2 Display and controls
1. K1 –K4 lights up yellow when the associated
relay is energized.
2. E4 lights up red when message overflow
3.
4. E4 lights up yellow when the associated
electrode is immersed and the liquid resistance
is less than the set value Rliquid
5. E2 –E3 lights up yellow when the associated
electrode is immersed and the liquid resistance
is less than the set value RLiquid
6. E1 lights up red when dry run is reported
7.
8. E4 lights up yellow when the associated
electrode is immersed and the liquid resistance
is less than the set value Rliquid
9. four-pole DIP switch for selecting the desired
program (Pr1...Pr6)
10. Potentiometer for setting the relay delay time (0…10s)
11. Potentiometer for adjusting the sound threshold to the conductivity of the liquid in the range of
5kΩ...250kΩ
12. Potentiometer for setting the alarm reset delay time (0...10s)
13. Potentiometer for setting the alarm trip delay time (0…10s)
3 Application and short description
The NS43V level relay is an electronic device for monitoring levels in conductive liquids. The monitoring is
carried out via electrodes which are immersed or not depending on the liquid level. A satisfactory level
detection of up to 250kΩ liquid resistance between the electrodes makes it possible to monitor all conductive
liquids, but preferably water at various hardness levels. For adaptation to the conductivity of the liquid, the
switching threshold can be set in the range of 5kΩ ... 250kΩ. Thus, for example, it is possible to distinguish
between the liquid itself and foam above it.
The NS protects aggregates and systems from leakage damage, from unnecessary loss of liquids and from
dry run and overflow. It controls and monitors liquid levels in wastewater engineering, swimming pools, fish
farming and wherever a specific level needs to be maintained.
Depending on the application and the set program, it regulates the liquid level between 2
or 3 electrodes by controlling the inlet and outlet of the container. The uppermost and the lowermost
electrodes protect aggregates and equipment’s from dry run and overflow.
Since a pure AC measuring path is used, electrolytic decomposition of the stainless steel electrodes, as well
as oxyhydrogen gas formation, are excluded.
The universal control voltage AC/DC 24-240V enables the supply from all common power networks. The
electrical isolation to the control voltage reliably prevents malfunctions due to accidental energization even
with DC control voltages.
4 Overview of functions
•Monitoring of up to 4 levels
•4 output relays each 1 changeover contact
•Response threshold adjustable 5...250kΩ
•Response delay for relay adjustable 0...10s
•Switch-on and switch-off delay for alarms adjustable 0...10s
•Basic programs (adjustable with DIP switches) for various applications
•Universal control voltage AC/DC 24-240V
•Pluggable connection terminals
•Distributor housing 6 TE, installation depth 55 mm