WAREMA Omnexo Weather station move User manual

1
warema_2052443_alhb_en_v3•2023-07-01 We reserve the right to make technical modifications
the housing or the connecting lines show
signs of damage,
the device is no longer working.
ARNINGW
The sensor may only be operated with
safety extra low voltage.
ARNINGW
An automatically controlled mechanism
may begin to move unexpectedly!
Therefore, never place any objects in the area of
movement of an automatically controlled mechanism.
Disconnect the power supply of the controlled sun
shading products before maintaining or cleaning the
products.
Function
The weather station records precipitation events such as
rain or snow, wind speed, ambient brightness, dawn/dusk
and outside temperature. The weather station only has to
be connected as a network device; the 24VDC power
supply is provided via the four-wire bus line.
Four photo sensors arranged at right angles record the
ambient brightness; sensor 1 also records dawn/dusk
values in a second measuring area.
Sensor surface to detect precipitation
In case of precipitation in the form of fine drizzle, rain
or snow the sensor triggers a switching signal. When
the outside temperature is below 15°C or there is
precipitation, the sensor surface is automatically heated.
This prevents ice formation or a false alarm due to
high humidity. After the sensor surface has detected
precipitation, it quickly dries again because of the heating.
The inclination of the sensor surface creates the required
angle to allow the water to drain off the sensor surface.
Installation
Install the weather station using the mounting bracket
provided.
The weather station must be mounted in an upright
position with a maximum inclination of ±2°. The
photodiodes must be at right angles to the building
facades being shaded.
General information
Fig. 1 Omnexo Weather station move
The Omnexo Weather station move collects measuring
values for brightness, wind, precipitation and outside
temperature. The measuring values are sent to the
Omnexo Central control unit via the bus connection. It
controls the connected sun shading products as a function
of this weather information. The weather station is mounted
outside by means of a fixing bracket or a pole.
Intended use
The Omnexo weather station move is an electronic device
for the collection of measuring values in combination
with an Omnexo central control unit. The approval of
the manufacturer must be obtained for any use of the
device other than its intended purpose specified in these
instructions.
Safety instructions
ARNINGW
The electrical installation (assembly)/
dismantling must be performed by a
certified electrician in accordance with
VDE0100 and/or with the standards
and legal requirements pertaining to
the respective country. The electrician
must observe the installation notes and
instructions included with the electrical
devices supplied.
ARNINGW
If hazard-free operation cannot be
assumed, the device must not be started
or must be deactivated. This assumption is
justified if:
Omnexo Weather station
move
Operating and installation instructions
Valid from
1 July 2023
Keep for future use.

warema_2052443_alhb_en_v3•2023-07-01We reserve the right to make technical modifications
2
Install the weather station in an easily accessible
location at the highest point of the roof structure or
the facade side to be monitored. To avoid hindering
accurate wind evaluation, do not mount the device away
from the wind.
For the system to function properly, precipitation must
be able to hit the sensor surface without interference.
The supply line must be routed so that water cannot
enter into the device or into the building. Use weather-
proof (suitable for outdoor installation) cables such as
4xAWG26C UL black.
The total line length from the weather station must
not exceed 200m if a twisted paired line is used and
routed in an interference-proof manner.
Depending on the installation situation, you can
also directly route the line of type JY(St)Y to the
Omnexo weather station move. It must be ensured
that the line is protected against UV radiation (e.g.
in a conduit, tube) along its entire length.
The photodiode 1 is used for the dawn/dusk control.
The weather station should therefore be positioned so
that the photodiode cannot be influenced at night by
street or garden lighting or other external light sources
(e.g. flashlights).
Trees, bushes or parts of the building can shade the
sensor during the course of the day. In this case, the
sensor cannot deliver exact measuring values and the
results will be incorrect. Therefore, select the installation
location carefully.
The weather station can also be mounted on an
optionally available pole. This requires an additio-
nal fixing adapter (special accessory).
Electrical connection
An on-site overload current protection device (fuse) and a
disconnecting and isolating switch to switch off the entire
unit must be provided.
Use a line that is approved for the operating voltage
and is resistant to weather and UV rays (suitable for
outdoor use),
e.g. 4 x AWG 26 UL black.
The supply line must be routed so that water cannot
enter into the device or into the building.
The total line length must not exceed 1,200 m if a
twisted pair line is used and routed in an interference-
proof manner.
Pay attention to the minimum voltage at the weather
station (voltage drop) and use a separate power supply
unit for the power supply if necessary.
Connect the weather station to the Omnexo Central
control unit as per wiring diagram Fig. 4 on page 4.
The bus lines must be provided with terminating
resistors at the beginning and end of the line.
HUBs are needed for longer line lengths.
If you are using the optional Omnexo Weather station
pro power supply unit 24 V DC/1.3 A AP (article
number 2057430), a branch line of max. 10 m to the
Omnexo Weather station move is permissible.
Please take out the WAREMA ID labels from the devices
and give them to your system integrator (see also
page 4). A clear allocation of the devices and ID labels
must be ensured.
This device meets the requirements on electromagnetic
immunity and electromagnetic interference for use in
residential and commercial environments.
If the Omnexo Weather station move is the last
bus device in the bus line, the terminating resistor
needs to be manually set (see Fig. 4 on page
4).
Depending on the installation situation, you can
also directly route the line of type JY(St)Y to the
Omnexo weather station move. It must be ensured
that the line is protected against UV radiation
(e.g. in a conduit, tube) along its entire length.
Commissioning
To be able to commission the weather station, it must be
set up in the Omnexo software. To determine the serial
number, place the magnet (in central control unit scope of
delivery) on the right side of the housing (photo 2) until the
status LED lights up for confirmation. (see Fig. 3 on page
4).
Alternatively, you can manually enter the serial number
manually (see label on device).
When commissioning, note that the weather station
has an internal temperature correction feature that
improves measurement accuracy. A change in tem-
perature is displayed with a delay of 10 minutes
per °C.
When the operating voltage is first switched on, a
temperature measurement is taken at the weather
station. If the weather station was previously stored
at a considerably lower or higher temperature, it
may take several hours before the correct tempera-
ture is displayed.
If the weather station is already at the temperature
of its environment when it is first switched on, the
actual temperature measurement value will be dis-
played from the start.
Allocation of the photodiodes
The numbers 1 to 4 have been factory-assigned to the
four photodiodes (see Fig. 2). Therefore, position the
photodiodes according to the building facades being
shaded. Align photodiode 1 to the northernmost facade.
For installation directly on the facade, align photodiode 1 to
the facade.
Photo 1
(Dämmerung)
Photo 3
Photo 4 Photo 2
Fig. 2 Position of the photodiodes on the device

3
warema_2052443_alhb_en_v3•2023-07-01 We reserve the right to make technical modifications
Maintenance
There are no parts within the device that require
maintenance.
Cleaning
The weather station should occasionally be checked for
dirt (e.g. bird droppings) and cleaned carefully. Clean the
housing with a soft, damp cloth. Do not use detergents,
cleaning agents, solvents, abrasive substances or steam
cleaners!
Liability
Failure to comply with the product information in these
instructions and any use of the device other than its
intended use may result in the manufacturer refusing to
honour warranty claims for product damage. In this case,
liability for secondary harm to persons or damage to
property will also be excluded. Observe the information in
the operating instructions for your sun shading system. The
automatic or manual operation of the sun shading system
while iced over and the use of the sun shading system
during severe weather may cause damage and must be
prevented by the operator through suitable precautions.
Obligations for the disposal of electrical
devices
A marking with this symbol indicates the following
obligations under the scope of legal regulations:
The owner of this electrical device must dispose of it
separately from unsorted municipal waste for further
recycling.
Used batteries and accumulators that are not enclosed
in the old device, as well as lamps/bulbs that can be
removed from the old device without breaking, must be
disposed of separately.
Distributors of electrical devices and disposal
companies are obliged to take back the equipment free
of charge.
The owner must take it upon themselves to delete any
personal data contained in the electrical device prior to
disposal.
Technical data
Omnexo Weather station
move min. type max. Unit
Supply
Operating voltage (SELV) 21.6 24 26.4 VDC
Current consumption 30 100 mA
Temperature sensor*
Measuring range -20 60 °C
Resolution 0.5 °C
Accuracy ±2 °C
4 direction-dependent photo sensors
Measuring range 0 100 klx
Resolution 1 klx
Accuracy ±10 %
Dawn/dusk measuring range 0 500 lx
Resolution at dawn/dusk 1 lx
Accuracy at dawn/dusk ±10 %
Wind speed
Measuring range 0 25 m/s
Resolution 1 m/s
Accuracy ±1 m/s
Omnexo Weather station
move min. type max. Unit
Precipitation sensor
Measuring range Precipitation yes/no
Omnexo interface
Bus interface RS485 (two-wire bus)
Housing
Dimensions 130 ×175 ×130 mm (WxHxD)
Degree of protection IP43
Safety class III
Installation Wall/pole
Miscellaneous
Conformity
Can be viewed at
www.warema.de/ce
This device complies with the EMC directives for use in
residential and commercial areas.
Software class A
Ambient conditions
Operating temperature -30 60 °C
Storage temperature 0 70 °C
Humidity
(not condensing)
10 100 %RH
Degree of soiling 2
Connection
Omnexo interface Screw terminal
Permissible line cross-section
single-wire/fine-wire without
ferrule
0.14 - 1.5mm²
Permissible line cross-section
fine-wire with ferrule
0.14 - 0.75mm²
Stripping length 7 mm
Maximum line length 10m
Recommended line type
for outdoors
4 x AWG26 C UL (resistant to
UV rays)
Article numbers
Omnexo Weather station move 2047094
Optional accessories
Omnexo Weather station
pro power supply unit 24 V
DC/1.3 A AP
2057430
Connecting line 4 x AWG
26 C UL (resistant to UV rays)
3m
634277
Connecting line 4 x AWG
26 C UL (resistant to UV rays)
10m
634288
Pole L = 35cm;
Dia. 20mm, wall mounting, wall
distance 150mm
632075
Pole L = 100 cm;
Dia. 20mm, wall mounting, wall
distance 150mm
632085
Adapter for pole
Dia. 50 mm
632095
WAREMA Renkhoff SE
Hans-Wilhelm-Renkhoff-Strasse 2
D-97828 Marktheidenfeld, Germany
Germany
* Temperature measuring value:
To obtain correct and highly accurate measuring values,
the weather station must be installed in direct sunlight.
Therefore, when the sun is shining brightly, the
temperature values measured with other thermometers in
the shade may differ from the values measured here.
This deviation has no effect when you use the ice
monitoring function in a network user.

warema_2052443_alhb_en_v3•2023-07-01We reserve the right to make technical modifications
4
KEEP IN A SAFE PLACE FOR COMMISSIONING!
Affix the ID label for the Omnexo Weather station move here
Note down installation location here
175 mm
130 mm
140 mm
40 mm
40 mm
55 mm
45 mm
Identify the weather station, if this
is required by the menu, by holding
the supplied magnet against the
type label on the right-hand side
(as seen from the front).
→ The status LED lights up
as a confirmation.
Magnet
Fig. 3 Omnexo Weather station move and magnet dimensions for commissioning
4 x AWG 26 UL black
JY(St)Y 4 x 2 x 0.8 mm ∅
junction box
on-site
Omnexo
Central control unit
1234
terminal 1: 0 V
terminal 2: 24 V
terminal 3: A
terminal 4: B
View from below
Strain relief
WH OG
YE BN
BK
RD
BK
RD
OG
BN
BK
RD
The wire colours may vary
depending on the
type of lines used.
terminating resistor 120 Ω
ferrules must be
sure to be used
Fig. 4 Omnexo Weather station move wiring diagram
Other WAREMA Weather Station manuals