Von Duprin PS914 User manual

1 of 4
These instructions cover the following parts:
Installation
Instructions
PS914 Power Supply
© 2010 Ingersoll-Rand Company
1-877-671-7011
44487056 Rev. 10/10_a
44487056
To avoid risk of electric shock, turn off AC power
before installing or servicing PS914 power supply.
DANGER:
!
PS914 Power Supply Specifications:
Input 120/240 VAC, 1.4 A, 50/60Hz, High Voltage Class 1 Wiring Required
Output 4 Amp DC @ 12/24 VDC
May be used to power Von Duprin & Falcon EL device at 24VDC, 16A, 300ms
Enclosure 14” H x 12” W x 4” D (8 knockouts, 1/2” or 3/4” )
Temperature Range 32°-120° F (0°- 49° C)
Fuse F1, T6.3A
250 VAC
Compliance UL 294, ULC-S318, RoHS, & FCC Part 15, Class 2 Output
Compatible Boards
(Optional, 2 boards maximum)
900-2RS
900-2Q
900-4R
900-4RL
900-8F
900-8P
Fire Alarm Input Board (Optional) 900-FA (Requires one option board above)
Battery Backup Board (Optional) 900-BB
AC Monitor Output Form C Contacts, 30 VDC, 1 Amp, Resistive Load
For protection against risk of fire, replace fuse with same type and rating
CAUTION:
!
INST. INSTRUCTIONS - 44487056
INST. INSTRUCTIONS - 44487098
INST. INSTRUCTIONS - 44487106
INST. INSTRUCTIONS - 44487080
INST. INSTRUCTIONS - 44487106
INST. INSTRUCTIONS - 44487106
INST. INSTRUCTIONS - 44487072
INST. INSTRUCTIONS - 44487064
Inputs I1,I2 Dry contacts required (Closed = Active)
Connect control contacts between SC (Signal Common) and any input
Outputs O1,O2 • 12/24VDC, 3A (wet) when AC powered • 9.6-13.2VDC or 19.2-26.4VDC when battery powered
• May be used with PS914 to power EL device at 24VDC, 16A, 300ms
• Maximum load cannot exceed power supply ratings or 3A for outputs combined
Board Input Power Board requires 0.1A max. of power supply output current to operate
Temperature Range 32°-120° F (0°- 49° C)
Compliance UL 294, ULC-S318, RoHS, & FCC Part 15
Fire Alarm Input Accepts 900-FA Fire Alarm Board (Optional)
900-2RS Specifications:
900-BB Battery Backup
(optional)
Page 3
900-2RS (optional) - Page 4
(2 Zone EL Control -
Individual/Sequential)
900-KL Keylock
(optional)
Page 2
PS914 Power Supply
Pages 1-3
F1
DANGER
!
!
DANGER:
!
WARNING:
!
WARNING:

2 of 4
1 MOUNT POWER SUPPLY
1a Mark 2 Top Holes 1b Secure Enclosure with 4 Screws
MOUNTING NOTES
The PS914 must be installed in accordance with the article 760 of the National Electrical Code or NFPA 72,
Canadian Electrical Code, or any other applicable codes.
Install the PS914 indoors within the protected premises.
Check national and local codes for additional installation requirements.
Enclosure must be firmly mounted to a solid surface using hardware suitable for the surface.
xx
2 SECURE ENCLOSURE DOOR
If No Keylock
Enclosure will be secured with 2 screws
as shown (done as last step)
If Keylock
Remove knockout and insert key cylinder, then slide in clip
ab
OR
Board not shown
for clarity

3 of 4
3 PS914 SETUP AND TESTING
F1
DC Output
(Red LED)
12/24 VDC
Output Terminals
AC Input
(Green LED)
AC Monitor
Active when AC
present and F1
fuse not open
(Form C dry
contacts)
NC C NO
24
12
900-BB Connector
If AC LED is off, turn off AC breaker
prior to checking F1 fuse
!DANGER:
High Voltage
If main board must be
removed, turn off AC power
and wait 8minutes before
removal
Do not remove this cover, no
serviceable parts
DANGER
!
3a Connect AC Wiring
NEU
LINE
Green (Ground)
White (Neutral)
Black (Hot)
AC (In)
120/240
VAC
AC Input
Use Jumper to SelectUse Jumper to Select
24 VDC or 12 VDC Output
3b
!DANGER:
Ensure AC
Breaker is
Turned Off
OR
12 VDC
Output Setting
24 VDC
Output Setting
Minimum of 1/4” separation
between AC and DC wiring
as well as power limited and
non-power limited.
Note:
4 INSTALL 900-BB BATTERY BACKUP (IF INCLUDED)
4a Place Batteries in Box with
Terminals to the Left
4b Attach Wires from Battery Board
Red wires = (+)
Black wires = (-)
Note: Allow 24 hours for batteries to fully charge
Battery 1 Battery 2
Black Wires = (-)
+
+
BB LED
(Amber)
On-Solid
AC On
Batteries
Charging
On-Blinking
AC Off
Batteries
Supplying
Power
Battery Supervision Terminals
(Form C Dry Contacts)
Active
AC On
Inactive
AC Off
(Shown
AC Off)
NO
C
NC
Red Wires = (+)
Refer to 900-BB instructions
for additional info
5 TURN ON AC BREAKER TO TEST POWER SUPPLY
• Verify AC LED is On = GREEN
• Verify DC LED is On = RED
• Verify BB LED (if applicable) is On = AMBER

4 of 4
6 INSTALL 900-2RS OPTION BOARD (IF REQUIRED)
7 CONNECT WIRING TO 900-2RS OPTION BOARD
Sequential Mode - Typical Wiring
Input I1 will activate both outputs
Individual Mode - Typical Wiring
Input I1 will activate output 1
Input I2 will activate output 2
EL Device 2
(not polarized)
Access
Control
for Device 2
EPT-2/10
EL Device 1
(not polarized)
Access
Control
for Device 1
EPT-2/10
SC I1 01 I2 02 GND
2RS
120/240 VAC
50/60Hz
A
B
A
B
EL Device 1
(not polarized)
Access
Control
for
Devices 1 & 2
EPT-2/10
EL Device 2
(not polarized)
EPT-2/10
SC I1 01 I2 02 GND
2RS
120/240 VAC
50/60Hz
A
B
A
Note:
Fail secure output only
allowed if approved
by Authority Having
Jurisdiction
6a Use Jumper to SelectUse Jumper to Select
Function
OR
Sequential Individual
6b Plug 2RS Cable into any
Available Option Connector
6c Secure Board with Screws
Option 2
Option 1
12
If installing board in location 2, rotate board 180˚
Note: 24VDC output setting required when EL
device connected
!DANGER:
Ensure AC breaker is turned off when
installing or wiring option boards
NOTE: WHEN INSTALLATION IS
COMPLETE, SECURE ENCLOSURE
DOOR WITH SCREWS OR KEYLOCK
Wire Ga
(AWG)
Device Current
(Amps DC)
Output*
(max. ft)
Input
(max. ft)
14 0.3 850
0.5 500
18 0.3 340 1200
0.5 200
12 Using EL device with EPT or Door Loop
(PS914 required)
200
14 100
12 Using EL device with Electric Hinge/Pivot
(PS914 required)
150
14 75
Wire table (suggested maximum)
*Wiring allows for 10% voltage drop at device current at 12 or 24VDC
Max. ft = one way distance between power supply and device
IF PS-914 HAS OTHER OPTION BOARDS,
SEE THEIR INSTRUCTIONS
8

44487080
Installation
Instructions
900-4RL Option Board
900-4RL Specifications:
Inputs I1-I4 Dry contacts required (Closed = Active)
Connect control contacts between SC (Signal Common) and any input
Outputs O1-O4 • Form C contacts rated 30VDC, 3A (Dry) • 12/24VDC, 3A (Wet) when AC powered • 9.6-13.2VDC or
19.2-26.4VDC when battery powered • May be used with PS914 to power EL device at 24VDC, 16A,
300ms • Maximum load cannot exceed power supply ratings or 6A for outputs combined
Board Input Power Board requires 0.18A max. of power supply output current to operate
Temperature Range 32°-120°F (0°- 49° C)
Compliance UL 294, ULC-S318, RoHS, & FCC Part 15
Fire Alarm Input Accepts 900-FA Fire Alarm Board (Optional)
© 2010 Ingersoll-Rand Company
1-877-671-7011
44487080 Rev. 10/10_a
1 INSTALL 4RL BOARD(S) INTO POWER SUPPLY
1a Review Available 900-4RL
Mounting Locations (Gray)
PS902
PS904
PS914
PS906
1
12
2
3
1
1b Plug 4RL Cable into any
Available Option Connector
1c Secure Board(s) with Screws
Option 1
Option 2
Option 1
Option 3
Option 2
Option 1
PS902
PS904, 914
PS906
1
To avoid risk of electric shock, turn off AC power to
power supply before installing or wiring option board
DANGER:
!
Refer to installation instructions for compatible supply models - PS902, PS904,
PS906, and PS914.
Note:
For UL listed installations, use
only UL listed locks and strikes

2
1 2
1 2
1 2
ON
OFF
ON
OFF
ON
OFF
SW2
Function LED (D17)
SW1
1 2
OFF ON
2 CHOOSE FUNCTION OF 900-4RL BOARD BY SETTING SW2 DIP SWITCHES
3 TO COMPLETE CONFIGURATION AND WIRING, GO TO APPROPRIATE SECTION
4TD
AO
SI
Four Zone Controller Function (4TD):
Controls up to four inputs and four outputs with time delay.
This is the default setting.
Function LED will blink one time every 5 seconds
Auto Operator Function (AO):
Coordinates the unlocking of one or two zones with the
signaling of an auto operator.
Function LED will blink two times every 5 seconds
Security Interlock Function (SI):
Controls multi-door interlocks. Two through six door
systems are possible (additional boards required for three
to six doors).
Function LED will blink three times every 5 seconds
For 4TD: Go to pages 3-4
For AO: Go to pages 5-6
For SI: Go to pages 7-8
Basic Troubleshooting: Go to page 8
Powered Outputs
(Default)
Dry Contact Outputs
(Optional)
(OPTIONAL) DRY CONTACT CONFIGURATION
Output 2
Output 4
Output 3
Output 1
Output 2
Output 4
Output 3
Output 1
Jumpers factory
installed
Jumper
rotated 90˚
Zone 2
Zone 4
Zone 3
Zone 1
Zone 2
Zone 4
Zone 3
Zone 1
By default, all outputs provide12/24VDC For dry contact outputs, remove appropriate jumpers and
rotate 90˚, then reinstall (Zone 1 - Zone 4)

3
4TD - SET TIME DELAY USING SW1 DIP SWITCHES
SWITCH
NUMBER
4TD DIP SWITCH DEFINITIONS
All switches shown in “OFF” position in wiring diagram
Enable Time Delay
Allows you to choose which
outputs will have the below time delay.
1 Turn “ON” to enable time delay for Locking Device 1
2 Turn “ON” to enable time delay for Locking Device 2
3 Turn “ON” to enable time delay for Locking Device 3
4 Turn “ON” to enable time delay for Locking Device 4
Set Time Delay
(0-75 seconds, 5 second increments)
0 Sec: Switches 5-8 “OFF”
75 Sec: Switches 5-8 “ON”
5 Adds 5 seconds to the time delay when “ON”
6 Adds 10 seconds to the time delay when “ON”
7 Adds 20 seconds to the time delay when “ON”
8 Adds 40 seconds to the time delay when “ON”
DIP switches on SW1 can be turned “ON” by
moving them in the direction that the arrow is
pointing. Switches below shown in “OFF” position
Summary of Operation
• Output turns “ON” when input is activated (closed).
• Time delay begins when input is released (opened).
• Locking Device output will remain “ON” during time delay.
• If I1-I4 inputs are wired together, outputs will sequence.
SW1
1 2 3 4 5 6 7 8
ON
OFF
SW1 SW2
12345678 12
4TD INPUT / OUTPUT
TERMINAL BLOCK DEFINITIONS
Input 1 Access Control 1
Input 2 Access Control 2
Input 3 Access Control 3
Input 4 Access Control 4
Output 1* Lock 1
Output 2* Lock 2
Output 3* Lock 3
Output 4* Lock 4
*See page 2 for dry contacts

4
4TD - WIRING EXAMPLE - FAIL SECURE
4TD - WIRING EXAMPLE - FAIL SAFE
GND
NC2
C2
NO2
I2
NC1
C1
NO1
I1
SC
GND
NC4
C4
NO4
I4
NC3
C3
NO3
I3
SC
4RL
120/240 VAC
50/60Hz
Access
Control 2
EPT 2 or 10
EL Device 2
(not polarized)
Access
Control 1
EPT 2 or 10
EL Device 1
(not polarized)
PS914
x 4RL
Access
Control 4
EPT 2 or 10
EL Device 4
(not polarized)
Access
Control 3
EPT 2 or 10
EL Device 3
(not polarized)
Note:
To control EL1 & EL2 with Access Control 1, jumper I1-I2
To control EL1 - EL4 with Access Control 1, jumper I1-I2-I3-I4
0-100 ft, use 14 gauge stranded wire
0-200 ft, use 12 gauge stranded wire
Note:
Fail secure output only allowed if approved
by Authority Having Jurisdiction
GND
NC2
C2
NO2
I2
NC1
C1
NO1
I1
SC
GND
NC4
C4
NO4
I4
NC3
C3
NO3
I3
SC
4RL
120/240 VAC
50/60Hz
Access
Control 2
Mag Lock 2
Mag Lock 1
Access
Control 1
PS902
or
PS904
or
PS906
Access
Control 4
Mag Lock 4
Mag Lock 3
Access
Control 3
Note:
To control Mag Locks 1 & 2 with Access Control 1, jumper I1-I2
To control Mag Locks 1 - 4 with Access Control 1, jumper I1-I2-I3-I4
Refer to Wire Table
(page 7)

5
AO - SET CONFIGURATION USING SW1 SWITCHES
SW1 SWITCH
NUMBER
AO DIP SWITCH DEFINITIONS
All switches shown in “OFF” position in wiring diagram
Set Auto Operator Signaling Option
Determines when the auto operator signal will be active
1 Off
2 Off
Operator is signaled when latch monitor switch becomes active.
Monitor switch required
1 On
2 Off
Operator is signaled 0.5 seconds after control switch
becomes active. No monitor switch used.
1 Off
2 On
Operator is signaled 1.0 seconds after control switch
becomes active. No monitor switch used.
1 On
2 On
Operator is signaled 1.5 seconds after control switch
becomes active. No monitor switch used.
Not Used 3 Not used
Set Individual Mode or Sequential Mode
Individual Mode - One input will trigger one locking device.
Sequential Mode - One input will trigger two locking devices.
4 Turn “OFF” (default) to enable Individual Mode (single doors).
Turn “ON” to enable Sequential Mode (double doors).
Set Time Delay*
(0-30 seconds, 2 second increments)
0 Sec: Switches 5-8 “OFF”
30 Sec: Switches 5-8 “ON”
5 Adds 2 seconds to the time delay when “ON”
6 Adds 4 seconds to the time delay when “ON”
7 Adds 8 seconds to the time delay when “ON”
8 Adds 16 seconds to the time delay when “ON”
DIP switches on SW1 can be turned “ON” by
moving them in the direction that the arrow is
pointing. Switches below shown in “OFF” position
* Time Delay begins when an input is released.
SW1
1 2 3 4 5 6 7 8
ON
OFF
SW1
12345678 12
SW2
AO INPUT / OUTPUT
TERMINAL BLOCK DEFINITIONS
Input 1 Access Control 1
Input 2 Lock Monitor 1
Input 3 Access Control 2
Input 4 Lock Monitor 2
Output 1* Lock 1
Output 2* AO Signal 1
Output 3* Lock 2
Output 4* AO Signal 2
*See page 2 for dry contacts

6
GND
NC2
C2
NO2
I2
NC1
C1
NO1
I1
SC
GND
NC4
C4
NO4
I4
NC3
C3
NO3
I3
SC
4RL
120/240 VAC
50/60Hz
PS914
x 4RL
Access
Control
for Device 2
EL-LX Device 2
Auto Operator 2
EL
LX
(Optional)
EPT 10
Gray
White
Access
Control
for Device 1
EL-LX Device 1
Auto Operator 1
EL
LX
(Optional)
EPT 10
Gray
White
0-100 ft, use 14 gauge stranded wire
0-200 ft, use 12 gauge stranded wire
AO - WIRING EXAMPLE - TWO SINGLE DOORS
Summary of Operation
For each door, access control input unlocks door.
Latch monitor (LX) triggers auto operator.
Single Door Board Configuration
1. Position jumpers for dry contact for outputs 2 and 4
(see page 2).
2. Turn on switches 5 and 6 on SW1 (6 second time delay).
3. If LX is not used, turn on switch 1 on SW1.
AO - WIRING EXAMPLE - DOUBLE DOORS
Summary of Operation
Access control input unlocks both doors.
Both latch monitors (LX) trigger auto operators.
Double Door Board Configuration
1. Position jumpers for dry contact for outputs 2 and 4
(see page 2).
2. Turn on switches 4, 5, and 6 on SW1 (6 second
time delay).
3. If LX is not used, turn on switch 1
on SW1.
SW1 SW2
1 2 3 4 5 6 7 8
ON
OFF
1 2
SW1
1 2 3 4 5 6 7 8
ON
OFF
SW2
1 2
Access
Control
for Devices
1 & 2
EPT 10
EL-LX Device 1 EL-LX Device 2
Auto Operator Auto Operator
White
Gray
EL EL
EPT 10
GND
NC2
C2
NO2
I2
NC1
C1
NO1
I1
SC
GND
NC4
C4
NO4
I4
NC3
C3
NO3
I3
SC
4RL
120/240 VAC
50/60Hz
PS914
x 4RL
Gray
White
Second auto operator,
if needed
LX
(Optional)
LX
(Optional)
0-100 ft, use 14 gauge stranded wire
0-200 ft, use 12 gauge stranded wire
Note:
Fail secure output only
allowed if approved
by Authority Having
Jurisdiction
Refer to Wire Table
(page 7)

7
SI - CONFIGURE SW1 DIP SWITCHES
DIP switches on SW1 can be turned “ON” by
moving them in the direction that the arrow is
pointing. Switches below shown in “OFF” position
SW1
1 2 3 4 5 6 7 8
ON
OFF
SW1
12345678 12
SW2
SWITCH
NUMBER
SI DIP SWITCH DEFINITIONS
All switches shown in “OFF” position in wiring diagram
Enable Time Delay
Allows you to choose which
outputs will have the below time delay.
1 Turn “ON” to enable time delay for Locking Device 1
2 Turn “ON” to enable time delay for Locking Device 2
Enable Interlock
3 Turn “ON” to remove O2 from interlock (Allows a single independent door)
4 Turn “ON” for global interlock (interlocks with other SI boards that have this
switch “ON”)
Set Time Delay (Output Active)*
(0-30 seconds, 2 second increments)
0 Sec: Switches 5-8 “OFF”
30 Sec: Switches 5-8 “ON”
5 Adds 2 seconds to the time delay when “ON”
6 Adds 4 seconds to the time delay when “ON”
7 Adds 8 seconds to the time delay when “ON”
8 Adds 16 seconds to the time delay when “ON”
SI INPUT / OUTPUT
TERMINAL BLOCK DEFINITIONS
Input 1 Access Control 1
Input 2 Access Control 2
Input 3 Lock Monitor 1
Input 4 Lock Monitor 2
Output 1* Lock 1
Output 2* Lock 2
Output 3* Follows Output 1
by .5 Sec
Output 4* Follows Output 2
by .5 Sec
*See page 2 for dry contacts
GLOBAL INTERLOCK
SWITCH SETTING EXAMPLES
SI Board
#1
SI Board
#2
SI Board
#3
Application
SW1-3 SW1-4 SW1-3 SW1-4 SW1-3 SW1-4
Off Off Off Off Off Off Each SI board is a standalone,
2-door interlock.
Off On Off On Off On 6-door interlock by setting all
boards “global”.
Off On On On A three-door interlock, plus an
additional independent door
on output 2 of SI Board #2.
Off On Off On Off Off 4-Door interlock (SI Board
#1,2) and a standalone 2-door
interlock (SI Board #3).
Wire Ga
(AWG)
Device Current
(Amps DC)
Output*
(max. ft)
Input
(max. ft)
14 0.3 850
0.5 500
18 0.3 340 1200
0.5 200
12 Using EL device with EPT or Door Loop
(PS914 required)
200
14 100
12 Using EL device with Electric Hinge/Pivot
(PS914 required)
150
14 75
Wire table (suggested maximum)
*Wiring allows for 10% voltage drop
at device current at 12 or 24VDC
Max. ft = one way distance between
power supply and device

8
SI - WIRING EXAMPLE - 2 TO 6 DOOR INTERLOCK, NORMALLY LOCKED
GND
NC2
C2
NO2
I2
NC1
C1
NO1
I1
SC
GND
NC4
C4
NO4
I4
NC3
C3
NO3
I3
SC
4RL
120/240 VAC
50/60Hz
Access
Control 2
Mag Lock 2 Mag Lock 1
Access
Control 1
DPS 2
(contact shown
with door closed)
DPS 1
(contact shown
with door closed)
PS904
x 4RL
Note:
Fail secure output only allowed if approved
by Authority Having Jurisdiction
Refer to Wire Table
(page 7)
SI Configuration
1.Turn on switches 1, 2, 4, 5, and 6 on SW1.
2. Install 2 doors per SI board.
3. Add up to 2 additional SI boards for a total
of 6 door interlock per power supply:
PS902 (2 doors maximum)
PS904 (4 doors maximum)
PS906 (6 doors maximum)
1 2 3 4 5 6 7 8
ON
OFF
1 2
SW1 SW2
BASIC TROUBLESHOOTING FOR ALL FUNCTIONS
Symptom Check
900-4RL Function LED (yellow) is not
blinking, and inputs and outputs are
inactive
Verify 900-4RL cable is plugged into an “option” connector on the main board.
Check AC wiring and AC breaker.
Check PS-900 main board F1 fuse.
Use voltmeter to verify 12 VDC or 24 VDC output on PS-900 main board.
900-4RL Function LED (yellow) is
blinking, but inputs and outputs are
inactive
If 900-FA option is installed onto 900-4RL, verify fire alarm contacts are closed
across FA1 and FA2.
If 900-FA option is not installed, then verify jumper wire is installed into
FA-JMPR connector on the 4RL board.
Inputs and outputs behaving incorrectly. Verify 2-position DIP switch is set for proper function.
Watch yellow LED to confirm 4RL function setting .
See page 2. (Verify each DIP switch is pushed into its fully-on or fully-off
position.)
Verify 8-position DIP switch is set properly for your application. If you are unsure
of proper settings, contact Technical Services for assistance. (Verify each DIP
switch is pushed into its fully-on or fully-off position.)
Verify wiring for all input and output hardware is connected to proper terminals.
(Reminder: If 900-4RL is mounted in location 1, top terminals will be GND. If
900-4RL mounted in location 2 or 3, top terminals will be SC.)
NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS OR
KEYLOCK

Installation
Instructions
900-FA Fire Alarm Input
© 2010 Ingersoll-Rand Company
1-877-671-7011
44487072 Rev. 10/10_a
The 900-FA Fire Alarm board can be
installed on any one of the following
power supply or option boards
(refer to installation instructions):
(900-2RS
option board
shown)
• If 900-FA was factory installed, go to step 2
• If installing to option board, go to 1a
• If installing to PS902 main board, go to 1b
1a IF INSTALLING TO OPTION BOARD
44487072
900-2RS
(2 Relay)
PS902
Power Supply
900-2Q
(2 Relay w/com)
900-4R
(4 Relay)
900-4RL
(4 Relay w/logic)
900-8F
(8 Zone
Distribution-fuse)
900-8P
(8 Zone
Distribution-PTC)
F1
DANGER
!
!
DANGER:
!
WARNING:
!
WARNING:
Remove Jumper from Option Board
Install 900-FA to Option Board
Choose Option Board where 900-FA is to be Installed
12
3
Option board may be in any of these three locations.
Note:
If using
battery backup,
location 3 is
not available.
To avoid risk of electric shock, turn off AC power to power supply before installing or wiring
900-FA board. In the event a fire alarm is active, this board will remove power from the
PS902 DC output and any 900-series option board output.
DANGER:
!
Input (Fire Alarm) Dry contacts required (Closed = no fire alarm)
Connect control contacts between FA1 and FA2
Output (Supervision) 30VDC, 1A resistive dry contact
Board Input Power Board requires 0.05A max. of power supply output current to operate
Temperature Range 32°-120° F (0°- 49° C)
Compliance UL 294, ULC-S318, RoHS, & FCC Part 15

NC FA2FA1NOC
One 900-FA Board - Automatic Reset
Two 900-FA Boards on one power supply
Automatic Reset
NC FA2FA1NOC
NC FA2FA1NOC
NC FA2FA1NOC
One 900-FA Board - Manual Reset
Two 900-FA Boards on two power supplies
Automatic Reset
NC FA2FA1NOC
NC FA2FA1NOC
Supervision Output
Contacts Shown FA Active (open)
Fire Alarm Input
NC C NO FA1 FA2
Terminal Definitions
Fire Alarm Contact
Closed = no fire
Open = fire
Manual Reset
(Temporarily close to reset)
Fire Alarm Contact
Closed = no fire
Open = fire
Fire Alarm Contact
Closed = no fire
Open = fire
Fire Alarm Contact
Closed = no fire
Open = fire
Note: Use 18 gauge wire for all wiring. Wire
length dependent on physical layout.
Remove Jumper Install 900-FA Here
Note: Complete power failure shall result in a fail safe operation.
When connected to a fire alarm releasing control unit, total
loss of power for the locking mechanisms shall be configured
for a fail safe operation.
1b IF INSTALLING TO PS902 MAIN BOARD
2900-FA WIRING
NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS OR
KEYLOCK

Installation
Instructions
900-BB Battery Backup
© 2010 Ingersoll-Rand Company
1-877-671-7011
44487064 Rev. 10/10_a
44487064
1 INSTALL 900-BB ONTO MAIN CIRCUIT BOARD AND SECURE WITH SCREW
Plug Connector
Here
Secure with
Screw Here
(PS914 main board shown)
BATTERY SPECIFICATIONS
Battery Life Model PS906 = 6A @ 24V
Model PS904 = 4A @ 24V
Model PS902 = 2A @ 24V
Model PS914 = 4A @ 24V
Battery Type 12VDC, 7Ah Gel Sealed Rechargeable Battery (2 included)
5 Year Service Life
Replacement Part Number Schlage 991280
To avoid risk of electric shock,
turn off AC power to power
supply before installing or
wiring 900-BB board
DANGER:
!
Charge only Schlage 991280 batteries.
Other types may burst, causing personal injury
and damage. Observe the proper polarity
when connecting the batteries.
CAUTION:
!
}
Refer to installation instructions for compatible supply models - PS902, PS904, PS906, and PS914.
Suitable for Canadian Class IV standby power for access control

2b Place Batteries in Box with
Terminals to the Left
2c Attach Wires from Battery Board
Red wires = (+)
Black wires = (-)
2d Verify That Battery LED is On
If LED is not on, cycle AC power off and then
back on.
2 INSTALL AND CONNECT BATTERIES
Note: Allow 24 hours for batteries to fully charge
2a Turn On AC Breaker to
Energize Power Supply
Battery 1 Battery 2
Black Wires = (-)
+
+
BB LED
(Amber)
On-Solid
AC On
Batteries
Charging
On-Blinking
AC Off
Batteries
Supplying
Power
Battery Supervision Terminals
(Form C Dry Contacts)
Active
AC On
Inactive
AC Off
(Shown
AC Off)
NO
C
NC
Red Wires = (+)
NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS OR
KEYLOCK
Incorrect connection may cause damage to the batteries
WARNING:
!

Installation
Instructions
900-FA Fire Alarm Input
© 2010 Ingersoll-Rand Company
1-877-671-7011
44487072 Rev. 10/10_a
The 900-FA Fire Alarm board can be
installed on any one of the following
power supply or option boards
(refer to installation instructions):
(900-2RS
option board
shown)
• If 900-FA was factory installed, go to step 2
• If installing to option board, go to 1a
• If installing to PS902 main board, go to 1b
1a IF INSTALLING TO OPTION BOARD
44487072
900-2RS
(2 Relay)
PS902
Power Supply
900-2Q
(2 Relay w/com)
900-4R
(4 Relay)
900-4RL
(4 Relay w/logic)
900-8F
(8 Zone
Distribution-fuse)
900-8P
(8 Zone
Distribution-PTC)
F1
DANGER
!
!
DANGER:
!
WARNING:
!
WARNING:
Remove Jumper from Option Board
Install 900-FA to Option Board
Choose Option Board where 900-FA is to be Installed
12
3
Option board may be in any of these three locations.
Note:
If using
battery backup,
location 3 is
not available.
To avoid risk of electric shock, turn off AC power to power supply before installing or wiring
900-FA board. In the event a fire alarm is active, this board will remove power from the
PS902 DC output and any 900-series option board output.
DANGER:
!
Input (Fire Alarm) Dry contacts required (Closed = no fire alarm)
Connect control contacts between FA1 and FA2
Output (Supervision) 30VDC, 1A resistive dry contact
Board Input Power Board requires 0.05A max. of power supply output current to operate
Temperature Range 32°-120° F (0°- 49° C)
Compliance UL 294, ULC-S318, RoHS, & FCC Part 15

NC FA2FA1NOC
One 900-FA Board - Automatic Reset
Two 900-FA Boards on one power supply
Automatic Reset
NC FA2FA1NOC
NC FA2FA1NOC
NC FA2FA1NOC
One 900-FA Board - Manual Reset
Two 900-FA Boards on two power supplies
Automatic Reset
NC FA2FA1NOC
NC FA2FA1NOC
Supervision Output
Contacts Shown FA Active (open)
Fire Alarm Input
NC C NO FA1 FA2
Terminal Definitions
Fire Alarm Contact
Closed = no fire
Open = fire
Manual Reset
(Temporarily close to reset)
Fire Alarm Contact
Closed = no fire
Open = fire
Fire Alarm Contact
Closed = no fire
Open = fire
Fire Alarm Contact
Closed = no fire
Open = fire
Note: Use 18 gauge wire for all wiring. Wire
length dependent on physical layout.
Remove Jumper Install 900-FA Here
Note: Complete power failure shall result in a fail safe operation.
When connected to a fire alarm releasing control unit, total
loss of power for the locking mechanisms shall be configured
for a fail safe operation.
1b IF INSTALLING TO PS902 MAIN BOARD
2900-FA WIRING
NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS OR
KEYLOCK

Installation
Instructions
900-BB Battery Backup
© 2010 Ingersoll-Rand Company
1-877-671-7011
44487064 Rev. 10/10_a
44487064
1 INSTALL 900-BB ONTO MAIN CIRCUIT BOARD AND SECURE WITH SCREW
Plug Connector
Here
Secure with
Screw Here
(PS914 main board shown)
BATTERY SPECIFICATIONS
Battery Life Model PS906 = 6A @ 24V
Model PS904 = 4A @ 24V
Model PS902 = 2A @ 24V
Model PS914 = 4A @ 24V
Battery Type 12VDC, 7Ah Gel Sealed Rechargeable Battery (2 included)
5 Year Service Life
Replacement Part Number Schlage 991280
To avoid risk of electric shock,
turn off AC power to power
supply before installing or
wiring 900-BB board
DANGER:
!
Charge only Schlage 991280 batteries.
Other types may burst, causing personal injury
and damage. Observe the proper polarity
when connecting the batteries.
CAUTION:
!
}
Refer to installation instructions for compatible supply models - PS902, PS904, PS906, and PS914.
Suitable for Canadian Class IV standby power for access control

2b Place Batteries in Box with
Terminals to the Left
2c Attach Wires from Battery Board
Red wires = (+)
Black wires = (-)
2d Verify That Battery LED is On
If LED is not on, cycle AC power off and then
back on.
2 INSTALL AND CONNECT BATTERIES
Note: Allow 24 hours for batteries to fully charge
2a Turn On AC Breaker to
Energize Power Supply
Battery 1 Battery 2
Black Wires = (-)
+
+
BB LED
(Amber)
On-Solid
AC On
Batteries
Charging
On-Blinking
AC Off
Batteries
Supplying
Power
Battery Supervision Terminals
(Form C Dry Contacts)
Active
AC On
Inactive
AC Off
(Shown
AC Off)
NO
C
NC
Red Wires = (+)
NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS OR
KEYLOCK
Incorrect connection may cause damage to the batteries
WARNING:
!
Other manuals for PS914
1
Table of contents
Other Von Duprin Power Supply manuals
Popular Power Supply manuals by other brands

Vector
Vector START-IT VEC021ST owner's manual

TDK-Lambda
TDK-Lambda HWS300 Series instruction manual

TOOQ
TOOQ TQEP-650SP user manual

Altronix
Altronix ALTV2416ULX installation guide

Puls
Puls Dimension Q-Series manual

Rockwell Automation
Rockwell Automation Allen-Bradley 1606-XLE480EH installation instructions