Water Furnace TPCC32U01 Manual

1
INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT
IG1601EW 06/12 997-012330-3-R
Instruction Guide:
Color Touchscreen Communicating with Humidity Control Thermostat
TPCC32U01
Heat Pump Thermostat User Information
This communicating thermostat communicates via a 4-wire
Modbus protocol and will only operate with the Aurora Control
System.
Thermostat Operation
Adjusting Temperature
(Temporary Override in Programmable models)
NOTE: Outdoor temperature is only displayed if an outdoor
sensor is installed.
1. To select a MODE, press the screen button MODE, and
then press the desired operating mode.
2. Press the blue up or down arrow to increase or decrease the
cooling temperature set point. Press the red up or down arrow
to increase or decrease the heating temperature set point.
Menu
Press the Menu button.
If your heat pump has Energy Monitor installed, the screen shall
be this:
Fan Operation
The thermostat can operate the fan in three ways:
AUTO (on only during heating and cooling calls)
ON (always on)
INTERMITTENT (cycles fan)
1. From the Home screen or Menu, press the Fan button.
2. Select the operation you desire as described above by
pressing the up and down arrows ▲▼.
Intermittent Fan
Temperature conditions can vary widely between the thermostat
location and extremities of the space the thermostat serves.
This air stratification problem can be especially pronounced
during mild outdoor conditions when long periods elapse
between space conditioning demands from the thermostat. This
intermittent fan operation can also improve the performance of
air cleaning or special filtration systems that locate the cleaning
or filtration media at the return air side of the fan.
Color Touchscreen Communicating with Humidity Control
TPCC32U01

2
INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT
IG1601EW 06/12 997-012330-3-R
If the FAN hasn’t been on for an hour, the fan will start cycling
based on these times. Default is OFF. The first screen is the
amount of time you want the fan to be energized. Ranges are
OFF, or 5-20 minutes in 5 minute increments. Then adjust the
time of the fan is OFF. Ranges are 0 minutes, or 5-40 minutes in
5 minute increments. Fan ON and OFF cycles will continue until
the fan has been energized by a call for heating or cooling.
Display Dealer Information
The installing dealer’s contact information can be displayed on this
screen. From the main screen, press Menu and then press Dealer.
Programming Your Thermostat
Preset Programming
Preset options will step you through the programming. Simply
select the temperatures and then view the completed program.
Programming a Day or a Series Of Days
After selecting the programming screen, you have the option
of programming everyday, weekdays, weekends, or individual
days. Once you’ve selected a certain day to program, a screen
appears that allows you to set the time, heat setting, cool
setting, and fan operation for each event.
1. From the Program menu, select program ON.
2. Select the number of events each day, 2 or 4.
3. You can program each day differently, or every day the
same or the weekdays or weekends the same.
Copying a Program From One Day to Another
In the PROGRAM menu, there is an option to COPY. The option
can be used to copy the program from one day to another day.
After COPY is selected, the thermostat will prompt you for which
day to copy from. Next, it will prompt you for which day to copy
the program to. After these selections, it will then confirm what is
being copied to where.
Advanced Settings
Set Date and Time
1. From the home screen, press Menu, then press Settings,
then press Date/Time
2. Set month/ day/year, by pressing the up and down arrows
▲▼.
3. Set hour: minute, by pressing the up and down arrows ▲▼.
4. Within this menu option, you can change the time displayed
by your thermostat to 24 Hour time (Military Time).
5. If your area observes daylight savings time, select D.S.T.
to ON.
6. Date and Time are now set. You can return to the Main
Menu by pressing the BACK to return to the previous menu.
Security Lockout
This thermostat has the option to set security features to lockout
everything but the adjustment of the temperature.
1. From the home screen, press Menu, then press Settings.
2. Select Security, press ON.

3
INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT
IG1601EW 06/12 997-012330-3-R
3. Enter Pin Number screen.
4. Select a pin number to lock out the thermostat. Once
you’ve entered the 4-digit pin number, press the OK button
to save the pin.
5. In the event pin number is lost default is 9999
Backlight Brightness
Press the up and down arrows ▲▼ to adjust desired backlight
brightness when the thermostat is in active display or in the
sleep display mode.
Sound Volume
Adjust the desired sound level of screen buttons when pressed
and the desired sound, either beep, one click, or two clicks.
Background
Select the desired background.
Vacation
1. From the MENU, press the Vacation button to set vacation
starting date, time, and desired temperature, return date, time.
2. To cancel this setting, press the CANCEL button.
3. Press the OK to return to the previous menu.
USB
This screen allows you to import or export the User setting or
Program.
Superboost (Variable Speed Heat Pumps Only)
Superboost can be found under the main menu settings of
the thermostat. The Superboost option temporarily enables a
larger cooling capacity range. Normal cooling mode is limited
to compressor speeds 1-9 and Superboost allows compressor
speeds 10-12 if needed. This screen will allow the homeowner
to turn on or off the Superboost option. The Superboost option
will be enabled, by default, for a 24-hour period of time and then
will automatically be disabled.
On Peak
This screen allows you to adjust the desired On Peak temperature.
Energy Monitor
1. If your heat pump has Energy Monitoring installed, the energy
consumed can be viewed by pressing the Energy button.
2. There are three choices to view the energy consumed:
Instant, Daily, and Monthly.
Instantaneous Energy Use screen
Daily Energy Use screen

4
INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT
IG1601EW 06/12 997-012330-3-R
Monthly Energy Use screen
Yearly Summary screen
Installer Information/Advanced Features
Safety Considerations
Improper wiring or installation may damage thermostat. Wiring
must conform to local and national electrical codes.
Introduction
The thermostat is a wall mounted, low-voltage thermostat which
maintains room temperature by controlling the operation of a
heating and air conditioning system. Batteries are not required;
temperature and mode settings are preserved with the power off.
Installation Considerations
The thermostat requires no batteries. The thermostat is not a
power stealing device and MUST have both R and C connected.
Installation
Thermostat Location
Thermostat should be mounted:
• Approximately 5 ft. (1.5m) from floor.
• Close to or in a frequently used room, preferably on an
inside partitioning wall.
• On a section of wall without pipes or duct work.
• Thermostat should NOT be mounted:
• Close to a window, on an outside wall, or next to a
door leading to the outside.
• Exposed to direct light and heat from a lamp, sun,
fireplace, or other temperature-radiating object which
may cause a false reading.
• Close to or in direct airflow from supply registers and
return-air grilles.
• In areas with poor air circulation, such as behind a
door or in an alcove.
Install Thermostat
1. Turn off all power to unit.
2. If an existing thermostat is being replaced:
• Remove existing thermostat from wall.
• Disconnect wires from existing thermostat, one at a time.
Be careful not to allow wires to fall back into the wall.
• As each wire is disconnected, record wire color and
terminal marking.
• Discard or recycle old thermostat.
NOTE: Mercury is a hazardous waste and MUST be
disposed of properly.
3. Separate the front and back pieces of plastic.
4. Route thermostat wires through hole in back piece of
plastic. Level plastic against wall (for aesthetic value only
- thermostat need not be leveled for proper operation) and
mark wall through 2 mounting holes.
5. Drill two 3/16-in. mounting holes in wall where marked.
(NOTE: Mounting holes on thermostat are designed to fit
on a horizontal J-box).
6. Secure back plastic to wall with 2 anchors and screws
provided making sure all wires extend through hole in plastic.
7. Connect wires to proper terminal of the connector block in
the front plastic.
8. Push any excess wire back into wall. Excess wire inside the
thermostat plastic case can interfere with proper air flow
across the temperature sensor. Seal hole in wall to prevent
air leaks. Leaks can affect operation.
9. Snap front and back pieces of plastic together.
10. Turn on power to the unit.
Wiring Diagrams
All excess wire should be pushed back into the wall as far as
possible. Excess wire inside the thermostat plastic case may
interfere with the air flow across the temperature sensor.
Thermostat Connections
C – 24V Common for Control Circuit
R – 24V Supply for Control Circuit
DX+ – Communication Terminal
DX- – Communication Terminal
S1, S2 – Remote Temperature Sensor (indoor or outdoor)
WARNING: Before installing thermostat, turn off
all power to unit. There may be more than one
power disconnect. Electrical shock can cause
personal injury or death.
C
P7
P1
–
R
W
C 24VAC (Common)
R 24VAC (Hot)
B- Communication
W1 (Optional)
Microprocessor Controller
Thermostat Connection
+A+ Communication
TPCM32U03/TPCM32U04
Monochrome Thermostats
C
P7
–
R
C 24VAC (Common)
R 24VAC (Hot)
DX- Communication
Microprocessor
Controller
Thermostat
Connection
+DX+ Communication
TPCC32U01
Color Touchscreen
Thermostat

5
INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT
IG1601EW 06/12 997-012330-3-R
Installer Settings
NOTE: These options are intended to be used by the installer.
End users are not advised to change or modify any of these
settings. Doing so may make your equipment stop working
properly and/or may void the warranty of the thermostat as well
as the equipment connected to the thermostat. To access the
installer setting menu, press and hold the upper left corner of the
screen for at least 5 seconds to enter the installer screen.
Equipment
The system will auto detect the type of equipment connected an
displays it on this screen.
SINGLE STAGE/MULTI STAGE
Single Stage – Used with heat pumps with PSC motors
Multi Stage – Used with heat pumps with ECM motors,
either Single Speed or Dual Capacity
Variable Speed – Used with heat pumps with variable
speed compressors
Thermostat Type
NORMAL/DUAL FUEL
Normal – used for normal operation
Dual Fuel – used on dual fuel systems; needs outdoor
sensor to lockout dual fuel
Restore Defaults
This will allow you to revert to the factory default settings.
Humidity Settings
If your system is setup with a humidifier, or you desire a
dehumidification option, select the appropriate setting.
HUMIDIFY
DEHUMIDIFY
BOTH (H or DH)
NONE
NOTE: If you have an outdoor sensor attached to the
thermostat, the Humidification setting is adjusted automatically
based on the outdoor temperature.
Humidify - Turns on the H output when the room humidity is
below the set point and MODE is set to HEAT, EHEAT,
or AUTO when Heating was the last mode run.
Dehumidify – Turns on the DH output when the room
humidity is above the set point and the MODE is set to
COOL or AUTO when Cool was the last mode run.
Both – HUMIDIFY operates in the HEAT mode and
DEHUMIDIFY operates in COOL mode.
NONE – Neither is active.
Installer Setting Page Two
Press NEXT button. It will bring you to the second page of
installer setting.
Cycles Per Hour
This feature will not allow more than the specified number of
equipment cycles per hour. Values can range from 4 or 6 (or 1
cycle every 15 minutes (default) or 1 cycle every 10 minutes, if
6 is set). Factory default setting is 4. This default selection will
provide optimum performance in nearly all installations.

6
INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT
IG1601EW 06/12 997-012330-3-R
Differential
This adjustment will vary the number of degrees, from the set
point, before a call for heating or cooling is made. Adjustments
can range between 0.5˚ and 4˚ differential. Default is 0.5˚ offset.
(If your set point is 70˚F in heating, your thermostat will not call
for heat until the temperature is 69.5˚F, with a 0.5 differential).
Smart Heat Staging (Heat Pump Only)
This delays 3rd stage heating for a set time. Options are ON
or OFF. Default is OFF. Range for this are 0-120 minutes in 5
minute increments. If set to ON, 30 minutes is the default time.
( If ‘ON’ is selected and the demand has not been satisfied the
thermostat will energize electric heat after the selected time has
expired regardless of demand.)
Smart Recovery
Smart recovery is a feature of your thermostat designed to
improve comfort by adjusting temperatures to achieve a room
temperature by the programmed time. When it’s time for a
programmed temperature change, smart recovery begins
working in advance, turning the system on and off as needed to
adjust the indoor temperature. During these transition periods,
you may notice that the actual temperature and your temperature
setting don’t match. That’s smart recovery in action, adjusting
temperatures in small increments for greater energy efficiency.
This is more energy efficient than simply allowing the system to
operate at full capacity until the desired temperature has been
met. Smart Recovery helps avoid excessive use of auxiliary heat
when recovering from night setback in the heating mode.
Electric Heat (Aux) Lockout
When an outdoor temperature sensor is installed, you can set it
up so the electric heat or Dual Fuel option doesn’t energize if the
outdoor temperature is above a certain temperature. Ranges for
this are NONE (default), 5˚F to 60˚F in 5˚ increments.
Cooling Lockout
When an outdoor temperature sensor is installed, it can be set
up so cooling option doesn’t energize if the outdoor temperature
is below a certain temperature. Ranges for this are NONE
(default), 45˚F, 50˚F, or 55˚F.
Remote Sensor
Allows selection of the remote sensor to determine indoor
temperature. Options are REMOTE SENSOR, AVERAGE, and
STAND ALONE. The REMOTE SENSOR is connected to the S1
and S2 on the thermostat terminals.
Compressor Satisfy
Normal – allows compressor downstaging from Y2 to Y1.
Recommended setting for most products.
Y2 Finish – Once the heat pump has engaged Y2 the
thermostat will not allow downstaging to Y1. The call is
satisfied in Y2.
Installer Setting Page Three
Press NEXT button. It will bring you to the installer setting page three.
Set Anticipator
This adjustment controls the sensitivity and cycle rate of the
thermostat. Higher numbers decrease the cycle rate. Lower
numbers increase the cycle rate. Default value is 0, and the
range is 0-4.
Accessories
Each of these options has settings for Cumulative Run Time
and Calendar Time. Messages will flash at the top of the Main
screen when these events are met to alert the owner that it is
time service these options.

7
INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT
IG1601EW 06/12 997-012330-3-R
Air Filter - Cumulative Run Time default is 1000 hours and
Calendar Time is 6 months. Values can range from
400-3600 hours for Cumulative Run Time (in 100 hour
increments), or Calendar Time can be set to OFF, or
3-48 months (in 3 month increments).
Humidifier - Cumulative Run Time default is 0 hours (OFF)
and Calendar Time is OFF. Values can range from
400-3600 hours for Cumulative Run Time (in 100 hour
increments), or Calendar Time can be set to OFF, or
3-24 months (in 3 month increments).
UV Lamp - Cumulative Run Time default is 0 hours (OFF)
and Calendar Time is OFF. Values can range from
400-3600 hours for Cumulative Run Time (in 100 hour
increments), or Calendar Time can be set to OFF, or
3-48 months (in 3 month increments).
Air Cleaner - Cumulative Run Time default is 0 hours (OFF)
and Calendar Time is OFF. Values can range from
400-3600 hours for Cumulative Run Time (in 100 hour
increments), or Calendar Time can be set to OFF, or
3-24 months (in 3 month increments).
To cancel the message, select the CANCEL.
Offsets
Temperature Offsets – This option allows calibration (or
deliberate miscalibration) of the room temperature
sensor(s). There are various reasons why the
displayed temperature would be adjusted to a higher
or lower value. NOTE: Do not adjust for 30 minutes
after installation because board may be heated by
handling. The selected number is the number of
degrees, plus or minus, which will be added to actual
temperature. The numbers can range between -5˚ and
+5˚. Default values are set to 0˚ offset.
Temperature Offset
Remote Indoor Offset (if sensor is attached)
Outdoor Offset (if sensor is attached)
Humidity Offset – This option allows calibration of the
humidity sensor. Adjustments can range between -10%
and +10%. Default is 0% offset.
Auto Changeover
With auto changeover, the thermostat automatically switches
itself from heating to cooling, or vise versa, based on the
setpoints. When setting up the thermostat you have to enter
both a cooling setpoint and a heating setpoint. The thermostat
will also prevent the user from setting the cooling setpoint lower
than the heating setpoint. Mode is set to AUTO for this operation
to work.
Auto Changeover Time – This setting sets the minimum off
time before the thermostat can change from one mode
to another. Default is 5 minutes. Range is from 0-120
minutes in 15 minute increments.
Auto or Manual Change – Default is AUTO. If MANUAL
is chosen, you will need to change from heating to
cooling or vise versa. When MANUAL is set, AUTO is
removed from the MODE screen as a choice.
USB
Allows Import and Export of Installer Settings, User Settings,
Program, and Dealer Details.

8
INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT
IG1601EW 06/12 997-012330-3-R
©2012 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and reserves the
right to change design and specications without notice.
NOTES
Table of contents
Other Water Furnace Thermostat manuals

Water Furnace
Water Furnace TPCM32U03 Manual

Water Furnace
Water Furnace IntelliZone2 ZoneStat User manual

Water Furnace
Water Furnace IntelliZone2 MasterStat Operation manual

Water Furnace
Water Furnace TPCC32U01 Manual

Water Furnace
Water Furnace IntelliZone User manual

Water Furnace
Water Furnace TP32U03 User manual

Water Furnace
Water Furnace TP32W03 User manual

Water Furnace
Water Furnace IntelliZone2 ZoneStat Manual

Water Furnace
Water Furnace IntelliZone2 MasterStat User manual

Water Furnace
Water Furnace IntelliZone2 MasterStat User manual