head screws
Separate
the base
Figure 3
Flood Detector Installation
FUNCTION SELECTOR
TRANSMITTER
RF MODULE
TAMPER
SWITCH
AUX. INPUT
TERMINALS
3
V
LITHIUM
B
A
TTERY
LED
FLEXIBLE
RET
A
INER P.C.
BO
A
RD
SUPPORTS
WIRES TO FLOOD
SENSOR
Figure 4 - Flood Detector Printed Circuit Board
Note regarding flood detector internal function selector
The flood detector has 4 internal switches (see Fig. 4):
SW1 and SW2: These switches must be always in OFF (as set
by the manufacturer).
SW3: If the detector will be used only with MCW-570, the position
of this switch is not important. If the detector will be used with
other systems (e.g. PowerMax), this switch enables (ON) or
disables (OFF) event end reporting.
SW4: This switch is not used.
5. CONTROL UNIT INSTALLATION
5.1 Installation Location
The Control Unit, the flood detectors and the flood sensors are designed
for installation inside the house only. The electro-mechanical water
valve(s) should be installed on the site main water pipe.
5.2 Control Unit Installation (see figure 5)
Before installation, disconnect the power that was connected to the
Control Unit during the enrolling process. Install the Control Unit as shown
in figure 5, step 3. at height of at least 1.2m.
Snap-in
tooth
(1 of 2)
Base
Cover
CLOSED LED (red)
READY LED (green)
Remove
screw
Push near the 2
snap-in teeth to
remove the cover
2
1
Wire
antenna
Close cover
and fasten
with screw
4
3
Hold the base on mounting
surface, mark and drill 2
holes in mounting surface,
insert wall anchors if
necessay and enter wires
into the base through the
wiring holes or wiring
knockouts. Attach the base
to the mounting surface with
two screws.
Figure 5 - Control Unit Mounting
5.3 Electro-mechanical Valve Installation
The water valve(s) must be installed by a qualified plumber in the site
main water pipe.
Caution: The water valve(s) must be installed in addition to the existing
water valve and not instead of it!
5.4 Power Connection
Connect the AC adaptor output (9VAC), that is supplied with the system,
to the "PWR" terminals (see figure 6) - disregard the polarity.
RELAY
N.C.N.O. C
9VAC Water
valve
A
Water
valve
B
Closed
LED
(red)
Ready
LED
(green)
CONTROL
MODULE
RECEIVER
MODULE
Signal / memory
status red LED
Memory
location
yellow
LED
Delete
button
Tamper
switch
Close
button Open
button
operate
learn
toggle
pulse
Jumpers
Figure. 6 - Power Connection
5.5 One Water Valve Wiring
Connect the water valve cable to VALVE A or VALVE B connector (see
Fig. 6).
5.6 Two Water Valves Wiring
Connect the cable of one valve to VALVE A connector and the cable of
the other valve to VALVE B connector.
5.7 Remote control Panel Wiring (option)
Perform wiring as shown in figure 7.
RELAY
N.C.
N.O. C
FLOOD
ZONE
GND TRANSMITTER
INACTIVITY
INPUT
OPTIONAL REMOTE CONTROL PANEL
LOW
BAT
INPUT
+Vcc
18Ω18Ω
+Vcc Notes
The ZONE INPUT is
activated when flood occurs.
The TRANSMITTER
INACTIVITY INPUT is
activated if a supervised flood
detector fails to send its
attendance message within
a 4-8 hours time frame.
The LOW BAT INPUT is
activated whenever a low
battery message is received
from one of the flood
detectors.
RELAY
N.C.N.O.C
MCW-570
CONTROL
UNIT
Figure 7 - Optional Remote Control Panel Wiring
5.8 Final Actions
Carefully close the front panel of the control panel, straighten the antenna wire
and tighten the front panel with the screw (see figure 5).
4 D-300767
6. SYSTEM FUNCTIONAL TEST
6.1 Valve(s) Manual Closing/Opening Test
A. Valve(s) Manual Closing Test
1. Press the CLOSE button (see figure 6).
2. Verify that the water valve(s) will be closed within few seconds, during
which the red CLOSED LED (see figure 1) will flash. At the end of the
closing process, the red CLOSED LED will constantly light and the
valve(s) status indicator (see figure 8) should indicate "closed".
B. Valve(s) Manual Opening Test
1. Press the OPEN button (see Fig. 6).
2. Verify that the water valve(s) will be open within few seconds, during
which the red CLOSED LED (see figure 1) will flash. At the end of the
opening process, the red CLOSED LED will not light and the valve(s)
status indicator (see figure 8) should indicate "open".
6.2 Valve(s) Automatic Closing Test
1. Thoroughly clean the flood detectors' sensors (see figure 1) with a rag
and Immerse them in water (for example, by using a glass of water) and
verify that the water valve(s) will be closed within few seconds. During the
closing process, the red CLOSED LED (see Fig. 1) will flash.
At the end of the closing process, the red CLOSED LED will light
steadily and the valve(s) status indicator (see Fig. 8) should indicate
"closed".
2. Press the OPEN button (see Fig. 6), and verify that the water supply is
restored.
3. Perform steps 1 and 2 for every system's flood sensor.
Figure 8 - Water Valve Status Indication
7. MAINTENANCE
System functional test must be performed every 3 months at least,
including thorough cleaning of the flood sensors, according to section 6. After the test turn the valve(s) to OPEN position (see par. 6.2.B).
8. SPECIAL NOTES
Although this system is a highly reliable system, it does not guarantee complete
protection against flood. Even the most sophisticated systems can sometimes
be defeated or may fail because of:
A. Incorrect or improperly connected power supply.
B. The ambient temperature of the protected site is outside the range
specified in the SPECIFICATION section.
C. Even the most reliable electrical systems, including this system, may go
wrong because of an unexpected failure of a component part and may
cause closing or opening of the water valve(s).
D. When the electric power fails, it is impossible to close/open the water
valve(s).
A protection system should not be regarded as a substitute for insurance.
Home and property owners or renters should be prudent enough to continue
insuring their lives and property, even though they are protected by the flood
protection system.
Due to low transmitting power and limited range (required by FCC and other
regulatory authorities), there are some limitations to be considered:
A. Receivers may be blocked by radio signals occurring on or near their
operating frequencies.
B. Wireless equipment should be tested regularly to determine whether there are
sources of interference and to protect against faults.
The user is cautioned that changes or modifications to the unit, not
expressly approved by Visonic Ltd., could void the user's FCC authority
to operate the equipment.
This device has been designed to comply with the European Council Directive
EMC 89/336/EEC & 92/31/EEC and bears the CE mark and certification.
This device has been designed to comply with the limits for a Class B digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in residential
installations. This equipment generates uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may
cause harmful interference to radio and television reception. However, there is
no guarantee that interference will not occur in a particular installation. If this
device does cause such interference, which can be verified by turning the
device off and on, the user is encouraged to eliminate the interference by one
or more of the following measures:
– Re-orient or re-locate the receiving antenna.
– Increase the distance between the device and the receiver.
– Connect the device to an outlet on a circuit different from the one which
supplies power to the receiver.
– Consult the dealer or an experienced radio/TV technician.
WARRANTY
Visonic Limited (the “Manufacturer") warrants this product only (the "Product") to the original
purchaser only (the “Purchaser”) against defective workmanship and materials under normal use of
the Product for a period of twelve (12) months from the date of shipment by the Manufacturer.
This Warranty is absolutely conditional upon the Product having been properly installed, maintained
and operated under conditions of normal use in accordance with the Manufacturers recommended
installation and operation instructions. Products which have become defective for any other reason,
according to the Manufacturers discretion, such as improper installation, failure to follow
recommended installation and operational instructions, neglect, willful damage, misuse or vandalism,
accidental damage, alteration or tampering, or repair by anyone other than the manufacturer, are not
covered by this Warranty.
The Manufacturer does not represent that this Product may not be compromised and/or
circumvented or that the Product will prevent any death and/or personal injury and/or damage to
property resulting from burglary, robbery, fire or otherwise, or that the Product will in all cases
provide adequate warning or protection. The Product, properly installed and maintained, only
reduces the risk of such events without warning and it is not a guarantee or insurance that such
events will not occur.
THIS WARRANTY IS EXCLUSIVE AND EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES,
OBLIGATIONS OR LIABILITIES, WHETHER WRITTEN, ORAL, EXPRESS OR IMPLIED,
INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE, OR OTHERWISE. IN NO CASE SHALL THE MANUFACTURER BE LIABLE TO
ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS
WARRANTY OR ANY OTHER WARRANTIES WHATSOEVER, AS AFORESAID.
THE MANUFACTURER SHALL IN NO EVENT BE LIABLE FOR ANY SPECIAL, INDIRECT,
INCIDENTAL, CONSEQUENTIAL OR PUNITIVE DAMAGES OR FOR LOSS, DAMAGE, OR
EXPENSE, INCLUDING LOSS OF USE, PROFITS, REVENUE, OR GOODWILL, DIRECTLY OR
INDIRECTLY ARISING FROM PURCHASER’S USE OR INABILITY TO USE THE PRODUCT, OR
FOR LOSS OR DESTRUCTION OF OTHER PROPERTY OR FROM ANY OTHER CAUSE, EVEN
IF MANUFACTURER HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
THE MANUFACTURER SHALL HAVE NO LIABILITY FOR ANY DEATH, PERSONAL AND/OR
BODILY INJURY AND/OR DAMAGE TO PROPERTY OR OTHER LOSS WHETHER DIRECT,
INDIRECT, INCIDENTAL, CONSEQUENTIAL OR OTHERWISE, BASED ON A CLAIM THAT THE
PRODUCT FAILED TO FUNCTION.
However, if the Manufacturer is held liable, whether directly or indirectly, for any loss or damage
arising under this limited warranty, the Manufacturer's maximum liability (if any) shall not in any case
exceed the purchase price of the Product, which shall be fixed as liquidated damages and not as a
penalty, and shall be the complete and exclusive remedy against the Manufacturer.
When accepting the delivery of the Product, the Purchaser agrees to the said conditions of sale and
warranty and he recognizes having been informed of.
Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages, so
these limitations may not apply under certain circumstances.
The Manufacturer shall be under no liability whatsoever arising out of the corruption and/or
malfunctioning of any telecommunication or electronic equipment or any programs.
The Manufacturers obligations under this Warranty are limited solely to repair and/or replace at the
Manufacturer’s discretion any Product or part thereof that may prove defective. Any repair and/or
replacement shall not extend the original Warranty period. The Manufacturer shall not be
responsible for dismantling and/or reinstallation costs. To exercise this Warranty the Product must
be returned to the Manufacturer freight pre-paid and insured. All freight and insurance costs are the
responsibility of the Purchaser and are not included in this Warranty.
This warranty shall not be modified, varied or extended, and the Manufacturer does not authorize
any person to act on its behalf in the modification, variation or extension of this warranty. This
warranty shall apply to the Product only. All products, accessories or attachments of others used in
conjunction with the Product, including batteries, shall be covered solely by their own warranty, if
any. The Manufacturer shall not be liable for any damage or loss whatsoever, whether directly,
indirectly, incidentally, consequentially or otherwise, caused by the malfunction of the Product due to
products, accessories, or attachments of others, including batteries, used in conjunction with the
Products. This Warranty is exclusive to the original Purchaser and is not assignable.
This Warranty is in addition to and does not affect your legal rights. Any provision in this warranty
which is contrary to the Law in the state or country were the Product is supplied shall not apply.
Warning: The user must follow the Manufacturer’s installation and operational instructions including
testing the Product and its whole system at least once a week and to take all necessary precautions
for his/her safety and the protection of his/her property. 1/08
W.E.E.E. Product Recycling Declaration
For information regarding the recycling of this product you must contact the company from which you orignially purchased it. If you are discarding this product and not
returning it for repair then you must ensure that it is returned as identified by your supplier. This product is not to be thrown away with everyday waste.
Directive 2002/96/EC Waste Electrical and Electronic Equipment.
VISONIC LTD. (ISRAEL): P.O.B 22020 TEL-AVIV 61220 ISRAEL. PHONE: (972-3) 645-6789, FAX: (972-3) 645-6788
VISONIC INC. (U.S.A.): 65 WEST DUDLEY TOWN ROAD, BLOOMFIELD CT. 06002-1376. PHONE: (860) 243-0833, (800) 223-0020. FAX: (860) 242-8094
VISONIC LTD. (UK): 7 COPPERHOUSE COURT, CALDECOTTE, MILTON KEYNES. MK7 8NL. PHONE: (0870) 7300800 FAX: (0870) 7300801
PRODUCT SUPPORT ( 0870) 7300830
INTERNET: www.visonic.com
©VISONIC LTD. 2008 MCW-570 Installation Instructions D-300767 (REV. 4, 11/08)
Open
Optional knob
Pull out and
rotate for
manual open /
close
Closed

Other Visonic Security Sensor manuals

Visonic CLIP SMA User manual

Visonic

Visonic CLIP SMA User manual

Visonic CLIP SMA User manual

Visonic

Visonic CLIP SMA User manual

Visonic TOWER 10 AM - User manual

Visonic

Visonic TOWER 10 AM - User manual

Visonic DISCOVERY K9-80 MCW - INSTALLER GUIDE User manual

Visonic

Visonic DISCOVERY K9-80 MCW - INSTALLER GUIDE User manual

Visonic MP-802 K9-85 PG2 User manual

Visonic

Visonic MP-802 K9-85 PG2 User manual

Visonic SRN-2000W/PCN User manual

Visonic

Visonic SRN-2000W/PCN User manual

Visonic MCT-560 User manual

Visonic

Visonic MCT-560 User manual

Visonic MCW User manual

Visonic

Visonic MCW User manual

Visonic DUO 240 User manual

Visonic

Visonic DUO 240 User manual

Visonic MP-802 K9-85 PG2 User manual

Visonic

Visonic MP-802 K9-85 PG2 User manual

Visonic DISCOVERY K9-80 User manual

Visonic

Visonic DISCOVERY K9-80 User manual

Visonic POWERMAX - User manual

Visonic

Visonic POWERMAX - User manual

Visonic MCT-550 User manual

Visonic

Visonic MCT-550 User manual

Visonic NEXT PLUS PIR / K9-85 User manual

Visonic

Visonic NEXT PLUS PIR / K9-85 User manual

Visonic MCT-441 User manual

Visonic

Visonic MCT-441 User manual

Visonic Logica User manual

Visonic

Visonic Logica User manual

Visonic NEXT K9-85 PG2 User manual

Visonic

Visonic NEXT K9-85 PG2 User manual

Visonic MP-841 User manual

Visonic

Visonic MP-841 User manual

Visonic SRN-2000 User manual

Visonic

Visonic SRN-2000 User manual

Visonic CLIP PG2 User manual

Visonic

Visonic CLIP PG2 User manual

Visonic SPD-1000 User manual

Visonic

Visonic SPD-1000 User manual

Visonic DISC MCW User manual

Visonic

Visonic DISC MCW User manual

Visonic NEXT CAM PG2 User manual

Visonic

Visonic NEXT CAM PG2 User manual

Visonic MP-840 User manual

Visonic

Visonic MP-840 User manual

Popular Security Sensor manuals by other brands

Satel ADD-200 user manual

Satel

Satel ADD-200 user manual

General Monitors FL3102 instruction manual

General Monitors

General Monitors FL3102 instruction manual

Axiometrix Solutions imc CLSx manual

Axiometrix Solutions

Axiometrix Solutions imc CLSx manual

AJAX DoorProtect quick start guide

AJAX

AJAX DoorProtect quick start guide

Respirex GLS 300 A User instructions

Respirex

Respirex GLS 300 A User instructions

WATERGUARD Solo installation guide

WATERGUARD

WATERGUARD Solo installation guide

Niko 25421 quick start guide

Niko

Niko 25421 quick start guide

Dingtek DF703 datasheet

Dingtek

Dingtek DF703 datasheet

ELTEX UPG-Stitch instructions

ELTEX

ELTEX UPG-Stitch instructions

Kanlux SENTO quick start guide

Kanlux

Kanlux SENTO quick start guide

Elenco Electronics AK-510 Assembly and instruction manual

Elenco Electronics

Elenco Electronics AK-510 Assembly and instruction manual

Honeywell 5800COMBO Installation and setup guide

Honeywell

Honeywell 5800COMBO Installation and setup guide

Sensit HXG-2d instruction manual

Sensit

Sensit HXG-2d instruction manual

Satel AGD-200-BR user manual

Satel

Satel AGD-200-BR user manual

Smartenit ZBMS3 quick start guide

Smartenit

Smartenit ZBMS3 quick start guide

Niko 350-20071 manual

Niko

Niko 350-20071 manual

PCE Health and Fitness PCE-LDC 8 user manual

PCE Health and Fitness

PCE Health and Fitness PCE-LDC 8 user manual

Manostar EMD8A066 instruction manual

Manostar

Manostar EMD8A066 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.