
W2W Heat Pump Controller - Basic
Page 5 of 7 rev 1505
LD_TMP – The measured load-side leaving water temperature, in degrees Fahrenheit.
Desuperheater
For W2W heat pumps equipped with an optional desuperheater (hot water booster), the
following parameters apply:
DSP_TMP – The measured desuperheater temperature, in degrees Fahrenheit.
DSP_MAX (default is 140oF) – Maximum allowable desuperheater temperature. When the
measured temperature exceeds this setting, the desuperheater pump will not be brought
on.
Freeze Protection
The W2W heat pump controller measures the source- and load-side leaving water
temperatures to help prevent the system from freezing. By default, the freeze protection
level is set based on water. If an antifreeze solution is used, these levels may need to be
changed to match that of the true freezing point of the solution. The parameters below are
used to modify freeze protection settings:
LD Min &SRC Min (default is 34oF) – the minimum allowable load and source leaving
water temperatures. If the measured temperature drops below this setting, the
compressor will be shut off. This value should be set slightly above the freeze point of the
water or antifreeze solution used in the source/load loop.
Alarm Conditions and Lockout
There are a number of possible operating conditions which can result in a system alarm,
causing the call to the compressor to be interrupted. When an alarm occurs, a short status
message will be displayed, as outlined in Table 1 on page 3 of this manual. If three alarm
conditions occur within 24 hours of one another, the system controls will “lock out” and no
longer allow the heat pump to run. If this occurs, there may be an issue with the heat
pump, and so a qualified technician should be contacted for service.
LOCK-OUT – The system has locked out due to a recurring alarm condition. Contact a
qualified technician for service. Qualified technicians may reset alarms and lockouts using
the parameters below:
LAST_TXT – will display the last alarm message that occurred. To reset this, set
LAST_RST to ON for a few seconds, and then set back to OFF. It is important to write
this down before resetting, in order to help with system troubleshooting.
ALM_CTR – will count the number of alarm conditions encountered over the last 24 hours.
If the alarm counter reaches three, the system will be locked out. To reset the alarm