PRODUCT INFORMATION
VMC34D - COMBINED METER BOARD - DEEP 34 WAY
SPECIFICATIONS
Rated operational voltage 415V a.c. maximum, 50Hz
Maximum current 100A
Rated insulation voltage 1000V
Short circuit withstand 10kA
Degree of protection IP40 – Indoor Use Only
Usage Recommended for use with copper conductors only
Number of ways (Poles) 34 ways – 2 rows of 17 ways
Gear tray Size of gear tray 320mm ×248mm
Maximum height of meter = 128mm
Maintenance This product does not require maintenance once
installed
DIMENSIONS AND WEIGHT
Height Width Depth Weight
Cover assembly 800mm 402mm 77mm 4.9 kgs
Base (cut out size) 754mm 355mm 98mm 5.0 kgs
INSTALLER NOTES
EARTH AND NEUTRAL BUSBAR LAYOUT
Material Number
of bars
Double
screw
tunnels
Single
screw
tunnels
Earth bar Brass steel 1 3 30
Neutral bar Brass steel 1 4 14
RCD neutral bar Brass steel 1 1 3
• The VMC34D is guaranteed for a period of one year from the date of purchase against defects in
workmanship and materials.
• Defects will be rectied by replacement of the product.
• This warranty becomes null and void if, in our opinion, the product has been misused, incorrectly installed,
tampered with, or subject to power surges.
• The warranty does not include any labour or other associated expenses that may be involved in removal or
installation of the product.
• To obtain a replacement under this guarantee, return the goods (prepaid) to the place of purchase
(proof of purchase must be supplied).
WARRANTY STATEMENT
1. This product is designed to be installed
inside a wall cavity with a minimum
stud size of 90mm and a minimum gib
board/ wall covering of 10mm.
2. For surface mounting use VMCC
surface mount enclosure in conjunction
with this board.
3. The metal wall enclosure must be
earthed.
4. Fold out tags (x6) on the side walls of
the enclosure can be folded out to set
the correct height onto the studs.
5. Door hinge pins are easily removable
and the door can be reversed so that it
swings either left or right.
6. This product is designed to be used
with New Zealand and Australia’s MEN
system.
7. DO NOT install a link between the
neutral bars and earth bar on circuits
dedicated to RCDs.
8. Please ensure circuits and protective
devices are adequately identied during
installation.