An Over-temperature
Limit Controller
With User Defined
Messages
Watlow’s SERIES 97 is a microprocessor-based controller
with a single input, second auxiliary input and four
outputs. Input one is used to measure temperature from a
sensor. Input two can be utilized as a remote reset switch
or a hardware lockout switch. With up to four outputs, the
controller is versatile in handling applications that require
a high/low limit, alarms, retransmit and communications.
The control is so user friendly that it can be set up to
display safety and limit messages created by the end
user to meet the exact application need.
The SERIES 97 limit controller is added to thermal
applications to limit over-temperature conditions.The
SERIES 97 limit controller provides safety assurance
against instances where a high temperature runaway
condition could occur from a shorted input sensor or an
output device that could fail in a closed position.
The SERIES 97 is recommended for any application
where thermal runaway could result in large product
scrap costs, affect operator safety, cause damage to
equipment or create a fire hazard.
The SERIES 97 is manufactured by ISO 9001 registered
Watlow Winona and reliably backed up by a three-year
warranty.
1241 Bundy Boulevard
Winona, Minnesota 55987-5580 USA
Phone: +1 (507) 454-5300
Fax: +1 (507) 452-4507
Internet: www.watlow.com
e-mail: info@watlow.com
WIN-97-1203
Registered Company
Winona, Minnesota USA
ISO 9001ISO 9001
Features and Benefits
Programmable messages
•Controller can be set up to display user
programmed limit message
NEMA 4X (IP65)
•Water and corrosion resistant; front panel
can be washed down
Microprocessor-based
•Accurate set point settings and quick
output response
Second auxiliary input
•Remote reset capability
Four outputs
•Handles high/low limit, alarms, communication
and retransmit requirements
Software and hardware lockouts
•High security
©2003 Watlow Electric Manufacturing Company Printed in the USA on Recycled Paper, 15 Percent Postconsumer Waste

Specifications
Controller
•Microprocessor-based
•Universal input 1, auxiliary input 2, 4 outputs
•Input sample period; Single input 10Hz (100 msec),
dual input 5Hz (200 msec) digital filter adjustable
•Display update; 2Hz (500 msec), time filter adjustable
•Input/Output/Communication isolation
•Displayed in °C, °F
Operator Interface
•Dual 4-digit LED displays: upper 10.2 mm (0.4 in.),
lower 6.2 mm (0.244 in.)
•Advance, Up Arrow, Down Arrow, Reset tactile keys
Standard Conditions For Specifications
•Ambient temperature 77°F (25°C) ±3°C, rated line
voltage, 50 to 60Hz, 0 to 90 percent RH
non-condensing,
15 minute warm-up
Universal Input 1
Thermocouple
•Type J, K, T, N, C (W5), E, PTII, D (W3), B, R, S
thermocouple types
•>20MΩinput impedance
•Maximum 20Ωsource resistance
•30mA open detection bias
RTD
•2- or 3-wire platinum, 100Ω
•JIS and DIN curves
•Whole or tenth degree indication
•150µA nominal RTD excitation current
Input 2
Event Input
•Contact or voltage
•20KΩinput impedance
•Voltage input: event high state 3 to 36VÎ(dc),
event low state 0 to 2VÎ(dc)
•Resistance/contact input: event high state > 23kΩ,
event low state 0 to 2kΩ
Output Types
Open Collector/Switched DC
•Open collector configuration:
Maximum voltage 42VÎ(dc)
Maximum current 200mA
Maximum “on” resistance 1.1Ω
Maximum offstate leakage current 100µA
•Switched dc configuration:
Switched dc supply voltage 22 to 28VÎ(dc)
dc supply current limited to 30mA
Solid State Relay
•Optically isolated
•Zero cross switched
•Without contact suppression
•Minimum load current 0.5mA rms
Solid State Relay (cont.)
•Maximum current 0.5A rms at 20 to 280VÅ(ac)
•Maximum offstate leakage current 10µA rms
•For resistive loads only, must use RC suppression for
inductive loads
Electromechanical Relay
•Form C contact configuration
•Minimum load current 10mA @ 5VÎ(dc)
•Rated resistive and inductive loads: 2A @ 250VÅ(ac)
or 30VÎ(dc) maximum
•Electrical life 100,000 cycles at rated current
•For resistive loads only, must use RC suppression for
inductive loads
Retransmit
•Range selectable: 0-20mA, 4-20mA, 0-5VÎ(dc),
1-5VÎ(dc), 0-10VÎ(dc)
•0to 10VÎ(dc) voltage output into a 1,000Ωminimum
load resistance
•0to 20mA current output into an 800Ωmaximum load
resistance
•Resolution:
Vdc ranges = 2.5mV nominal
mA ranges = 5µA nominal
•Calibration accuracy:
Vdc ranges = ±15mV
mA ranges = ±30µA
•Temperature stability 100ppm/°C
Communications
•EIA/TIA-485, EIA/TIA-232
•Opto-isolated
•ModbusTM RTU protocol
•1200, 2400, 4800, 9600, 19200 baud rates
•32 maximum units can be connected (With additional
485 repeater hardware, up to 247 units may be
connected)
Accuracy
•Input ranges
Type J: 0 to 750°C or 32 to 1382°F
Type K: -200 to 1250°C or -328 to 2282°F
Type T: -200 to 350°C or -328 to 662°F
Type N: 0 to 1250°C or 32 to 2282°F
Type E: -200 to 900°C or -328 to 1470°F
Type C(W5): 0 to 2315°C or 32 to 4200°F
Type D(W3): 0 to 2315°C or 32 to 4200°F
Type PTII: 0 to 1393°C or 32 to 2540°F
Type R: 0 to 1450°C or 32 to 2642°F
Type S: 0 to 1450°C or 32 to 2642°F
Type B: 870 to 1700°C or 1598 to 3092°F
DIN: -200 to 800°C or -328 to 1472°F
JIS: -200 to 630°C or -328 to 1166°F
ModbusTM is a trademark of AEG Schneider Automation.

Thermocouple Inputs
•Calibration accuracy ±0.1 percent of span ±1˚C at
standard conditions
Exceptions:
Type T; 0.12 percent of span for -200°C to -50°C
(-328°F to -58°F)
Types R and S; 0.15 percent of span for 0°C to 100°C
(32°F to 212°F)
Types B; 0.24 percent of span for 870°C to 1700°C
(1598°F to 3092°F)
•Accuracy span: 540°C (1000°F) minimum
•Temperature stability: ±0.1 degree per degree change
in ambient
RTD Inputs
•Calibration accuracy ±0.1 percent of span ±1˚C at
standard conditions
•Accuracy span: 540°C (1000°F) minimum
•Temperature stability: ±0.05 degree per degree change
in ambient
Agency Approvals
•FM Class 3545, File # J.I. 1B5A6.AF
•NEMA 4X, IP65
•CE 89/336/EEC, electromagnetic compatibility directive
CE 73/23/EEC, low-voltage directive
Terminals
•Touch safe
•22 to 12 AWG
Power
•100-240VÅ(ac) +10 percent, -15 percent; 50/60Hz,
±5 percent
•24-28VÅ(ac) or VÎ(dc) +10 percent, -15 percent;
50/60Hz, ±5 percent
•7.0VA maximum power consumption
•Data retention upon power failure via nonvolatile
memory
Operating Environment
•0to 65°C (32 to 149°F)
•0to 90 percent RH, non-condensing
•Storage temperature: -40 to 85°C (-40 to 185°F)
Dimensions
•Width 52 mm (2.05 in.)
•Height 52 mm (2.05 in.)
•Length 107 mm (4.2 in.)
•Depth behind panel surface 98.4 mm (3.875 in.)
•Approximate controller weight 0.2 kg (0.4 lbs)
Functionality Matrix
Type J: 1.0 0 to 815°C or 32 to 1500°F
0.1 0.0 to 815.0°C or 32.0 to 999.9°F
Type K: 1.0 -270 to 1370°C or -454 to 2500°F
0.1 -199.9 to 999.9°C or -199.9 to 999.9°F
Type T: 1.0 -270 to 400°C or -454 to 750°F
0.1 -199.9 to 400.0°C or -199.9 to 750.0°F
Type N: 1.0 0 to 1300°C or 32 to 2372°F
0.1 0.0 to 999.9°C or 32.0 to 999.9°F
Type E: 1.0 -270 to 800°C or -454 to 1470°F
0.1 -110.0 to 800.0°C or -199.9 to 999.9°F
Type C: 1.0 0 to 2315°C or 32 to 4200°F
0.1 0.0 to 999.9°C or 32.0 to 999.9°F
Type D: 1.0 0 to 2315°C or 32 to 4200°F
0.1 0.0 to 999.9°C or 32.0 to 999.9°F
Type PTII: 1.0 0 to 1395°C or 32 to 2543°F
0.1 0.0 to 999.9°C or 32.0 to 999.9°F
Type R: 1.0 0 to 1760°C or 32 to 3200°F
Type S: 1.0 0 to 1760°C or 32 to 3200°F
Type B: 1.0 0 to 1816°C or 32 to 3300°F
DIN 1.0 -200 to 800°C or -328 to 1472°F
0.1 -199.9 to 800.0°C or -199.9 to 999.9°F
JIS 1.0 -200 to 630°C or -328 to 1166°F
0.1 -199.9 to 630.0°C or -199.9 to 999.9°F
Allowable Operating Ranges
Note:These specifications are subject to change without prior notice.
High/ High/
232
Universal Low Low 485
Input Event Limit Alarm Retransmit Comm
Input 1
Input 2
Output 1
Output 2
Output 3
Output 4

Ordering Information
SERIES 97 9 7 - -
Microprocessor-based
1⁄16 DIN with universal input 1,
thermocouple and RTD.
Options include: software, power
supply, input 2, four outputs and
display color
Power Supply
A=100-240Vı(ac/dc)
B=24-28Vı(ac/dc)
Auxiliary Input 2
0=None
1=Event input
Limit Output 1
D=Electromechanical relay, Form C,
2A, without RC suppression
Alarm Output 2
A=None
C=Switched dc output/open collector
D=Electromechanical relay, Form C,
2A, without RC suppression
K=0.5A solid state relay without
RC suppression
Alarm Output 3
A=None
D=Electromechanical relay, Form C,
2A, without RC suppression
Auxiliary Output 4
A=None
D=Electromechanical relay, Form C,
2A, without RC suppression
R=232 Communications
U=485 Communications
M=Universal Retransmit, range selectable: 0-20mA,
4-20mA, 0-5VÎ(dc), 1-5VÎ(dc),
0-10VÎ(dc)
Software/Preset Parameters
00 = Standard software
Display/Overlay
Upper/Lower
RR = Red/Red display
RG = Red/Green display
GR = Green/Red display
GG = Green/Green display
234 % 96
1
52.070 mm
52.070 mm
Panel Cutout
44.958 mm x 44.958 mm
RESET
(2.050 in.)
(1.77 in. X 1.77 in.)
(2.050 in.)
107.747 mm
59.182 mm
98.425 mm
9.322 mm Customer's Front Panel
(4.242 in.)
(3.875 in.)
(2.330 in.)
(0.367 in.)
To be automatically connected to the nearest North American Technical and Sales Office call:
1-800-WATLOW2
International Technical and Sales Offices: Australia, +61 (39) 335-6449 • China, +86 (21) 6277-2138 • France, +33 (01) 3073-2425 •
Germany, +49 (0) 7253-9400-0 • Italy, +39 (02) 458-8841 • Japan, +81 (03) 5403-4688 • Korea, +82 (02) 575-9804 • Malaysia, +60 (4) 641-5977 •
Mexico, +52 (442) 217-6235 • Singapore, +65 6773-9488 • Spain, +34 916 759 192 • Sweden, +46 31 7014959 • Taiwan, +886 (0) 7-288-5168 •
Sweden, +46 31 7014959 • United Kingdom, +44 (0) 115-964-0777
Other manuals for 97 series
1
Table of contents
Other Watlow Temperature Controllers manuals

Watlow
Watlow 316-42-4-1 Instruction Manual

Watlow
Watlow L Series User manual

Watlow
Watlow EHG SL 10 User manual

Watlow
Watlow SD Series User manual

Watlow
Watlow Series 96 Use and care manual

Watlow
Watlow Sensors For High Temperature Heat Treating User manual

Watlow
Watlow EHG CLseries User manual

Watlow
Watlow EZ-ZONE ST Operating instructions