Water Furnace TPCM32U03 Manual

1
INSTRUCTION GUIDE: ELITE COMMUNICATING THERMOSTAT
IG1602EW 06/12
Instruction Guide:
Elite Communicating Thermostats
TPCM32U03/TPCM32U04
Thermostat Operation
NOTE: These communicating thermostats communicate via a
4-wire Modbus protocol and will only operate with the Aurora
Control System. TPCM32U03 is not applicable to variable speed
compressor equipment.
Adjusting Temperature
(Temporary Override in Programmable models)
1. Before you can adjust the temperature, a MODE must be
selected. If you are already in a Heating or Cooling mode,
then skip to step 5.
2. To select a MODE, use the keypad
arrows to scroll to MODE, and then
press the center button on the key
pad to enter the operating mode
menu.
3. Select the desired mode by
scrolling up or down, with the
arrows, and then press the center
button on the keypad to enter into that mode.
4. You are now returned to the Main Menu and Figure 1 is a
similar view. NOTE: Outdoor temperature is only displayed
if an outdoor sensor is installed.
5. To increase the temperature set point, use the arrow up
button. To decrease the set point, use the arrow down
button. Press the center button on the key pad for the new
set point to be effective
Setting Date And Time
1. From the Main Menu, scroll to MENU and press the center
button ■ on the keypad.
2. Select SET DATE AND TIME
3. If your area observes daylight savings time, select AUTO
DAYLIGHT SAVING, scroll to ON, then press the center
button ■ to save. You will be returned to the select SET
DATE AND TIME menu. Scroll to SET DATE AND TIME
and press the center button ■ on the keypad.
4. SET MONTH by using the up and down arrows ▲▼, and then
press the center button on the keypad to save the month.
5. SET DAY by using the up and down arrows ▲▼, and then
press the center button on the keypad to save the day.
6. SET YEAR by using the up and down arrows ▲▼, and then
press the center button on the keypad to save the year.
7. SET HOUR by using the up and down arrows ▲▼, and then
press the center button on the keypad to save the hour.
8. SET MINUTE by using the up and down arrows ▲▼, and
then press the center button ■ on the keypad to save the
minute.
9. Date and Time are now set. You can return to the Main
Menu by pressing the left arrow key to return to the
previous menu.
Hold Setting
Vacation and Permanent (Programmable models only)
This section describes the HOLD functions. You can program
the thermostat to hold the temperature for a period of time.
If you want to hold the temperature for a few hours or a few
weeks, your thermostat can accommodate your schedule.
Vacation Hold
(Programmable models only)
1. From the Main Menu, scroll to MENU and press the center
button ■ on the keypad.
2. Select HOLD → VACATION
3. First, the thermostat prompts you for a temperature to hold.
If you are in AUTO MODE you will be prompted for both
a heat setting and a cool setting. Use the up and down
arrows keys ▲▼ to select the desired temperature and
press the center button on the keypad.
4. Next it will prompt you for a date and time that you wish
to return to programmed operation. Returning to the Main
Screen, you will notice that in the upper part of the screen
is alternating HOLD TIL *date and time you specified* and
the actual date and time.
5. To cancel this hold, scroll to CANCEL HOLD from the Main
Menu and press the center button ■.
Permanent Hold
(Programmable models only)
1. From the Main Menu, scroll to MENU and press the center
button ■ on the keypad.
2. Select HOLD → PERMANENT
3. First, the thermostat prompts you for a temperature to hold.
If you are in AUTO MODE you will be prompted for both
a heat setting and a cool setting. Use the up and down
arrows keys ▲▼ to select the desired temperature and
press the center button on the keypad.
4. Returning to the Main Screen, you will notice that in the
upper part of the screen is alternating PERMANENT HOLD
and the actual date and time.
5. You can adjust to permanent hold temperature at will, and
the temperature you select will remain until the permanent
hold is canceled.
6. To cancel this hold, scroll to CANCEL HOLD from the Main
Menu and press the center button ■. This will revert to the
programmed settings.
Figure 1
Elite Communicating Thermostats
TPCM32U03/TPCM32U04

2
INSTRUCTION GUIDE: ELITE COMMUNICATING THERMOSTAT
IG1602EW 06/12
Fan Operation
The thermostat can operate the fan in four ways:
AUTO (on only during heating and cooling calls)
ON (always on)
INTERMITTENT (cycles fan) Pg. 3
PROGRAMMED FAN (fan follows the program set in the
program menu screen) (programmable models only) Pg. 3
1. From the Main Menu, scroll to (FAN) and press the center
button on the keypad ■.
2. Select the operation you desire as described above.
Changing Modes
1. From the main screen select MODE.
2. Select the operating mode you need
and press the center button ■.
NOTE: If selecting EMERGENCY HEAT,
the backlight color will change from
blue to red indicating that auxiliary heat
is operating instead of the heat pump
compressor. Auxiliary/emergency heat is significantly more
expensive to operate than the heat pump compressor, and
should not be selected unless the heat pump compressor is not
operational.
Fahrenheit or Celsius
1. From the Main Menu, scroll to MENU and press the center
button ■ on the keypad.
2. Select SETINGS → SCREEN SETTINGS → FAHRENHEIT
OR CELSIUS
3. Select which scale you prefer.
12 or 24 Hour Clock
Within this menu option, you can change the time displayed by
your thermostat to 24 Hour time (Military Time).
1. From the Main Menu, scroll to MENU and press the center
button ■ on the keypad.
2. Select SETINGS → SCREEN SETTINGS → 12 OR 24
HOUR CLOCK
3. Select which time base you prefer.
Contrast Adjustment
You can change the contrast level of your thermostat screen to
be displayed to your preference.
1. From the Main Menu, scroll to MENU and press the center
button on the keypad.
2. Select SETINGS → SCREEN SETTINGS →CONTRAST
3. Use the up and down arrows ▲▼ to increase or decrease
the contrast level.
4. Press the center button to accept the new setting.
Backlight ON Time
This thermostat has a two color backlight feature. Anytime
a button is pressed, the blue backlight stays on for a certain
amount of time. A red backlight is visible if you are selecting
Emergency Heat mode. You can adjust the amount of time the
backlight stays on in the menu options.
1. From the Main Menu, scroll to MENU and press the center
button ■ on the keypad.
2. Select SETINGS → SCREEN SETTINGS →BACKLIGHT
ON TIME
3. You can change the backlight on time by using the up and
down arrows ▲▼. 30, 60, 90, 120, and ON (all the time)
are your choices. Press the center button to save the new
backlight on time.
Programming Your Thermostat
(programmable models only)
Preset Programming
Preset options will step you through the programming. Simply
select the temperatures and then view the completed program.
Programming a Day or a Series of Days
After selecting the programming
screen, you have the option of
programming everyday, weekdays,
weekends, or individual days. Once
you’ve selected a certain day to
program, a screen appears that allows
you to set the time, heat setting, cool
setting, and fan operation for each
event.
1. From the Main Menu, scroll to
MENU and press the center button
■ on the keypad.
2. Select PROGRAM
3. You can program each day
differently by going through each
day and personalizing them.
Or, you can program everyday the same by scrolling
to EVERYDAY. Or, you can program the weekdays or
weekends the same by selecting the appropriate menu item.
4. To program everyday the same, select EVERYDAY and
then press the center button ■.
5. Using the right arrow button ►, highlight the WAKE time,
and change to desired time by using the up and down
arrow ▲▼ buttons. Move to the next entry by using the
right arrow button ►. To change the HEAT set point, use
the up and down arrows. Continue this process until all
settings are to your liking.
6. To save these settings, scroll to SAVE, and press the center
button ■.
Copying A Program From One Day To Another
In the PROGRAM menu, there is an option to COPY. The option
can be used to copy the program from one day to another day.
After COPY is selected, the thermostat will prompt you for which
day to copy from. Next, it will prompt you for which day to copy
the program to. After these selections, it will then confirm what
is being copied to where. At this point you have the option of
canceling the copy process, by pressing ◄ to return to the copy
menu, or saving what you have by pressing the center button ■.
The SAVED screen will appear returning you to the copy menu.
Pressing ◄ will return you to the PROGRAM menu. Pressing ◄
again will return you to the MAIN MENU.

3
INSTRUCTION GUIDE: ELITE COMMUNICATING THERMOSTAT
IG1602EW 06/12
Advanced Settings
Security Lockout
This thermostat has the option to set
security features to lockout everything but
the adjustment of the temperature or a total
keypad lockout.
1. From the Main Menu, scroll to MENU
and press the center button ■ on the
keypad.
2. Select SECURITY LOCKOUT.
3. Select whether you want to lockout
everything but TEMP ADJUST ONLY or
TOTAL KEYPAD LOCKOUT.
4. Either selection will bring you to the
Enter Pin Number screen.
5. Using the up and down arrows ▲▼, select a pin number
to lock out the thermostat. The right arrow ► moves you to
the next pin digit.
6. Once you’ve entered the 4-digit pin number, press the
center button ■ to save the pin. The screen will display
LOCKED and return to the main Screen.
7. Once you return to the Main Screen, in the upper left of the
screen will alternate between LOCKED and the date and
time.
8. If you selected TEMP ADJUST ONLY, you will only be able
to adjust the set point temperature. Any other operation will
require the pin number to unlock the thermostat.
9. Once unlocked, you’ll have to set a pin number again to
lockout the thermostat again.
10. In the event pin number is lost default is 9999.
Offsets
1. MENU → SETTINGS → OFFSETS
Temperature Offsets
This option allows calibration (or deliberate
miscalibration) of the room temperature sensor(s). There
are various reasons why the displayed temperature
would be adjusted to a higher or lower value. NOTE: Do
not adjust for 30 minutes after installation because board
may be heated by handling. The selected number is the
number of degrees, plus or minus, which will be added to
actual temperature. The numbers can range between -5˚
and +5˚. Default values are set to 0˚ offset.
Temperature Offset
Remote Indoor Offset (if sensor is attached)
Outdoor Offset (if sensor is attached)
Humidity Offset
This option allows calibration of the humidity sensor.
Adjustments can range between -10% and +10%. Default
is 0% offset.
Auto Changeover
With auto changeover, the thermostat automatically switches itself
from heating to cooling, or vise versa, based on the setpoints.
When setting up the thermostat you have to enter both a cooling
setpoint and a heating setpoint. The thermostat will also prevent
the user from setting the cooling setpoint lower than the heating
setpoint. Mode is set to AUTO for this operation to work.
MENU → SETTINGS → AUTO CHANGEOVER
Auto Changeover Time – This setting sets the minimum off time
before the thermostat can change from one mode to
another. Default is 5 minutes. Range is from 0-120
minutes in 15 minute increments.
Auto or Manual Change – Default is AUTO. If MANUAL is
chosen, you will need to change from heating to
cooling or vise versa. When MANUAL is set, AUTO is
removed from the MODE screen as a choice.
Instantaneous Energy Monitoring
Instantaneous Energy Monitoring
can be found under the main menu,
if the energy monitoring option has
been enabled on the Aurora Control
System. The screen displays energy
usage in real time, the current mode
of the heat pump, and the outdoor air
temperature (if installed).
Superboost (Variable Speed Heat Pumps ONLY)
Superboost can be found under the main menu. The Superboost
option temporarily enables a larger cooling capacity range. The
screen will allow the homeowner to turn on or off the Superboost
option. The option will enable by default for a 24 hour period of
time and then will automatically be disabled.
WARNING: OVERUSE OF THIS OPTION MAY
CAUSE OVERHEATING OF LOOPS.
Intermittent Fan
Temperature conditions can vary widely between the thermostat
location and extremities of the space the thermostat serves.
This air stratification problem can be especially pronounced
during mild outdoor conditions when long periods elapse
between space conditioning demands from the thermostat. This
intermittent fan operation can also improve the performance of
air cleaning or special filtration systems that locate the cleaning
or filtration media at the return air side of the fan.
SUPERBOOST
STATUS:
OFF
TURN ON SUPERBOOST
◄BACK
SUPERBOOST
STATUS:
ON
TURNING OFF IN:
23HRS 15MIN
TURN OFF SUPERBOOST
◄BACK
INST ENERGY MONITOR
MODE: STANDBY
BLOWER 0 W
COMPRESSOR 0 W
ELEC HT 0 W
PUMP 0 W
TOTAL 0 W
OUTDOOR AIR NA
◄BACK

4
INSTRUCTION GUIDE: ELITE COMMUNICATING THERMOSTAT
IG1602EW 06/12
Installer Information/Advanced Features
Safety Considerations
Improper wiring or installation may damage thermostat. Wiring
must conform to local and national electrical codes
Introduction
The thermostat is a wall mounted, low-voltage thermostat which
maintains room temperature by controlling the operation of a
heating and air conditioning system. Batteries are not required;
temperature and mode settings are preserved with the power off.
Installation Considerations
The thermostat requires no batteries. The thermostat is not a
power stealing device and MUST have both R and C connected.
Installation
Thermostat Location
Thermostat should be mounted:
- Approximately 5 ft. (1.5m) from floor.
- Close to or in a frequently used room, preferably on an
inside partitioning wall.
- On a section of wall without pipes or duct work.
Thermostat should NOT be mounted:
- Close to a window, on an outside wall, or next to a door
leading to the outside.
- Exposed to direct light and heat from a lamp, sun,
fireplace, or other temperature-radiating object which
may cause a false reading.
- Close to or in direct airflow from supply registers and
return-air grilles.
- In areas with poor air circulation, such as behind a door
or in an alcove.
Install Thermostat
1. Turn off all power to unit.
2. If an existing thermostat is being replaced:
a) Remove existing thermostat from wall.
b) Disconnect wires from existing thermostat, one at a
time. Be careful not to allow wires to fall back into the
wall.
c) As each wire is disconnected, record wire color and
terminal marking.
d) Discard or recycle old thermostat.
NOTE: Mercury is a hazardous waste and MUST be
disposed of properly.
3. Separate the front and back pieces of plastic.
4. Route thermostat wires through hole in back piece of
plastic. Level plastic against wall (for aesthetic value only
- thermostat need not be leveled for proper operation) and
mark wall through 2 mounting holes.
5. Drill two 3/16-in. mounting holes in wall where marked.
(NOTE: Mounting holes on thermostat are designed to fit
on a horizontal J-box).
6. Secure back plastic to wall with 2 anchors and screws
provided making sure all wires extend through hole in plastic.
1. MENU → SETTINGS →
INTERMITTENT FAN
2. If the FAN hasn’t been on for an hour,
the fan will start cycling based on these
times. Default is OFF. The first screen
is the amount of time you want the fan
to be energized. Ranges are OFF, or 5-20 minutes in 5
minute increments.
3. After entering this time and pressing
the center button ■, the next screen
is the amount of time the fan is OFF.
Ranges are 0 minutes, or 5-40 minutes
in 5 minute increments.
4. After entering this time and pressing
the center button ■ you will be returned to the Setting Menu
screen.
5. Fan ON and OFF cycles will continue until the fan has been
energized by a call for heating or cooling.
Service Information
MENU → SETTINGS → SERVICE INFO
These screens help an installer or
contractor to have a good understanding of
what problems might be occurring before
arriving for service.
WARNING: Before installing thermostat, turn off
all power to unit. There may be more than one
power disconnect. Electrical shock can cause
personal injury or death.

5
INSTRUCTION GUIDE: ELITE COMMUNICATING THERMOSTAT
IG1602EW 06/12
Installer Settings
NOTE: These options are intended to be used by the installer.
End users are not advised to change or modify any of these
settings. Doing so may make your equipment stop working
properly and/or may void the warranty of the thermostat as
well as the equipment hooked up to the thermostat. To access
the installer setting menu, the mode must be set to OFF. Then,
press both the up and down arrows keys at the same time for at
least 5 seconds to enter the installer screen.
Model Configuration
Options to select from:
PROGRAMMABLE / NONPROGRAMMABLE,
SINGLE STAGE/MULTI STAGE
Single Stage – Used with heat pumps with PSC motors
Multi Stage – Used with heat pumps with ECM motors,
either Single Speed or Dual Capacity
NORMAL/DUAL FUEL/INTELLIZONE STANDARD/
INTELLIZONE NO DOWN STAGING
Normal – used for normal operation
Dual Fuel – used on dual fuel systems. Needs outdoor
sensor to lockout dual fuel.
IntelliZone Standard – used with IntelliZone. The ‘W’ acts
like a Y3 and requires less droop. It activates 3rd stage with
the same time/temperature weighting as Y1 and Y2.
IntelliZone No Down Staging – used with IntelliZone and if
used, SHOULD BE ONLY ON MAIN ZONE. The thermostat
will hold the deepest call encountered and should minimize
compressor speed changes.
Accessories
Each of these options has settings for Cumulative Run Time
and Calendar Time. Messages will flash at the top of the Main
screen when these events are met to alert the owner that it is
time service these options.
Air Filter – Cumulative Run Time default is 1000 hours and
Calendar Time is 6 months. Values can range from
400-3600 hours for Cumulative Run Time (in 100 hour
increments), or Calendar Time can be set to OFF, or
3-48 months (in 3 month increments).
Humidifier – Cumulative Run Time default is 0 hours (OFF)
and Calendar Time is OFF. Values can range from
400-3600 hours for Cumulative Run Time (in 100 hour
increments), or Calendar Time can be set to OFF, or
3-24 months (in 3 month increments).
UV Lamp – Cumulative Run Time default is 0 hours (OFF)
and Calendar Time is OFF. Values can range from
400-3600 hours for Cumulative Run Time (in 100 hour
increments), or Calendar Time can be set to OFF, or
3-48 months (in 3 month increments).
Air Cleaner – Cumulative Run Time default is 0 hours (OFF)
and Calendar Time is OFF. Values can range from
400-3600 hours for Cumulative Run Time (in 100 hour
increments), or Calendar Time can be set to OFF, or
3-24 months (in 3 month increments).
7. Connect wires to proper terminal of the connector block in
the front plastic.
8. Push any excess wire back into wall. Excess wire inside the
thermostat plastic case can interfere with proper air flow
across the temperature sensor. Seal hole in wall to prevent
air leaks. Leaks can affect operation.
9. Snap front and back pieces of plastic together.
10. Turn on power to the unit.
Wiring Diagrams
All excess wire should be pushed back into the wall as far as
possible. Excess wire inside the thermostat plastic case may
interfere with the air flow across the temperature sensor.
Thermostat Connections
C – 24V Common for Control Circuit
R – 24V Supply for Control Circuit
W1 – Auxiliary Heat
A+ – Modbus RS485 Positive
B - – Modbus RS485 Negative
GND – Ground
OD – Outdoor Temperature Sensor
ID – Indoor Temperature Sensor
NOTE: Geothermal equipment must have the Aurora Control
system to use these communicating thermostats.
THERMOSTAT GEOTHERMAL
C C
–
DH
R R
W1 W
H
O
Y2
Y1
G +
L –
–
A+ OUTDOOR SENSOR
B-
GND
OD
ID INDOOR SENSOR
GND
*** Dashed line represents optional, but highly suggested, “W” terminal
connection for Loss of Communication Backup Heat.

6
INSTRUCTION GUIDE: ELITE COMMUNICATING THERMOSTAT
IG1602EW 06/12
Both – HUMIDIFY operates in the HEAT mode and
DEHUMIDIFY operates in COOL mode.
None – Neither is active.
Reversing Valve Option
Option of the reversing valve (O output) being on when in
cooling or heating. Default is COOLING.
Restore Defaults
This will allow you to revert to the factory default settings.
Anticipator
This adjustment controls the sensitivity and cycle rate of the
thermostat. Higher numbers decrease the cycle rate. Lower
numbers increase the cycle rate. Default value is 0, and the
range is 0-4.
Differential
This adjustment will vary the number of degrees, from the set
point, before a call for heating or cooling is made. Adjustments
can range between 0.5˚ and 4˚ differential. Default is 0.5˚ offset.
(If your set point is 70˚F in heating, your thermostat will not call
for heat until the temperature is 69.5˚F, with a 0.5 differential).
Cycles Per Hour
This feature will not allow more than the specified number of
equipment cycles per hour. Values can range from 4 or 6 (or 1
cycle every 15 minutes (default) or 1 cycle every 10 minutes, if
6 is set). Factory default setting is 4. This default selection will
provide optimum performance in nearly all installations.
MENU → SETTINGS → CYCLES PER HOUR
Program Settings
MENU → SETTINGS → PROGRAM SETTINGS
Smart Recovery
Smart recovery is a feature of your thermostat designed to
improve comfort by adjusting temperatures to achieve a room
temperature by the programmed time. When it’s time for a
programmed temperature change, smart recovery begins working
in advance, turning the system on and off as needed to adjust
the indoor temperature. During these transition periods, you
may notice that the actual temperature and your temperature
setting don’t match. That’s smart recovery in action, adjusting
temperatures in small increments for greater energy efficiency.
This is more energy efficient than simply allowing the system to
operate at full capacity until the desired temperature has been
met. Smart Recovery helps avoid excessive use of auxiliary heat
when recovering from night setback in the heating mode.
To cancel the message, select the CANCEL ALARM, and press
the center button ■.
Input Dealer Info
Contractors are able to input Contractor Name, and Contractor
Phone number into these screens. The model and serial number
are communicated from the unit. This way, the owner could give
this information to the contractor so that he would know what
system the owner has prior to the service visit.
1. Scroll to the info you want to enter and press the center
button ■.
2. Enter the information by scrolling through the characters
using the up & down arrows ▲▼. Once the character you
want is set, press the right arrow ► to move to the next
space and begin entering another character.
3. Once you’ve completed filling out the field, press the center
button ■ to save the entry and return to the INPUT DEALER
INFO screen. Repeat this process for all fields you want
saved.
4. Once all fields have been entered, scroll to SAVE and press
the center button ■.
Fan with Heat Option
Options are ON or OFF. This selection determines whether G
(fan) output is to be ON or OFF when W (auxiliary heat) output
is ON.
Humidity Option (TPCM32U04 Only)
If your system is setup with a humidifier, or you desire a
dehumidification option, select the appropriate setting.
HUMIDIFY (TPCM32U04 only)
DEHUMIDIFY (TPCM32U04 only)
BOTH (H or DH)
NONE
To adjust the Set Point for Humidification or Dehumidification,
Select the RH from the Main menu. The values can be selected
and adjusted from that screen.
NOTE: If you have an outdoor sensor attached to the
thermostat, the Humidification setting is adjusted automatically
based on the outdoor temperature.
Humidify – Turns on the H output when the room humidity is
below the set point and MODE is set to HEAT, EHEAT,
or AUTO when Heating was the last mode run.
Dehumidify – Turns on the DH output when the room humidity is
above the set point and the MODE is set to COOL or
AUTO when Cool was the last mode run.

7
INSTRUCTION GUIDE: ELITE COMMUNICATING THERMOSTAT
IG1602EW 06/12
Faults
Non-Critical Faults
Non-critical faults are displayed
below the temperature on the main
screen. These faults will clear
themselves if the fault condition
corrects itself. Your dealer should
be informed when either a critical or
non-critical fault occurs.
Lockout/Critical Faults
Critical faults will change the screen
to the service needed screen
and turn the backlight color to
red. The system can be reset by
pressing the left arrow key on the
thermostat. Some of the faults
will clear themselves if the fault
condition corrects itself. Your dealer
should be informed when either a
critical or non-critical fault occurs.
Fault Reference
Fault Code Fault Description
1 Inputs Error (O and W)
2 High Pressure
3 Low Pressure
4 Freeze Detection (FP2)
5 Freeze Detection (FP1)
7 Condensate Overflow
8 Over/Under Voltage
9 Air Flow/RPM
10 Compressor Monitor
11 FP1 or FP2 Sensor Error
15 Hot Water Limit
18 Non Critical Communication Error
19 Critical Communication Error
NOTE: For a complete list of fault codes, please reference the
unit’s manual.
1/5/12 12:40 PM
FAN AUTO
76° OFF
E18-NCRITCOMM ERROR
HUMIDITY
34%
REL HUM MODE FAN MENU
SERVICE
NEEDED
PHONE CONTRACTOR
CONTRACTORS NAME
HERE
555-555-5555
MODEL NUMBER
MODEL HERE
SERIAL NUMBER
0000000000
E2 –HIGH PRESSURE
◄RESET TRIP
Events Per Day
This is where you can set the number of events per day. (An
event is a period of time scheduled with a certain heating and
cooling setpoint.) For instance if you are away from your home
from 8am to 5pm, make this period of time an event and set
the thermostat at an energy saving setting. You have the option
of setting the events per day to 4-RESIDENTIAL (4 events),
2-RESIDENTIAL (2 events) or 2-BUSINESS (2 events).
Smart Heat Staging (Heat Pump Only)
This delays 3rd stage heating for a set
time. Options are ON or OFF. Default is
OFF. Range for this are 0-120 minutes in 5
minute increments. If set to ON, 30 minutes
is the default time.( If ‘ON’ is selected and
the demand has not been satisfied the
thermostat will energize electric heat after the selected time has
expired regardless of demand.)
Cooling Lockout
When an outdoor temperature sensor is installed, it can be set
up so cooling option doesn’t energize if the outdoor temperature
is below a certain temperature. Ranges for this are NONE
(default), 45˚F, 50˚F, or 55˚F.
Electric Heat Or Dual Fuel Lockout
When an outdoor temperature sensor is installed, you can set it
up so the electric heat or Dual Fuel option doesn’t energize if the
outdoor temperature is above a certain temperature. Ranges for
this are NONE (default), 5˚F to 60˚F in 5˚ increments.
Compressor Satisfy
Normal – Allows compressor downstaging from Y2 to Y1.
Recommended setting for most products.
Y2 Finish – Once the heat pump has engaged Y2 the thermostat
will not allow downstaging to Y1. The call is satisfied
in Y2.
Remote Sensor
Allows selection of the remote sensor to determine indoor
temperature. Options are REMOTE SENSOR, AVERAGE, and
STAND ALONE. The REMOTE SENSOR is connected to the ID
and GND on the thermostat terminals.
4-Residential
(Default)
2-Residential 2-Business

8
INSTRUCTION GUIDE: ELITE COMMUNICATING THERMOSTAT
IG1602EW 06/12
©2012 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and reserves the
right to change design and specications without notice.
NOTES
This manual suits for next models
1
Table of contents
Other Water Furnace Thermostat manuals

Water Furnace
Water Furnace IntelliZone2 MasterStat User manual

Water Furnace
Water Furnace IntelliZone2 ZoneStat User manual

Water Furnace
Water Furnace IntelliZone2 MasterStat Operation manual

Water Furnace
Water Furnace TP32W03 User manual

Water Furnace
Water Furnace TPCC32U01 Manual

Water Furnace
Water Furnace IntelliZone2 MasterStat User manual

Water Furnace
Water Furnace TPCC32U01 Manual

Water Furnace
Water Furnace IntelliZone User manual

Water Furnace
Water Furnace IntelliZone2 ZoneStat Manual

Water Furnace
Water Furnace TP32U03 User manual