17
You also need to set simultaneously the
Central Unit in radio configuration mode
(see receiver Central Unit leaflet)
12 dEG Unit of the temperatures displayed
°C Celsius | °F Fahrenheit
13 hour Selection of the Time clock display
24H (24:00) | 12H (12:00 AM / PM)
14 dst: Daylight Summer time change
Summer <-> Winter
YES automatic change according to
date.
no no daylight summer time automatic
change.
15 AirC: Calibration of the internal probe
The calibration must be done after 1 day
working with the same setting tempera-
ture in accordance with the following
description:
Put a thermometer in the room at 1.5M
distance from the heater and check the
real temperature in the room after 1 hour.
When you enter on the calibration param-
eter no is displayed on the right to indicate
no calibration has made.
To enter the value shown on the thermom-
eter, use the LESS ( ) or MORE ( )keys
to enter the real value. Then, press ( ) key
to confirm. The value will be stored in the
internal memory.
If you need to erase a calibration press
LEFT ( ) or RIGHT ( ) keys during the
change, the old value will be erased and
the message no will be displayed.
16 ITCS Intelligent Temperature Control
System
YES | no
This function will activate your installation
in advance (2 hours maximum) to assure
the desired temperature at the hour pro-
grammed following your weekly program.
This automatic control system works in
the following way: When you start your
thermostatic head for the first time, it will
measure the time taken by your heater
to reach the set temperature. The ther-
mostatic head will re-measure this time
at each program change to compensate
external temperature change & influence.
You can now program your thermostatic
head without the need to adjust the
temperature in advance because it does
automatically this for you.
17 Win Open window
YES | no
This function, if activated, will detect the
room temperature decreasing for more
than 5°C and will automatically put the
setting to 7°C to save energy. (see sec-
tion 4.2 for more details)
18 Batt Battery level
Indicates the battery voltage value.
19 Soft Software version
Indicates the software version v X.X
20 ByPass
In some installation, a bypass loop
should be installed in the installation to
allow permanent flow of water. In only
one thermostatic head of your installa-
tion, you may set the minimum opening
of the valve. The regulation above this
threshold is maintained. By default, this
parameter is set to 0% (no bypass)
21 Clr: Reset to Factory setting
Press and maintain ( ) key during 2
seconds to reset Set points temperatures
and user parameters in this menu to fac-
tory default settings. User programs will
also be resetted.
Pay attention: Ensure that you have
all necessary elements to re-setup your
installation before using this function.
22 End: Exit the parameters menu
Press ( ) key to exit installation param-
eters menu and return to normal oper-
ation.